C C W S: Hillers and Hilled Ater Ystems

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

CHILLERS AND CHILLED WATER SYSTEMS

Chapter-1 Introduction to Chilled Water Systems


၁.၁ What is heat? 1-1
၁.၁.၁ (Heat) 1-2
၁.၂ Unit of Refrigeration 1-2
၁.၃ Sensible Heat 1-3
၁.၄ Air Conditioning System 1-4
၁.၅ Decentralized Cooling and Heating Systems 1-6
၁.၅.၁ System Characteristics 1-6
၁.၅.၂ Decentralized System (Advantages) 1-7
၁.၅.၃ Decentralized System (Disadvantages) 1-8
၁.၆ Central Cooling and Heating Systems 1-8
၁.၆.၁ System Characteristics 1-9
၁.၆.၂ Central System (Advantages) 1-10
၁.၆.၃ Central System (Disadvantages) 1-10
၁.၆.၄ 1-11
၁.၇ (Design Considerations) 1-11
၁.၇.၁ Cooling and Heating Loads 1-11
၁.၇.၂ (Noise) (Vibration) 1-12
၁.၇.၃ (Space Considerations) 1-12
၁.၇.၄ Central Plant and Equipment 1-13
၁.၈ Chilled Water System 1-14
၁.၉ Overview of Chilled Water Plant Rooms 1-15
၁.၁၀ Circuit (Naming of Circuit) 1-16
၁.၁၁ Chilled Water Distribution System ႔ Chilled Water Circuit/Loop 1-17
၁.၁၂ Condenser Water Loop ႔ Condenser Water Circuit 1-17
၁.၁၃ Air Distribution System (Circuit/Loop) 1-18

Chapter-2 Vapor Compression Fundamental


၂.၁ Refrigeration (Vapor Compression Cycle) 2-2
၂.၁.၂ Refrigeration 2-2
၂.၂ Refrigeration System 2-4
၂.၂.၁ Vapor Compression Refrigeration Cycle Process 2-5
၂.၂.၂ Principles of Refrigeration 2-6
၂.၂.၃ Refrigeration cycle state 2-7
၂.၂.၄ Pressure-enthalpy (P-h) chart 2-8
၂.၃ Refrigeration System (၄) 2-11
၂.၃.၁ Evaporators 2-11
I
Chillers and Chilled Water Systems ႔

၂.၃.၂ Compressors 2-11


၂.၃.၃ Condensers 2-11
၂.၃.၄ Expansion Devices 2-12
၂.၄ What Are Refrigerants? 2-13
၂.၅ Refrigeration System 2-13
၂.၆ Low Pressure Side and High Pressure Side 2-14
၂.၇ Performance Of The Standard Vapor Compression Cycle 2-15
၂.၈ Actual Vapor Compression Cycle 2-16
၂.၉ Cycle Analysis and Calculations 2-16
၂.၁၀ Cycle with Subcooling and Superheat 2-19
၂.၁၁ – - 2-22
Table A-11 Saturated Refirgerant R134a Temperature Table 2-30
Table A-11 Saturated Refirgerant R134a Temperature Table (Continued) 2-31
Table A-12 Saturated Refirgerant R134a Pressure Table 2-32
Table A-13 Superheated Refirgerant R134a Table 2-33
Table A-13 Superheated Refirgerant R134a Table (Continued) 2-34
Pressure-Enthalpy Diagram for HFC-134a (SI Units) 2-35
Pressure-Enthalpy Diagram for HFC-134a (English Units) 2-36

Chapter-3 Vapor Compression Cycle Theory and Calculation


၃.၁ Vapor Compression Refrigeration Cycle 3-1
၃.၂ Reversed Carnot Cycles 3-1
၃.၃ Ideal Vapor Compression Refrigeration Cycles 3-3
၃.၃.၁ Ideal Vapor Compression Refrigeration Cycles (၁) 3-3
၃.၃.၂ Ideal Vapor Compression Refrigeration Cycles (၂) 3-4
၃.၃.၃ Ideal Vapor Compression Refrigeration Cycle (၁) 3-5
၃.၃.၄ Ideal Vapor Compression Refrigeration Cycle (၂) 3-9
၃.၃.၅ Ideal Vapor Compression Refrigeration Cycle (၃) 3-12
၃.၃.၆ Ideal Vapor Compression Refrigeration Cycle (၄) 3-14
၃.၃.၇ Ideal Vapor Compression Refrigeration Cycle (၅) 3-15
၃.၃.၈ Ideal Vapor Compression Refrigeration Cycle (၆) 3-16
၃.၄ Ideal Cycles Actual Cycles ႔ 3-17
၃.၅ Practical Considerations and COP 3-18
၃.၆ Refrigeration and Heat Pumps 3-20
၃.၇ Actual Vapor Compression Refrigeration Cycle 3-22
၃.၇.၁ Actual Vapor Compression Refrigeration Cycle 3-24
၃.၇.၂ Heat Rejection by A Refrigerator 3-25
၃.၇.၃ Vapor Compression Refrigeration Cycle (၁) 3-26
၃.၇.၄ Vapor Compression Refrigeration Cycle (၂) 3-27
၃.၇.၅ Vapor Compression Refrigeration Cycle (၃) 3-30
၃.၇.၆ Vapor Compression Refrigeration Cycle (၄) 3-31

