You are on page 1of 1

Salam Technology

General Cargo Terminal OSP Backbone Link Loss Calculation


SPC 38 Outside Plant Cabling System (OSP)

NPP/0067 – Port Master Systems Integration


Total Passive Perfomance
Receiver Power Min. Required
Main Fiber Cable Average Receiver Repair Other Attenuation Loss Link loss Budget Verification Receiver's
Fiber Cable Main OSP Main cable Drop off cable System Gain Operating Power Penalties Total fiber No of No of System Loss (dB)
Service Cable ID Cable Tag ID Ring Length in Source Destination Building ID Cable Type Drop off Cable ID Cable Tag ID SFP Part Number Transmitter Sensitivity Margin Performance (dBkm) (dB) (dB) [AB-AA] Dynamic Range
Type Cable Ring No length (MTR) length (MTR) (dB) [P-Q] Margin (dB) Penalties (dB) length (km) connector Splice [W-AD] Green if
Mts Power (dBm) (dBm) (dB) Loss (dB) [X*0.75+ [R-V] Green if +ve (dB)
(dB) [S+T+U] AA>AE
W*0.50+Y*0.3+Z) Value
P-GCTSTA-GF01-R01.01-F41:1.01-12/
STEVEDORE & TERMINAL STAFF AMENITIES PF 2.4 Primary FOC-012-2009 GCTSTA-GF01-R01.01-F40:01-06_ IT-FOC 468 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 6.90 4.261 17 -6.500

OFFICE BUILDING P-GCTFWP-GF02-R01.01-F42:1.01-12/


PUMP HOUSE - FIRE WATER (FRESH) PF 2.9.2 Primary FOC-012-2007 GCTFWP-GF02-R01.01-F41:01-06_ IT-FOC 790 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
(PF 2.1)
GROUND FLOOR P-GCTPWP-GF02-R01.01-F41:1.01-12/
RACK-3 PUMP HOUSE - POTABLE WATER PF 2.9.1 Primary FOC-012-2011 GCTPWP-GF02-R01.01-F40:01-06_ IT-FOC 1017 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500

P-GCTGAT-GF01-R01.01-F18:1.01-12/
GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY PF 2.10 Primary FOC-012-2013 GCTGAT-GF01-R01.01-F17:01-06_ IT-FOC 1338 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500
P-GCTOFF-GF30-R01.01-F43:01-24/
NPP LAN 48/SM FOC-048-0203 RING-1 1659
GCTOFF-0121-R01.01-F43:01-24_IT-FOC-PR01 P-GCTSTA-GF01-R01.01-F41:1.01-12/
STEVEDORE & TERMINAL STAFF AMENITIES PF 2.4 Secondary FOC-012-2010 GCTSTA-GF01-R01.01-F40:13-18_ IT-FOC 1191 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500

OFFICE BUILDING P-GCTFWP-GF02-R01.01-F42:1.01-12/


PUMP HOUSE - FIRE WATER (FRESH) PF 2.9.2 Secondary FOC-012-2008 GCTFWP-GF02-R01.01-F41:13-18_ IT-FOC 869 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
(PF 2.1)
FIRST FLOOR P-GCTPWP-GF02-R01.01-F41:1.01-12/
RACK-4 PUMP HOUSE - POTABLE WATER PF 2.9.1 Secondary FOC-012-2012 GCTPWP-GF02-R01.01-F40:13-18_ IT-FOC 642 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500

P-GCTGAT-GF01-R01.01-F18:1.01-12/
GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY PF 2.10 Secondary FOC-012-2014 GCTGAT-GF01-R01.01-F16:01-06_ IT-FOC 321 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500

