SETTING CALCULATION
765/21 kV , 600 MVA TRANSFORMER DIFFERENTIAL
PROTECTION
CTR HV: 500/5
CTR LV: 12500/5
Relay type : System A - P632
Relay Designation - 87GT
Transformer Data :
Power: 600 MVA
HV voltage: 765 KV
LV1 Voltage: 21KV
Transformer percentage imp: 15 %
Transformer vector group: Ynd11
Tap +/- 5 % in steps of 2.5%
SUPPORTIVE CALCULATION TO VERIFY BIAS SETTINGS
Id> 0.2 Iref
Id>> 10 Iref ( should me 10% more than max inrush current)
Id>>>15 Iref
m1 0.2
m2 0.8
Effect of CTs inside delta:
In LV — 21kV side, we have connected 2CTs inside delta and
the CTs are connected in such a way to sum the currents during
normal operation. As CTs are connected inside the delta, the
effective current will be the phase current and not the delta
current. Considering both the factors,
Effective CT ratio will be 12500/2 * 1.732 =10825A.
There is no vector correction required as CTs are connected
inside the delta.
At normal condition current in HV bias circ!
Primary current = GOOMVA / (1.732 * 765 kV)= 452.83 A
Current in CT Secondary = 452.83 / 500 A= 0.906
Required Ratio compensation = 1 / 0.754= 1.104
At normal condition current in LV bias circuit
Primary current = 600 MVA / (1.732 * 21kV)= 16,496.2A
Current in CT Secondary = 16496 / 10825= 1.524 In
Required Ratio compensation = 1 / 1.524= 0.656At - 5 % tap condition current in HV bias circuit:
HV Side current = 600 MVA / (1.732 * 726.75 kV)= 476.67A
Current in CT Secondary = 476.67x 1.104 / 500
With ratio compensation = 1.052
At + 5 % tap condition current in HV bias circuit
HV Side current = 600 MVA / (1.732 * 803.25 kV)= 431.27 A
Current in CT Secondary = 431.27 x 1.104 / 500
With ratio compensation = 0.952
Differential Current at Tap Extremities:
At -5% Tap Idiff1
At +5% Tap Idiff2
Bias Current at Tap Extremities:
Ibias = (IRHV + IRLV)/2 IRHV — Relay HV
Current
IRLV — Relay LV
Current
Ibias1 = (1.052 + 1)/2 = 1.026
Ibias2 = (0.952 + 1)/2 = 0.976
OPERATING CURRENT lop:
At-5% Tap.
lop1 = m1 x | bias + Id> x (1-0.5*m1)
0.2 x 1.026 + 0.2 x ( 1-0.5"0.2)= 0.3852 Amps
Idiff1/ lop1 = 0.052/0.3852 = 13.5%
Since the differential current is not greater than 90% of the
i tat 50, tan the calasuill anacata
OPERATING CURRENT lop:
At +5% Tap
lop1 = m1 x | bias + Id> x (1-0.5*m1)
0.2 x 0.976 + 0.2 x ( 1-0.5*0.2)
0.3752 Amps
iff2/lop2 = 0.048 / 0.3752= 12.79 %
Since the differential current is not greater than 90% of the
operating current at +5% tap the relay will operate
satisfactorily.
Hence Bias setting
m1 = 20% (0.2) 1.5 times of Full load current,
m2 = 80% for through fault stability(11-12)
20% 80%
0.2pu
1.Spu_ 2.5pu (a4i2y2