II

၃.၇.၇ Vapor Compression Refrigeration Cycle (၅) 3-32


၃.၇.၈ Vapor Compression Refrigeration Cycle (၆) 3-34
၃.၇.၉ Vapor Compression Refrigeration Cycle (၇) 3-35
၃.၈ Cascade Refrigeration Cycles 3-36
၃.၈.၁ Compound Systems 3-39
၃.၉ 3-39
၃.၁၀ Problems 3-44

Chapter-4 Refrigerants
၄.၁ Refrigerant 4-2
၄.၁.၁ ႔ Refrigerant 4-2
၄.၁.၂ Halocarbon 4-2
၄.၁.၃ Azeotropic Refrigerants 4-3
၄.၁.၄ Zeotropic Refrigerants 4-3
၄.၁.၅ Organic compound 4-4
၄.၁.၆ Inorganic mixture 4-4
၄.၂ Refrigerant Color Codes 4-4
၄.၂.၁ CFCs ႔ 4-4
၄.၂.၂ HCFCs ႔ 4-5
၄.၂.၃ HFCs ႔ 4-5
၄.၃ Refrigerant 4-7
၄.၄ Refrigerant 4-10
၄.၅ Nomenclature 4-11
၄.၆ Refrigerant 4-13
၄.၆.၁ R-11 Trichloromonofluoromethane - CCL3F 4-14
၄.၆.၂ R-12 Dichlorodifluoromethane - CCL2F2 4-14
၄.၆.၃ R-22 Monochlorodifluoromethane - CHCLF2 4-14
၄.၆.၄ R-500 (R - 152 a + R - 12) (CCL2F2/CH3CHF2) 4-14
၄.၆.၅ R - 502 (R - 22 + R - 115) (CHCLF2/ CCL2CF3) 4-14
၄.၆.၆ R-744 (Carbondioxide CO2) 4-15
၄.၆.၇ R-717 (Ammonia -NH3) 4-15
၄.၆.၈ R134 a R407C 4-15
၄.၆.၉ R407C 4-16
၄.၆.၁၀ R404A 4-16
၄.၆.၁၁ R290 Propane 4-16
၄.၆.၁၃ R744 ( (CO2) ) 4-16
၄.၆.၁၄ Sulfur Dioxide (SO2) 4-16
၄.၆.၁၅ R-718 4-16
၄.၇ Equivalent R-11 4-17
၄.၈ Virgin Refrigerant and Reconditioning Refrigerant 4-17
၄.၉ Selection of Refrigerants 4-17

III
Chillers and Chilled Water Systems ႔

၄.၁၀ Refrigerant (Selection of the Right Refrigerant) 4-19


၄.၁၁ Refrigerant - HFC-134a 4-19
၄.၁၂ Positive Pressure Refrigerant 4-22
၄.၁၂.၁ Smaller Footprint ( ) 4-22
၄.၁၂.၂ ) 4-22
၄.၁၂.၃ ) 4-22
၄.၁၃ Refrigerant Safety Group 4-23
၄.၁၄ Safety Requirements 4-23
၄.၁၄.၁ (Thermal Decomposition) 4-24
၄.၁၄.၂ Leakage Detection 4-26
၄.၁၄.၃ (Safety) 4-26
၄.၁၅ (Green House Effect) 4-27
၄.၁၆ (Ozone Layer) 4-28
၄.၁၆.၁ (ODP) 4-30
၄.၁၇ 4-31
၄.၁၈ (UV Index) 4-32
၄.၁၈.၁ (UV Index) 4-33
၄.၁၈.၂ 4-33
၄.၁၉ 4-33
၄.၁၉.၁ 4-34
၄.၂၀ 4-35
၄.၂၁ 4-35

Chapter-5 Heat Exchangers


၅.၁ (Fundamentals) 5-2
၅.၂ Heat Exchanger 5-3
၅.၂.၁ Shell and Tube Heat Exchangers 5-3
၅.၂.၂ Plate Heat Exchangers 5-4
၅.၃ Heat Exchanger (Components) 5-6
၅.၃.၁ Shell and Tube Components 5-6
၅.၃.၂ Plate Heat Exchanger Component 5-7
၅.၄ (Application) 5-8
၅.၅ (Selection Criteria) 5-8
၅.၅.၁ Thermal/Mechanical Design 5-9
၅.၅.၂ Thermal Performance 5-9
၅.၅.၃ 5-9
၅.၅.၄ (Pressure Drop) 5-9
၅.၅.၅ 5-9
၅.၅.၆ (Cost) 5-10
၅.၅.၇ Serviceability 5-10
၅.၅.၈ (Space Requirements) 5-10

