Hauser Endress: Pressure Transmitter Cerabar S PMC 731, PMP 731
Hauser Endress: Pressure Transmitter Cerabar S PMC 731, PMP 731
Endress + Hauser
The Power of Know How
The Cerabar S is designed as The table below provides a complete
Selecting the replaceable modules and is based on summary of the Cerabar S/ Deltabar S
Instrument the same construction principle as its families. Further information on
»twin brother« the Deltabar S. instruments:
This has the following advantages: • grey fields are found in this Technical
• Better stock management and Information
maintenance by stocking modules • white fields are found in Technical
instead of instruments Information TI 217P and TI 256P.
• Simple handling using a universal
operating principle.
Cerabar S PMC 731, PMP 731 PMC 731 PMC 731 PMP 731
Threaded and
flush-mounted 0 - 10 bar
process
connections
optional
flush-mounted
including diaphragm
flush-mounted or internal
process diaphragm with
connections adapter
0 - 10 bar
metal-free
S
S
S
Z
Z
Z
connection also
available
flush-mounted
ceramic sensor,
metal-free metallic
Z S
connection also diaphragm with
available with optional tube
S
Z
2
Modularity
Mechanical The intelligent pressure transmitters Features include:
Construction from Endress+Hauser • Interchangeable sensor module and
• Cerabar S: process connections
gauge/absolute pressure measurement • Interchangeable housing versions
• Deltabar S: • Universal interchangeable electronics
differential pressure, level and flow for gauge/absolute and differential
measurement (see TI 256P) pressure
offer optimum modularity for future • Simple and uniform operation
product development.
Interchangeable Sensor Modules
The sensor modules are fully calibrated
sliding cover for Goretex filter
for pressure and temperature in the
adjuster
factory. These data are stored in the
sensor module. After replacing the
sensor module, the data is automatically
A
Tes
t
1
4...2
0m
2
3
loaded into the electronics from the
BCD calibrated sensor module. The
789 A
EF
01
23456
Display Module
electronics connection
compartment compartment
A display module with the following
features can be used for showing
measured values and for simplifying
sensor module
local operation:
• Large four-character pressure display
-0.1...0.3 bar with bar graph showing current.
replaceable gasket
For 4…20 mA instruments, the bar
optional display module to graph shows the actual current value
display measured values and and for fieldbus instruments, it
replaceable process
to simplify local operation
connection displays the relationship between the
current measured pressure value and
the set measuring range.
• The housing has both an isolated
electronics compartment and an
isolated connection compartment.
Housings
Housing T4 is used for vertical mounting
of the Cerabar S:
• Protection IP 65
• Separate electronics and connection
T4 housing compartments
• Easily accessible operating elements
Tes
t
4...2
0m
2
A
BCD
789 A
EF
01
23456
3
System Components
Measuring System The complete measuring system
consists of: or
• Cerabar S pressure transmitter with • Cerabar S pressure transmitter with
− 4…20 mA signal output and HART − Foundation Fielbus digital
communication protocol and communications signal and
− power supply, e.g. with the RN 221N − Fieldbus interface card H1 or Link
transmitter power supply unit from and Fieldbus interface card H1 for
Endress+Hauser connecting to a PC with the
Non-Ex: 11.5…45 V DC, operating program
Ex d[ia]: 13…30 V DC,
Ex ia: 11.5…30 V DC
or
• Cerabar S pressure transmitter with
− PROFIBUS-PA digital
communications signal and
− connection via segment coupler to a
PLC or PC using e.g. the
Endress+Hauser Commuwin II
operating program
Connection to PLC or PC R
PROFIBUS-DP
4…20 mA
ENDRESS + HAUSER
PROFIBUS-PA
Non-Ex: 11.5…45 V DC,
Ex d[ia]: 13…30 V DC or
Ex ia: 11.5…30 V DC e. g. with RN 221N
TM
Fieldbus H1
TM
F
Fieldbus
interface card H1 Connection to PC
via Link and Fieldbus
interface card H1
or
Fieldbus
Complete measuring interface card H1
system Cerabar S
• left above:
PROFIBUS-PA
see also Operation ControlNet
page 7 or HSE
• right above:
Current output
4…20 mA with HART Fieldbus H1
communications Link
signal
• below:
Foundation Fieldbus
see also Operation
page 8
4
Ceramic Sensor Metal Sensor
Operating Principle The ceramic sensor is a dry sensor with The process pressure deflects the
the process pressure acting directly on separating diaphragm with a filling
the rugged ceramic diaphragm and liquid transmitting the pressure to a
deflecting it by a maximum of 0.025 mm. resistance bridge. The bridge output
A pressure-proportional change in the voltage, which is proportional to
capacitance is measured by the pressure, is then measured and
electrodes on the ceramic substrate and processed.