P-GCTMS1-0102-R01.01-F41:1.01-12/
GCT ELECTRICAL SUBSTATION 1- MAIN INTAKE PF 2.6.1 Primary FOC-012-2015 GCTMS1-0102-R01.01-F40:01-06_ IT-FOC 425 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500
OFFICE BUILDING
(PF 2.1) P-GCTLFS-GF01-R01.01-F09:1.01-12/
GCT LAND FUEL SYSTEM PF 2.7 Primary FOC-012-2019 GCTLFS-GF01-R01.01-F08:01-06_ IT-FOC 1194 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
GROUND FLOOR
RACK-3 P-GCTSWP-GF01-R01.01-F41:1.01-12/
PUMP HOUSE - SEA WATER PF 2.9.3 Primary FOC-012-2021 GCTSWP-GF01-R01.01-F40:01-06_ IT-FOC 1811 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
P-GCTOFF-GF30-R01.01-F42:01-24/
NPP LAN 48/SM FOC-048-0204 RING-2 2760
GCTOFF-0121-R01.01-F42:01-24_IT-FOC-PR02 P-GCTMS1-0102-R01.01-F41:1.01-12/
GCT ELECTRICAL SUBSTATION 1- MAIN INTAKE PF 2.6.1 Secondary FOC-012-2016 GCTMS1-0102-R01.01-F40:13-18_ IT-FOC 2335 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
OFFICE BUILDING
(PF 2.1) P-GCTLFS-GF01-R01.01-F09:1.01-12/
GCT LAND FUEL SYSTEM PF 2.7 Secondary FOC-012-2020 GCTLFS-GF01-R01.01-F08:13-18_ IT-FOC 1566 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
FIRST FLOOR
RACK-4 P-GCTSWP-GF01-R01.01-F41:1.01-12/
PUMP HOUSE - SEA WATER PF 2.9.3 Secondary FOC-012-2022 GCTSWP-GF01-R01.01-F40:13-18_ IT-FOC 949 10 SFP-10G-LR-S -8.2 -20 11.8 3.0 0 0.6 3.6 0.48 2 3 0 2.639 5.561 2.922 17 -5.200

P-GCTBGB-GF03-R01.01-F41:1.01-12/
BACKUP GENERATOR BUILDING PF 2.8 Primary FOC-012-2023 GCTBGB-GF03-R01.01-F40:01-06_ IT-FOC 510 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500

OFFICE BUILDING P-GCTREF-GF37-R01.01-F41,40:1.01-12/


REFRIGERATED STORAGE PF 2.5 Primary FOC-012-2025 GCTREF-GF37-R01.01-F39:01-06_ IT-FOC 952 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
(PF 2.1)
GROUND FLOOR REFRIGERATED STORAGE P-GCTREF-GF37-R01.01-F41,40:1.01-12/
RACK-3 PF 2.5 Primary FOC-012-2045 GCTREF-0101-R01.01-F14:01-06_ IT-FOC 952 105 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
IDF-2
P-GCTDS1-GF01-R01.01-F41:1.01-12/
GCT ELECTRICAL SUBSTATION 2- DISTRIBUTION PF 2.6.2 Primary FOC-012-2027 GCTDS1-GF01-R01.01-F40:01-06_ IT-FOC 1987 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500
P-GCTOFF-GF30-R01.01-F41:01-24/
NPP LAN 48/SM FOC-048-0205 RING-3 3438
GCTOFF-0121-R01.01-F41:01-24_IT-FOC-PR03 P-GCTBGB-GF03-R01.01-F41:1.01-12/
BACKUP GENERATOR BUILDING PF 2.8 Secondary FOC-012-2024 GCTBGB-GF03-R01.01-F40:13-18_ IT-FOC 2928 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500

OFFICE BUILDING P-GCTREF-GF37-R01.01-F41,40:1.01-12/


REFRIGERATED STORAGE PF 2.5 Secondary FOC-012-2026 GCTREF-GF37-R01.01-F39:13-18_ IT-FOC 2486 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
(PF 2.1)
FIRST FLOOR REFRIGERATED STORAGE P-GCTREF-GF37-R01.01-F41,40:1.01-12/
RACK-4 PF 2.5 Secondary FOC-012-2046 GCTREF-0101-R01.01-F14:13-18_ IT-FOC 2486 105 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
IDF-2
P-GCTDS1-GF01-R01.01-F41:1.01-12/
GCT ELECTRICAL SUBSTATION 2- DISTRIBUTION PF 2.6.2 Secondary FOC-012-2028 GCTDS1-GF01-R01.01-F40:13-18_ IT-FOC 1451 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500