IV

၅.၅.၉ Steam 5-10


၅.၆ (Installation) 5-10
၅.၆.၁ Control 5-10
၅.၆.၂ Piping 5-10
၅.၆.၃ Pressure Relief 5-10
၅.၆.၄ Flow Path 5-11
၅.၆.၅ Condensate Removal 5-11
၅.၆.၆ Insulation 5-11
၅.၇ (၇) 5-11
၅.၇.၁ Heat Exchanger Tube Diameter 5-11
၅.၇.၂ Thickness of the Tube 5-11
၅.၇.၃ Heat Exchanger Shell Diameter and Tube Length 5-11
၅.၇.၄ Tube Corrugation 5-11
၅.၇.၅ Tube Layout 5-12
၅.၇.၆ Tube Pitch 5-12
၅.၇.၇ Heat Exchanger Baffles 5-12

Chapter-6 Overview of Chillers


၆.၁ Chiller 6-1
၆.၁.၁ Vapor Compression Chiller Versus Absorption Chiller 6-2
၆.၁.၂ Electric Chillers Vs Non-electric Chillers 6-2
၆.၁.၃ Engine Drive Chillers 6-3
၆.၁.၄ Steam Turbine Driven Chillers 6-3
၆.၁.၅ Air Cooled Versus Water Cooled 6-3
၆.၁.၆ Gear Drive Versus Direct Drive 6-6
၆.၁.၇ Open Drive Versus Hermetic 6-6
၆.၁.၈ Fixed Orifice Versus Float Valve 6-6
၆.၁.၉ Falling Film Evaporator Versus Flooded Evaporator 6-7
၆.၂ Factors Affecting Performance of Refrigeration Systems 6-7
၆.၂.၁ Evaporating and Condensing Temperatures 6-7
၆.၂.၂ Effect of Condenser and Evaporator on System Efficiency 6-8
၆.၂.၃ Operating Speeds 6-8
၆.၂.၄ Chiller ႔ Coefficient of Performance (COP) 6-9
၆.၂.၅ 6-9
၆.၂.၆ (Reliability) (Maintenance) 6-9
၆.၂.၇ 6-10
၆.၂.၈ (Field Serviceability) 6-10
၆.၂.၉ (Stock Availability of Spares) 6-10
၆.၂.၁၀ Performance Specifications: 6-10
၆.၃ 6-11
၆.၄ Positive Pressure Machine (R134a) Negative Pressure Machine (R 123 Chiller) 6-12

V
Chillers and Chilled Water Systems ႔

၆.၅ Chiller 6-14


၆.၅.၁ Defining Chiller Performance Requirement 6-14
၆.၅.၂ Economic Evaluation of Chiller Systems 6-15
၆.၅.၃ (First Cost) 6-16
၆.၅.၄ (Annual Recurring Costs) 6-16
၆.၅.၅ Procurement Strategies 6-17

Chapter-7 Condensers and Evaporators


၇.၁ Heat Rejection 7-1
၇.၂ Condenser 7-2
၇.၂.၁ Condenser 7-3
၇.၃ Water Cooled Condensers 7-4
၇.၄ Air Cooled Condensers 7-6
၇.၄.၁ Air Cooled Condenser (Advantages) 7-7
၇.၄.၂ Air Cooled Condenser (Disadvantages) 7-7
၇.၄.၃ Application ၊ Selection and Maintenance of Remote Air Cooled Condensers 7-7
၇.၄.၄ Air Cooled Condenser Controls 7-8
၇.၅ Evaporative condenser 7-9
၇.၅.၁ Basic Operating Principles 7-9
၇.၅.၂ Common Configurations of Condenser 7-9
၇.၅.၃ Forced-Draft, Axial Fan Condensers 7-9
၇.၅.၄ Induced Draft, Axial Fan Condensers 7-10
၇.၅.၅ Forced Draft, Centrifugal Fan Condensers 7-10
၇.၆ Evaporative Cooling 7-10
၇.၆.၁ Evaporative Condensers 7-11
၇.၆.၂ Cooling Towers 7-12
၇.၆.၃ Water Cooling 7-13
၇.၆.၄ Capacity Control 7-13
၇.၆.၅ Capacity Ratings 7-14
၇.၇ Methods of Refrigerant Feed 7-14
၇.၇.၁ Gravity Feed Operation 7-14
၇.၇.၂ Recirculated ႔ Overfeed 7-15
၇.၇.၃ Flooded Evaporator 7-15
၇.၇.၄ Direct Expansion (DX) 7-17
၇.၈ Evaporator 7-18
၇.၈.၁ Evaporator 7-19
၇.၈.၂ Dry Expansion Type 7-21
၇.၈.၃ Forced Through Type Evaporators 7-21
၇.၈.၄ Pump Circulation Type Evaporators 7-21
၇.၈ Evaporator 7-18
၇.၈.၁ Evaporator 7-19

