Technical Specifications SDF 14216

1. Technical Data of the Transformer


1.1 Type : YTR 55000/36
1.2 Rated Power : 55 MVA
1.3 No-load Voltages : 30/11 kV
1.4 Vector Group : YNd11
1.5 Voltage Regulation : LV + 2x2,5% Off-load
1.6 Cooling Type : ONAN
1.7 Frequency : 50 Hz
1.8 Short-circuit Impedance : 12 %
1.9 Applicable Standard : IEC 60076

2. Performance Values
2.1 No-load Losses : 39 kW
2.2 Short-circuit Losses : 227 kW
2.3 Auxiliary Losses at ONAN : N.A. kW
2.4 No-load Current : 0,29 %
2.5 Sound Pressure Level at 0,3m ONAN : 74 dBA
2.6 Temperature Rises (Oil/Winding) : 50/55 ˚K
Note: No-load losses are guaranteed at 1.0Un and short-circuit losses are guaranteed at nominal tap and rated power.

3. Design Ambient Conditions


3.1 Maximum Ambient Temperature : 50 ˚C
3.2 Operational Altitude : < 1000 m

4. Insulation Levels
Rated Lightining Impulse Withstand Rated Power Frequency Withstand
Voltage (kV, 1.2 | 50Hz) Voltage (kV, 1min | 50Hz)
4.1 HV : 170 70
4.2 HV-N : 170 70
4.3 LV : 75 28

5.Bushings
Type Termination
5.1 HV : DIN Porcelain Oil/Air Bushings
5.2 HV-N : DIN Porcelain Oil/Air Bushing
5.3 LV : DIN Porcelain Oil/Air Bushings

6. Dimensions
Total (mm) Transport (mm)
6.1 Width : 4200 1900
6.2 Length : 6500 4900
6.3 Height : 4800 3000

7. Weights
7.1 Total Weight : 70000 kg
7.2 Oil Weight : 13500 kg
7.3 Active Part : 35500 kg
7.4 Transport Weight (without oil and radiators) : 44000 kg
Note: All Weights and dimensions are approximate values.
Note: Accessories can only be supplied with the manufacturer standards.