P-GCTTS1-GF06-R01.01-F41:1.01-12/
TRANSIT SHED-1 PF 2.2.1 Primary FOC-012-2029 GCTTS1-GF06-R01.01-F40:01-06_ IT-FOC 717 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500

OFFICE BUILDING P-GCTTS2-GF06-R01.01-F41:1.01-12/


TRANSIT SHED-2 PF 2.2.2 Primary FOC-012-2031 GCTTS1-GF06-R01.01-F40:01-06_ IT-FOC 1160 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
(PF 2.1)
GROUND FLOOR GCT ELECTRICAL SUBSTATION 3 - P-GCTDS2-GF01-R01.01-F41:1.01-12/
RACK-3 PF 2.6.3 Primary FOC-012-2033 GCTDS2-GF01-R01.01-F40:01-06_ IT-FOC 1373 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
DISTRIBUTION FUTURE
TRANSIT SHED-3 P-GCTTS3-GF01-R01.01-F41:1.01-12/
PF 2.2.3 Primary FOC-012-2035 GCTTS3-GF01-R01.01-F40:01-06_ IT-FOC 1608 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500
P-GCTOFF-GF30-R01.01-F40:01-24/ (FUTURE PHASE)
NPP LAN 48/SM FOC-048-0206 RING-4 3940
GCTOFF-0121-R01.01-F40:01-24_IT-FOC-PR04 P-GCTTS1-GF06-R01.01-F41:1.01-12/
TRANSIT SHED-1 PF 2.2.1 Secondary FOC-012-2030 GCTTS1-GF06-R01.01-F40:13-18_ IT-FOC 3223 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 7 0 3.839 3.061 -0.778 17 -6.500

OFFICE BUILDING P-GCTTS2-GF06-R01.01-F41:1.01-12/


TRANSIT SHED-2 PF 2.2.2 Secondary FOC-012-2032 GCTTS2-GF06-R01.01-F40:13-18_ IT-FOC 2780 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 6 0 3.539 3.361 -0.178 17 -6.500
(PF 2.1)
FIRST FLOOR GCT ELECTRICAL SUBSTATION 3 - P-GCTDS2-GF01-R01.01-F41:1.01-12/
RACK-4 PF 2.6.3 Secondary FOC-012-2034 GCTDS2-GF01-R01.01-F40:13-18_ IT-FOC 2567 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
DISTRIBUTION FUTURE
TRANSIT SHED-3 P-GCTTS3-GF01-R01.01-F41:1.01-12/
PF 2.2.3 Secondary FOC-012-2036 GCTTS3-GF01-R01.01-F40:13-18_ IT-FOC 2332 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
(FUTURE PHASE)
EQUIPMENT MAINTENANCE WORKSHOP P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PF2.3 Primary FOC-012-2017 GCTEMW-GF08-R01.01-F40:01-06_ IT-FOC 396 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500
OFFICE BUILDING IDF-1
(PF 2.1) EQUIPMENT MAINTENANCE WORKSHOP P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PF2.3 Primary FOC-012-2041 GCTEMW-0107-R01.01-F41:01-06_ IT-FOC 396 105 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
GROUND FLOOR IDF-2
RACK-4 P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PUMP HOUSE - WASTE WATER 9 PF 11.23.9 Primary FOC-012-0415 GCTW09- LAN-FEC0005-01:01-06_ IT-FOC 396 271 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
P-GCTOFF-GF30-R01.01-F39:01-24/
NPP LAN 48/SM FOC-048-0414 RING-5 1405
GCTOFF-0121-R01.01-F39:01-24_IT-FOC-PR05 EQUIPMENT MAINTENANCE WORKSHOP P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PF2.3 Secondary FOC-012-2018 GCTEMW-GF08-R01.01-F40:13-18_ IT-FOC 1009 10 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 5 0 3.239 3.661 0.422 17 -6.500
IDF-1
OFFICE BUILDING
(PF 2.1) EQUIPMENT MAINTENANCE WORKSHOP P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PF2.3 Secondary FOC-012-2042 GCTEMW-0107-R01.01-F41:13-18_ IT-FOC 1009 105 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 4 0 2.939 3.961 1.022 17 -6.500
FIRST FLOOR IDF-2
RACK-4 P-GCTEMW-GF08-R01.01-F42,F41:1.01-12/
PUMP HOUSE - WASTE WATER 9 PF 11.23.9 Secondary FOC-012-0416 GCTW09- LAN-FEC0005-02:01-06_ IT-FOC 1009 1021 GLC-LH-SMD -9.5 -20 10.5 3.0 0 0.6 3.6 0.48 2 3 0 2.639 4.261 1.622 17 -6.500