VI

၇.၈.၂ Dry Expansion Type 7-21


၇.၈.၃ Forced Through Type Evaporators 7-21
၇.၈.၄ Pump Circulation Type Evaporators 7-21
၇.၉ Evaporator Fan Liquid Cooling 7-21
၇.၁၀ Types of Refrigeration Evaporators 7-22
၇.၁၀.၁ Evaporator 7-22
၇.၁၀.၂ Bare Tube Evaporators 7-23
၇.၁၀.၃ Plate Type Evaporators 7-23
၇.၁၀.၄ Finned Evaporators 7-23
၇.၁၀.၅ Shell and Tube Evaporators 7-24
၇.၁၁ Condenser Small Temperature Difference 7-24
၇.၁၁.၁ Condenser Approach Temperature 7-25
၇.၁၁.၂ Evaporator Approach Temperature 7-26
၇.၁၂ Water Box Design Pressure 7-27

Chapter-8 Capacity Control of Refrigeration Systems


၈.၁ Compressor Control ၊ Chiller Control and Chilled Water Plant Control 8-1
၈.၁.၁ Individual Compressor Capacity Control 8-1
၈.၁.၂ Individual Chiller Control 8-3
၈.၁.၃ Chilled Water Plant Control 8-4
၈.၁.၄ Capacity Control for Varying Loads to Provide Better Efficiency 8-5
၈.၁.၅ Refrigerant Flow Control 8-6
၈.၂ Refrigerant Control Devices 8-6
၈.၂.၁ Hand Expansion Valve 8-7
၈.၂.၂ Constant Pressure Expansion Valves ႔ Automatic Expansion Valve (AEV) 8-8
၈.၂.၃ Thermostatic Expansion Valves (TEV) 8-10
၈.၂.၄ Thermal Electric Expansion Valve ႔ Electric Expansion Valve 8-13
၈.၂.၅ Electronic Expansion Valves 8-13
၈.၂.၆ Capillary Tubes 8-14
၈.၂.၇ Capillary Tubes and Restrictor 8-16
၈.၂.၈ Float Valves 8-17
၈.၂.၉ Low Pressure Side Float Valve 8-17
၈.၂.၁၀ Lower Pressure Float Valve and Switch 8-18
၈.၂.၁၁ High Pressure Side Float 8-19
၈.၂.၁၂ High Pressure Float Valves 8-20
၈.၃ Safety Controls 8-21
၈.၃.၁ Safety Cutouts 8-22
၈.၃.၂ Interlocks 8-22
၈.၃.၃ Chiller Control Load Limitation Control 8-23

VII
Chillers and Chilled Water Systems ႔

Chapter-9 Refrigeration Compressors


၉.၁ Positive-Displacement Compressors 9-3
၉.၂ Dynamic Compressors 9-4
၉.၂.၁ Centrifugal Compressors Function Based on Principles 9-4
၉.၃ Open Compressors ၊ Hermetic Compressors Semi-hermetic Compressors 9-4
၉.၃.၁ Open Compressors 9-4
၉.၃.၂ Hermetic Compressors 9-5
၉.၃.၃ Semi-hermetic Compressors 9-6
၉.၄ Performance 9-7
၉.၅ Ideal Compressor 9-8
၉.၆ Actual Compressor 9-9
၉.၇ Volumetric Efficiency 9-10
၉.၈ Compressor Efficiency ၊ Subcooling Superheating 9-11
၉.၉ Total Heat Rejection 9-12
၉.၁၀ Compressor Protection 9-13
၉.၁၁ Testing and Operating Requirements 9-16
၉.၁၂ Compressor Selection Criteria 9-18
၉.၁၃ Comparison Between Four Common Type of Refrigeration Compressors 9-19

Chapter-10 Auxiliary Devices


၁၀.၁ Control Devices 10-1
၁၀.၂ Receivers 10-1
၁၀.၃ Filter Dryers 10-3
၁၀.၃.၁ Dryers 10-4
၁၀.၄ Accumulators 10-4
၁၀.၅ Injection Capillary 10-5
၁၀.၆ Low Pressure Control Valves 10-6
၁၀.၇ Distributors 10-6
၁၀.၈ Suction to Liquid Heat Exchangers or Gas/Liquid Heat Exchangers 10-6
၁၀.၉ Pre-coolers 10-7
၁၀.၁၀ Mufflers 10-7
၁၀.၁၁ Solenoid Valves 10-7
၁၀.၁၂ Check Valves 10-8
၁၀.၁၄ Service Valves 10-9
၁၀.၁၅ Expansion Valve (Bypass) 10-9
၁၀.၁၆ Vapor Charging Valves 10-9
၁၀.၁၇ Liquid Charging Valves 10-9
၁၀.၁၈ Purge Valves 10-9
၁၀.၁၉ Suction Strainers 10-9
၁၀.၂၀ Liquid Sight Glass 10-10
၁၀.၂၁ Oil Separators 10-10