diaphragm. The measuring range is
determined by the thickness of the Advantages:
ceramic diaphragm. • For process pressures up to 400 bar
(6000 psi)
Advantages: • Excellent long-term stability
• Guaranteed resistance to overload up • Guaranteed resistance to overload up
to 40-times nominal pressure to 4-times nominal pressure
• Extremely high chemical resistance, (max. 600 bar/9000 psi)
comparable to Hastelloy
• For use with vacuums
5
The Cerabar S can be operated in the or
Operation following ways: • Using segment couplers to connect
• Using the four keys on the instrument the intrinsically-safe PROFIBUS-PA
directly at the mounting point for and PROFIBUS-DP fieldbus and
calibrating zero point and span at the operating the instrument via PC and
touch of a button. Commuwin II operating program
or or
• Operating remotely using the digital • Using interface card H1 or via Link
HART data protocols and interface card H1 for connecting
− e.g. via Commubox FXA 191 and a the intrinsically safe Foundation
PC with the Endress+Hauser Fieldbus and for operating via PC and
Commuwin II operating program or operating program.
− using the Universal HART
communicator DXR 275 handheld
terminal
Operation Using the Universal HART
Communicator DXR 275
There are two possibilities for scaling A zero point shift due to the orientation
the 4…20 mA output: either by directly of the instrument (bias pressure) can
applying the appropriate line pressures also be corrected using these keys as
or by entering the desired range-end well as for locking and unlocking the
values via the display module. measuring point.
• ZERO: +Z and –Z
• SPAN: +S and –S
Handheld Terminal
The Hart Communication DXR 275 can
be connected at any point along the
4…20 mA line to check, configure and
read additional information
(operating matrix, see page 7).
Cerabar S
4…20 mA 0003
min. 250 Ω
Test
1 2 3
+
4...20 mA *
FMD 230:LIC0001
Online
1 >Group Select
2 PV 20 mbar
FMD 230:LIC0001
Online
1 >Group Select
2 PV 20 mbar
Handheld terminal:
HELP HELP
Universal HART
The HART I
O
I
O Communicator
Communicator DXR
DXR 275
275 can be connected
anywhere along the
4…20 mA line.
* Use an intrinsically
other devices
safe power supply for
Ex i (z. B. FXN 671,
RN 221N).
6
Operation Using the Matrix
All operations and functions are All information can easily be accessed
identical whether the Cerabar S is using the operating matrix. Calibration is
calibrated using a process bus and PC just as easy.
or a handheld terminal.
Connecting to PROFIBUS-PA
PROFIBUS-PA is an open fieldbus The number of instruments operated by
standard to enable several sensors and one bus segment is:
actuators, including those in • up to 10 for EEx ia applications
explosion-hazardous areas, to be • up to 32 for non-Ex applications
connected to a bus line. With
PROFIBUS-PA, two-wire looped
instruments can be supplied by the
sensor with power and digital process
information.
Personal computer
with operating
program e.g. PLC
Commuwin II
PROFIBUS-DP
Cerabar S 0 - 10 bar
Segment coupler
ENDRESS + HAUSER
0 - 10 bar
0 - 10 bar
0 - 10 bar
Cerabar S with
PROFIBUS-PA
7
Connecting to Foundation Fieldbus The following instruments can be
Foundation Fieldbus is an open fieldbus operated via an interface card or via
standard to enable several sensors and Link and an interface card:
actuators, including those in • up to 10 instruments for
explosion-hazardous areas, to be Ex ia applications
connected to a bus line. With • up to 32 instruments for
Foundation Fieldbus, two-wire looped Non-Ex applications
instruments can be supplied by the
sensor with power and digital process
information.
CO H1 AI AO DI
Fieldbus H1
CO H1 AI AO DI
ControlNet or HSE
I/O FC LD
Fieldbus H1
Cerabar S with
Foundation Fieldbus
CO: Controller
H1: H1 interface
CN: ControlNet
AI: Analogue Input
AO: Analogue Output
DI: Digital Input
I/O: Input/Output
FC: Frequency converter
LD: Link
8
Mounting Instructions
Installation The Cerabar S is mounted in the same
way as a manometer. Its position
depends upon the application:
• Gases: • Liquids:
Mount above the tapping point Mount below or at the same level as
the tapping point
Gases Liquids
Mount above the tapping point Mount below the tapping point
0 - 10 bar
0 - 10 bar
shut-off valve
shut-off
valve
• Steam/vapour:
Mount with a pigtail below the tapping
point
Steam/vapour Steam/vapour
Mounted with pigtail with U-bend Mounted with circular pigtail
0 - 10 bar
circular
pigtail
shut-off valve
shut-off
valve
U-bend
9
Wall and Pipe Mounting
Installation A mounting set is available for mounting
(Continuation) on a wall or a horizontal or vertical pipe.