OFFICE BUILDING OFFICE BUILDING


P-GCTOFF-GF30-R01.01-F36:01-12/ (PF 2.1) (PF 2.1)
NPP LAN 24/SM FOC-024-0201 - 55 PF 2.1 - - - 55 0 X2-10GB-LR -8.2 -14.400 6.2 3.0 0 0.6 3.6 0.48 2 2 0 2.339 7.35 5.011 14.9 -8.700
GCTOFF-0121-R01.01-F36:01-12_IT-FOC-Z01 GROUND FLOOR FIRST FLOOR
RACK-3 RACK-4
OFFICE BUILDING OFFICE BUILDING
P-GCTOFF-GF30-R01.01-F37:01-12/ (PF 2.1) (PF 2.1)
NPP LAN 24/SM FOC-024-0202 - 55 PF 2.1 - - - 55 0 X2-10GB-LR -8.2 -14.400 6.2 3.0 0 0.6 3.6 0.48 2 2 0 2.339 7.35 5.011 14.9 -8.700
GCTOFF-0121-R01.01-F37:01-12_IT-FOC-Z02 GROUND FLOOR FIRST FLOOR
RACK-3 RACK-4
P-GCTMS1-0102-R01.01-F39:2.01-12/
GCT ELECTRICAL SUBSTATION 1- MAIN INTAKE PF 2.6.1 Primary FOC-012-0402 465 700 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 3 0 2.639 10.55 7.911 17 -6.000
GCTGEN- WLN-FEC0001-01:01-06_ IT-FOC
OFFICE BUILDING P-GCTTS1-GF06-R01.01-F39:2.01-12/
TRANSIT SHED-1 PF 2.2.1 Primary FOC-012-0406 1048 1298 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 4 0 2.939 10.55 7.611 17 -6.000
(PF 2.1) GCTGEN- WLN-FEC0003-01:01-06_ IT-FOC
GROUND FLOOR P-GCTTS2-GF06-R01.01-F39:2.01-12/
RACK-3 TRANSIT SHED-2 PF 2.2.2 Primary FOC-012-0404 1563 583 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 5 0 3.239 10.55 7.311 17 -6.000
GCTGEN- WLN-FEC0002-01:01-06_ IT-FOC
P-GCTSWP-GF01-R01.01-F39:2.01-12/
PUMP HOUSE - SEA WATER PF 2.9.3 Primary FOC-012-0408 2988 451 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 6 0 3.539 10.55 7.011 17 -6.000
P-GCTOFF-GF30-R01.01-F38:01-12/ GCTGEN- WLN-FEC0004-01:01-06_ IT-FOC
NPP WLAN 48/SM FOC-048-0401 - 3401
GCTOFF-0121-R01.01-F38:01-12_IT-FOC-Z03 P-GCTMS1-0102-R01.01-F39:2.01-12/
GCT ELECTRICAL SUBSTATION 1- MAIN INTAKE PF 2.6.1 Secondary FOC-012-0403 2936 457 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 6 0 3.539 10.55 7.011 17 -6.000
GCTGEN- WLN-FEC0001-02:01-06_ IT-FOC
OFFICE BUILDING P-GCTTS1-GF06-R01.01-F39:2.01-12/
TRANSIT SHED-1 PF 2.2.1 Secondary FOC-012-0407 2353 733 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 5 0 3.239 10.55 7.311 17 -6.000
(PF 2.1) GCTGEN- WLN-FEC0003-02:01-06_ IT-FOC
FIRST FLOOR P-GCTTS2-GF06-R01.01-F39:2.01-12/
RACK-4 TRANSIT SHED-2 PF 2.2.2 Secondary FOC-012-0405 1838 394 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 4 0 2.939 10.55 7.611 17 -6.000
GCTGEN- WLN-FEC0002-02:01-06_ IT-FOC
P-GCTSWP-GF01-R01.01-F39:2.01-12/
PUMP HOUSE - SEA WATER PF 2.9.3 Secondary FOC-012-0409 413 669 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 3 0 2.639 10.55 7.911 17 -6.000
GCTGEN- WLN-FEC0004-02:01-06_ IT-FOC