VIII

၁၀.၂၂ Oil Rectifiers 10-11


၁၀.၂၃ Oil Coolers 10-11
၁၀.၂၄ Purge Units 10-11
၁၀.၂၅ Vibration Absorbers 10-12
၁၀.၂၆ Crankcase Heaters 10-12
၁၀.၂၇ Relief Valves 10-12
၁၀.၂၈ Safety Devices (Pressure Switch) 10-13
၁၀.၂၉ High Pressure Switch (HPS) 10-13
၁၀.၃၀ Low Pressure Switch (LPS) 10-14
၁၀.၃၁ Condenser Pressure Regulators 10-14
၁၀.၃၂ Oil Pressure Switches (OPS) 10-14
၁၀.၃၃ Fusible Plugs 10-15
၁၀.၃၄ Safety Valves or Relief Valves 10-15

Chapter-11 Chiller Starters


၁၁.၁ Chiller Starters 11-1
၁၁.၁.၁ (Purpose of Starters) 11-1
၁၁.၁.၂ Starter Drive 11-4
၁၁.၃ Electro-Mechanical Starters 11-5
၁၁.၃.၁ Across the Line Starter (ACL) ႔ Direct On Line(DOL) 11-5
၁၁.၃.၂ Star-Delta ႔ Wye-Delta Starter (Closed Transition) 11-6
၁၁.၃.၃ Auto Transformer Starters(ATS) 11-7
၁၁.၄ Electronic Solid State Starters 11-8
၁၁.၄.၁ Electronic Solid State Starters Overview 11-8
၁၁.၄.၂ Electronic Solid State Starters Starting Current Profile 11-10
၁၁.၄.၃ Electronic Solid State Starters Benefits 11-10
၁၁.၄.၄ Electronic Solid State Starter Recommendations 11-11
၁၁.၅ Variable Speed Drive(VSD) 11-11
၁၁.၅.၁ Variable Speed Drive 11-11
၁၁.၅.၂ VSD Starting Profile 11-14
၁၁.၅.၃ Variable Speed Drive Benefits 11-15
၁၁.၆ Demand Charge 11-16
၁၁.၆.၁ Demand Limiter 11-17
၁၁.၇ Motor Torque Speed Curves 11-17
၁၁.၈ Safety Controls ၊ Accessories and Options 11-18
၁၁.၈.၁ “ – w V ” 11-18
၁၁.၈.၂ “ –H V ” 11-19
၁၁.၈.၃ Safety Controls 11-19

IX
Chillers and Chilled Water Systems ႔

Chapter-12 Oil in Refrigerant Circuits


၁၂.၁ 12-1
၁၂.၁.၁ Oil in Refrigeration System 12-2
၁၂.၁.၂ General Classification of Oils 12-2
၁၂.၂ Requirements and Characteristics 12-2
၁၂.၃ ႔ (Moisture and Air Contamination) 12-5
၁၂.၄ Oil Separators 12-7
၁၂.၅ Oil Circulation 12-8
၁၂.၆ Lubricating Oils and Their Effects 12-9
၁၂.၇ Oil System for Compressor 12-11
၁၂.၇.၁ Reciprocating Compressors 12-11
၁၂.၇.၂ Rotary Compressors 12-11
၁၂.၇.၃ Centrifugal Compressors 12-11
၁၂.၇.၄ Helical Screw Compressors 12-11
၁၂.၇.၅ Scroll Compressors 12-11
၁၂.၈ Promoting Oil Return 12-12

Chapter-13 Reciprocating Compressors and Chillers


၁၃.၁ Introduction 13-1
၁၃.၂ (၃) 13-2
၁၃.၂.၁ Enclosed Motor ႔ Hermetic Compressors 13-3
၁၃.၂.၂ Semi-Hermetic Compressors 13-5
၁၃.၂.၃ Open Compressors 13-5
၁၃.၃ Reciprocating Refrigeration System Components and Accessories 13-6
၁၃.၃.၁ Cylinder and Cylinder Arrangement 13-6
၁၃.၃.၂ Arrangement 13-7
၁၃.၃.၃ Piston and Piston Ring 13-7
၁၃.၃.၄ Cylinder Block and Piston 13-8
၁၃.၃.၅ Connection Rods 13-8
၁၃.၃.၆ Valves and Valve Plates 13-10
၁၃.၃.၇ Crankshaft 13-10
၁၃.၃.၈ Crankshaft Seal 13-10
၁၃.၃.၉ Suction and Discharge Valves 13-11
၁၃.၃.၁၀ Crankcase Heater 13-11
၁၃.၃.၁၁ Liquid Receiver 13-11
၁၃.၃.၁၂ Liquid Suction Heat Exchanger (LSHE) 13-12
၁၃.၃.၁၃ Filter Dryer and Strainer 13-13
၁၃.၃.၁၄ Reed Valve Plate 13-14
၁၃.၃.၁၅ Service Valves 13-15
၁၃.၄ (Compression Process) 13-16
၁၃.၄.၁ Clearance Area 13-19

X

၁၃.၄.၂ Multi- Cylinder Compressors 13-19


၁၃.၄.၃ Cooling and Protection 13-20
၁၃.၅ Compressor Efficiency 13-22
၁၃.၆ Reciprocating Chiller 13-23
၁၃.၅ Compressor Efficiency 13-22
၁၃.၆.၁ Types of Reciprocating Refrigeration Systems 13-25
၁၃.၆.၂ Liquid Overfeed Reciprocating Refrigeration Systems 13-27
၁၃.၆.၃ Real Cycle of a Single-Stage Reciprocating Refrigeration System 13-28
၁၃.၇ Reciprocating Refrigeration System Oil Lubrication 13-28
၁၃.၇.၁ Strainers ၊ Lubrication and Crankcase Heater 13-29
၁၃.၈ Capacity Control of Reciprocating Compressors 13-29
၁၃.၈.၁ Cycling (on/off) With or Without Multiple Compressors 13-30
၁၃.၈.၂ Cylinder Unloader 13-31
၁၃.၈.၃ Hot gas bypass 13-32
၁၃.၈.၄ Speed Control 13-33
၁၃.၈.၅ Return Water Control Leaving Water Control 13-33
၁၃.၉ Reciprocating Compressor Startup Sequence 13-33
၁၃.၁၀ Reciprocating Refrigeration Systems Testing Standards 13-34

Chapter-14 Screw Compressors and Chillers


၁၄.၁ Screw Compressors 14-1
၁၄.၁.၁ Single Screw Compressors 14-2
၁၄.၁.၂ Twin Screw Compressors 14-4
၁၄.၂ Screw Chillers 14-5
၁၄.၃ Screw Chiller Refrigerant Circuit 14-8
၁၄.၄ Screw Compressor 14-8
၁၄.၅ Capacity Control 14-12
၁၄.၅.၁ Slide Valve 14-14
၁၄.၅.၂ VSD Controls 14-15
၁၄.၆ Oil System 14-15
၁၄.၇ Power Up to Starting 14-17
၁၄.၇.၁ Trane RTHD screw chiller Power Up to Starting 14-18
၁၄.၇.၂ Stopped to Starting 14-18
၁၄.၇.၃ Normal Shutdown to Stopped 14-18
၁၄.၈ 23XRV Water Cooled Screw Compressor (VSD) 14-20
၁၄.၉ Air Cooled VSD Screw Chillers 14-22

Chapter-15 Centrifugal Compressors and Chillers


၁၅.၁ Dynamic Compressors 15-1
၁၅.၂ Centrifugal Compressors 15-3
၁၅.၂.၁ Centrifugal Compressor Theory 15-8

XI
Chillers and Chilled Water Systems ႔

၁၅.၂.၂ Centrifugal Chiller 15-10


၁၅.၃ System Components 15-10
၁၅.၃.၁ Evaporator 15-10
၁၅.၃.၂ Condenser 15-10
၁၅.၃.၃ Vessel Pass Arrangements 15-10
၁၅.၃.၄ Flash Cooler 15-11
၁၅.၃.၅ Orifice Plates or Float Valves 15-11
၁၅.၃.၆ Variable Orifice 15-12
၁၅.၃.၇ Purge Unit 15-12
၁၅.၄ Water Cooled Centrifugal Chiller 15-14
၁၅.၅ Performance Rating Conditions 15-15
၁၅.၆ Centrifugal Compressor Performance Map 15-17
၁၅.၆.၁ Centrifugal Compressor Map at Variable Speed 15-17
၁၅.၆.၁ Velocity Components 15-19
၁၅.၇ Surge of Centrifugal Compressors 15-19
၁၅.၇.၁ Two-Stage Compressors Surge Less and Later 15-21
၁၅.၇.၂ Prevention of Surge 15-22
၁၅.၇.၃ Rotating stall and Surge of Centrifugal Chillers 15-22
၁၅.၇.၄ Impeller and Vane Diffuser Stall 15-23
၁၅.၇.၅ Vane Less Diffuser Stall 15-23
၁၅.၇.၆ Compressor Surge and Stall 15-23
၁၅.၈ Capacity Control of Centrifugal Chillers 15-25
၁၅.၈.၁ Required System Head at Part-Load Operation 15-27
၁၅.၈.၂ Capacity Control Using Inlet Vanes 15-27
၁၅.၈.၃ Inlet Guide Vane (Pre-Rotation Vane) 15-28
၁၅.၈.၄ Capacity Control by Variable Speed 15-29
၁၅.၈.၅ Comparison Between Inlet Guide Vanes and Variable Speed 15-30
၁၅.၉ Oil System 15-30
၁၅.၁၀ Functional Controls and Optimizing Controls 15-31
၁၅.၁၀.၁ Chilled Water Leaving Temperature Control 15-31
၁၅.၁၀.၂ Condenser Water Temperature Control 15-32
၁၅.၁၁ Sequence of Operation of A Typical Centrifugal Chiller 15-32
၁၅.၁၂ System Balance at Full Load 15-33
၁၅.၁၂.၁ Evaporating and Condensing Temperatures at Part-Load Operation 15-33
၁၅.၁၃ Typical 19XR Components 15-35
၁၅.၁၄ Turbo Compressors 15-41