P-GCTGAT-GF01-R01.01-F14:01-06/ GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY


NPP AGMS 12/SM FOC-012-0272 - 889 P-GCTGLN-AGM-FEC0013_IT-FEC - - - - 889 0 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 2 0 2.339 10.55 8.211 17 -6.000
GCTGLN-AGM-FEC0013-18:01-06_IT-FOC-Z04 (PF2.10)

P-GCTGAT-GF01-R01.01-F14:13-18/ GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY


NPP AGMS 12/SM FOC-012-0273 - 89 P-GCTGLN-AGM-FEC0013_IT-FEC - - - - 89 0 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 2 0 2.339 10.55 8.211 17 -6.000
GCTGLN-AGM-FEC0013-18:13-18_IT-FOC-Z05 (PF2.10)

P-GCTGAT-GF01-R01.01-F15:01-06/ GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY


NPP AGMS 12/SM FOC-012-0274 - 188 P-GCTGLN-AGM-FEC0014_IT-FEC - - - - 188 0 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 2 0 2.339 10.55 8.211 17 -6.000
GCTGLN-AGM-FEC0014-18:01-06_IT-FOC-Z06 (PF2.10)

P-GCTGAT-GF01-R01.01-F15:13-18/ GCT ENTRY & EXIT GATE COMPLEX WITH CANOPY


NPP AGMS 12/SM FOC-012-0275 - 188 P-GCTGLN-AGM-FEC0014_IT-FEC - - - - 188 0 GLC-LX-SM-RGD -20 -31.000 11 3.0 0 0.6 3.6 0.48 2 2 0 2.339 10.55 8.211 17 -6.000
GCTGLN-AGM-FEC0014-18:13-18_IT-FOC-Z07 (PF2.10)

Description: Details Description: Details Description: Details


Service: Systems (LAN, WLAN & AGMS) Source: Cable starting point / Location / MDF / IDF / Manhole Main cable Length: Main cable length from Source to Drop off / Destination to Drop off Length details in MTR.
Fiber Cable Type: Type of Fiber cable and fiber core details. Destination: Cable ending point / Location / MDF / IDF / Manhole / Panel Drop off cable Length: Cable length from Drop off location (Manhole / Rack mount enclosure) to Fiber patch panel in MDF / IDF.
Cable ID: FOC-(XX)X-YYYY cable ID details. Building ID: Port Facility (PF) number details for the Buildings. Total fiber length : Sum of Main cable length + Drop off cable length
Cable Tag ID: Main cable Tag ID for the FOC ID details. Cable Type: Primary / Secondary cable details. No. of Connector: Number of connectors used in the Link.
Main OSP Cable Ring No: Ring No’s assigned for FOC cables. Drop off Cable ID: FOC-(XX)X-YYYY Drop off cable ID details. No. of Splice: Number of splicing in the Link between Source to destination.
Main Fiber cable length: Main Cable length from Source to destination. Drop off Cable Tag ID: Drop off Cable Tag ID for FOC ID details. Total Loss: No. of connector x 0.75 + Distance in KM x 0.50 + No. of Splice point x 0.3

Attachment-03 Page 1 of 1

You might also like