Chapter-16 Scroll Compressors and Chillers


၁၆.၁ Rotary Compressors 16-1
၁၆.၂ Scroll Compressors 16-2
၁၆.၃ Scroll Compressor 16-5

XII

၁၆.၄ 16-6
၁၆.၅ Two Step Capacity Control for Scroll Compressors 16-8
၁၆.၆ Scroll Compressor (Advantages) 16-9
၁၆.၇ Sliding and Rotary Vane Compressor 16-10
၁၆.၇.၁ (Advantages) (Disadvantages) 16-11
၁၆.၇.၂ Capacity Control 16-12

Chapter-17 Chilled Water System Configurations


၁၇.၁ Chilled Water Plant Basics 17-1
၁၇.၁.၁ Chilled Water Temperatures 17-1
၁၇.၁.၂ Effect of Chilled Water Temperature 17-2
၁၇.၁.၃ Effect of Chilled Water Flow Rate 17-2
၁၇.၁.၄ Condenser Water Temperature 17-2
၁၇.၁.၅ Effect of Condenser Water Temperature 17-2
၁၇.၁.၇ Effect of Condenser Water Flow Rate 17-2
၁၇.၁.၈ Chilled Water and Condenser Water Flow Rates 17-3
၁၇.၁.၁ Chilled Water Temperatures 17-1
၁၇.၂ Single Chiller System 17-3
၁၇.၂.၁ Single Chiller System Advantages and Disadvantages 17-4
၁၇.၃ Multiple Chiller System 17-4
၁၇.၄ Parallel Chillers System 17-5
၁၇.၅ Primary Only System 17-5
၁၇.၅.၁ Primary Only System with Common Header 17-6
၁၇.၅.၂ Primary Only System with Dedicated Pump 17-9
၁၇.၅.၃ Primary-Only System 17-9
၁၇.၆ Primary - Secondary System 17-10
၁၇.၆.၁ Dedicated Pump and Manifold Pump (Common Header) 17-10
၁၇.၆.၂ Dedicated Pumps at Production Loop or Primary Chilled Water Circuit/Loop 17-12
၁၇.၆.၃ Bypass Line ႔ Decouple Line sizing 17-13
၁၇.၆.၄ Bypass Control Problems 17-14
၁၇.၆.၅ Production Loop/Circuit ႔ Primary Loop/Circuit 17-15
၁၇.၆.၆ Secondary Loop Flow Control 17-16
၁၇.၆.၇ Secondary (Demand) Flow Primary (Supply) Flow ႔ 17-20
၁၇.၆.၈ Secondary (Supply) Flow Primary (Demand) Flow 17-20
၁၇.၆.၉ Secondary (Supply) Flow Primary (Demand) Flow 17-22
၁၇.၆.၁၀ Primary-secondary system 17-22
၁၇.၆.၁၁ Primary/Secondary System (Disadvantages) 17-23
၁၇.၇ Variable Flow Primary 17-24
၁၇.၇.၁ Variable Primary Flow Only (VPF) Advantages 17-25
၁၇.၇.၂ Variable Primary Flow Only (VPF) Disadvantages 17-26
၁၇.၈ Condenser Water Circuit 17-26

XIII
Chillers and Chilled Water Systems ႔

၁၇.၈.၁ Refrigerant Head Pressure Control 17-27


၁၇.၈.၂ w 17-28
၁၇.၉ Low Delta – T Syndrome 17-29
၁၇.၉.၁ Low Delta- Δ 17-29
၁၇.၉.၂ Chiller Performance 17-30
၁၇.၁၀ Series Chiller System 17-30
၁၇.၁၀.၁ Advantages and Disadvantages of Series Chillers 17-31
၁၇.၁၀.၂ Series Counter Flow 17-31
၁၇.၁၁ Chiller Staging 17-32

Chapter - 18 Chillers Performance Rating


၁၈.၁ Chiller Efficiency 18-1
၁၈.၁.၁ kW/RT 18-2
၁၈.၁.၂ Coefficient of Performance (COP) 18-2
၁၈.၁.၃ Energy Efficiency Ratio (EER) 18-3
၁၈.၂ Integrated Part Load Value (IPLV) Non Standard Part Load Value (NPLV) 18-4
၁၈.၃ Performance Characteristics and Efficiency Ratings 18-5
၁၈. ၃.၁ Performance Issues 18-5
၁၈.၄ Chiller Efficiency Ratings 18-6
၁၈.၅ Cooling Capacity Formulae 18-7
၁၈.၆ AHRI Conditions Vs Low Flow Conditions 18-8
၁၈.၇ ASHRAE/IESNA Standard 90.1.2004 18-10
၁၈.၈ Air Conditioning Codes & Standards in Singapore 18-11
၁၈.၉ International Air Conditioning Codes & Standards 18-11

Chapter-19 Design Processes and Chillers Selection


၁၉.၁ Plant 19-1
၁၉.၁.၁ Determine Requirements 19-1
၁၉.၁.၂ (Design Processes) 19-1
၁၉.၂ Chiller (Chiller Sizing) 19-4
၁၉.၂.၁ Chiller Plant Design Consideration ႔ Chiller Selection 19-5
၁၉.၂.၂ Chiller Selection – Chiller Sizing (Chiller ) 19-6
၁၉.၃ chiller 19-7
၁၉.၃.၁ Chiller Plant Retrofit Considerations 19-7
၁၉.၃.၂ Peak Load ႔ Maximum Load 19-8
၁၉.၃.၃ Off Peak Load 19-8
၁၉.၃.၄ Night load 19-9
၁၉.၃.၅ Weekend load 19-9
၁၉.၄ 19-10
၉.၅.၁ Cooling Load Chiller 19-11
၁၉.၆ Water Cooled Centrifugal Chiller Technical Data 19-13

XIV

၁၉.၇ Summary of design considerations for refrigeration systems 19-15

Chapter-20 Efficiency and Energy Saving


၂၀.၁ Chiller Efficiencies 20-1
၂၀.၁.၁ Chiller Efficiency 20-1
၂၀.၁.၂ (Potential Energy Efficiency Measures) 20-1
၂၀.၂ Single Stage Chiller 20-6
၂၀.၃ w (Major Causes) 20-7
၂၀.၃.၁ Chilled Water – Low Delta T Syndrome 20-7
၂၀.၄ Energy Efficiency 20-9
၂၀.၅ 20-13
၂၀.၅.၁ Chilled Water Reset 20-13
၂၀.၅.၂ Chiller ၌ Refrigerant 20-14
၂၀.၅.၃ Refrigerant (Leak) 20-15
၂၀.၅.၄ Supply Temperature 20-15
၂၀.၆ Efficiency 20-16

Chapter-21 Servicing and Maintenance


၂၁.၁ Pressure Testing 21-1
၂၁.၂ Vacuum Drawing ႔ System Evacuation 21-2
၂၁.၃ System ႔ Refrigerant (Methods of Charging) 21-3
၂၁.၃.၁ Superheat Method 21-3
၂၁.၃.၂ Subcooling Method 21-3
၂၁.၃.၃ ( ) ႔ (Vapor Charging) 21-4
၂၁.၃.၄ ( ) (Liquid Charging) 21-5
၂၁.၃.၅ ( ) Refrigerant (Charging by Weight) 21-7
၂၁.၃.၆ Trouble-Shooting of Charge Conditions 21-8
၂၁.၃.၇ System Refrigerant 21-9
၂၁.၃.၈ (Leak Detection) 21-9
၂၁.၄ Chiller Commissioning 21-10
၂၁.၄.၁ Chiller Pre-Commissioning Check Procedure 21-11
၂၁.၄.၂ Pre-Commissioning Checks 21-11
၂၁.၅ Chiller Testing and Commissioning 21-12
၂၁.၅.၁ Commissioning Procedure 21-12
၂၁.၆ Start Up Report 21-14
၂၁.၇ Maintenance Requirements for Chillers (Regularly Scheduled Maintenance) 21-15
၂၁.၇.၁ Recommended Chiller Monitoring Points 21-16
၂၁.၇.၂ Periodic Maintenance Chiller Log 21-17
၂၁.၇.၃ Maintenance Requirements for YK Chiller 21-18
၂၁.၇.၄Maintenance Requirements for YT Chiller 21-19
၂၁.၇.၅ Maintenance Requirements for YR Chiller 21-20

XV
Chillers and Chilled Water Systems ႔

၂၁.၇.၆ Maintenance Requirements for YS Chiller 21-21


၂၁.၇.၇ Maintenance Schedule 21-22
၂၁.၇.၈ Tube Cleaning 21-22
၂၁.၇.၉ Annual Shutdown 21-22
၂၁.၈ Long Term Maintenance 21-23
၂၁.၉ Overhaul 21-23
၂၁.၁၀ Troubleshooting 21-24
၂၁.၁၀.၁ Detecting and Correcting Problems 21-24
၂၁.၁၀.၂ Trouble Diagnosis Chart 21-27

Chapter-22 Water Treatment


၂၂.၁ Closed Loop Chiller Water System 22-2
၂၂.၁.၁ Heat Transfer Coefficient vs. Fouling 22-2
၂၂.၂ Open Loop Condenser Water System 22-4
၂၂.၂.၁ Scale Formation 22-4
၂၂.၂.၂ Inside Corrosion 22-4
၂၂.၂.၃ Fouling 22-4
၂၂.၂.၄ Biological Fouling 22-5
၂၂.၂.၅ Microbiological Controls 22-5
၂၂.၂.၆ Corrosion Rate Controls 22-6
၂၂.၂.၇ Water Quality Parameter Controls 22-6
၂၂.၂.၈ (Cost) 22-7
၂၂.၃ Water Treatment for Chilled Water 22-7
၂၂.၄ Chemical Treatment and Cleaning 22-8
၂၂.၅ Makeup Water 22-9

-End-

XVI

You might also like