• Material: 1.4301 (AISI 304) 0 - 10 bar
Ø6
Structure)
Mounting on a wall B
PMC 731 19 mm
PMP 731 flush-mounted diaphragm 14 mm
PMP 731 internal diaphragm 39 mm
118
3
60,3
81
70
B
Conversion factors
1 in = 25.4 mm 111 94
1 mm = 0.039 in
0 - 10 bar
loosen
tighten
10
Wiring 4…20 mA Wiring PROFIBUS-PA
Electrical Connection The two-wire cable is connected to The digital communication signal is
screw terminals (wire cross section transmitted to the bus using a two-wire
0.5…2.5 mm2/ AWG 20…13) in the connecting cable. The bus cable also
connecting compartment. carries the power supply.
• For the connecting line, we • Supply voltage:
recommend you use a twisted, − Non-Ex: 9…32 V DC
screened two-core cable. − Ex ia: 9…24 V DC
• Supply voltage: • Bus cable:
− Non-Ex: 11.5…45 V DC For the connecting line, we
− Ex d[ia]: 13…30 V DC recommend you use a twisted,
− Ex ia: 11.5…30 V DC screened two-core cable. The
• Internal protection circuits against following specifications must be
reverse polarity, HF interference and observed when using the FISCO
overvoltage peaks model (explosion protection):
(see Technical Information TI 241F − Loop resistance (DC)
“EMC Guidelines”). 15…150 Ω/km
• Test signal: − Inductance 0.4…1 mH/km
The output current can be measured − Capacitance 80…20 nF/km
between terminal 1 and 3 without Instructions on connecting and
interrupting the process measurement. grounding the network are given in
BA 198F “Project Instructions for
PROFIBUS-PA” as well as
PROFIBUS-PA specifications.
Test for PA PA FF FF
1 2 3 power + 1 2 3 + 1 2 3
+ supply
PA- FF–
internal
connection PA+ FF+
pole –
terminal 2
grounded ground terminal
ground terminal ground terminal
on housing: to on housing:
on housing:
be grounded! to be grounded!
to be grounded!
Electrical connection: Electrical connection: Electrical connection:
Cerabar S for version with flameproof enclosure Cerabar S for all versions with PROFIBUS-PA Cerabar S for all versions with Foundation Fieldbus
PMC 731 - I ❑ ❑❑ ❑ ❑ ❑ ❑❑ ❑ (Reversed polarity has no effect on function.) (Reversed polarity has no effect on function.)
11
Connection M12 Plug (PROFIBUS-PA) Connection 7/8" Foundation Fieldbus Connection Harting Plug
Plug
Endress+Hauser also provides a Endress+Hauser also provides a For applications in power stations, there
Cerabar S with a M12 plug. This version Cerabar S with 7/8" Foundation Fieldbus is a Cerabar S with a Harting Han7D
can be easily connected to the plug. This version can be easily plug.
PROFIBUS network using a connected to the Foundation Fieldbus
preterminated cable. network using a preterminated cable.
View onto pins, plug on instrument View onto pins, plug on instrument Plug on instrument
+ PE-connection
(blue) (green yellow)
not connected
not connected
FF– 7
(blue) 6 8
PA– PA+ 1 –
(brown)
(blue) (brown) 5 2
4 3
FF+
(brown) screen
(green yellow)
screen
(black)
1 2 3 1 2 3 1 2 3
BU BN BK Cerabar S BU BN GN-YE Cerabar S BU BN GN-YE Cerabar S
BU: blue
BN: brown
BK: black
GN-YE: green yellow
12
Technical Data
Application Measurement of absolute and gauge pressure in gases, vapours and liquids
Measuring range
PMC 731
Type of Measurement Nominal Recommended Overload Resistance to Order code
pressure limits value min. span low pressure
bar bar bar bar bar absolut
gauge –0.1…0.1 0.1 0.005 4 0.7 1C
gauge –0.4…0.4 0.4 0.02 10 0 1F
gauge –1.0…2 2 0.1 20 0 1K
gauge –1.0…10 10 0.5 40* 0 1P
gauge –1.0…40 40 2 62 0 1S
13
Input PMP 731
(continuation)
Type of Measurement Nominal Recommended Overload Resistance to Order code
pressure limits value min. span low pressure
bar bar bar bar mbar absolut
Gauge –1…1 1* 0.05 4 10 3H
Gauge –1…2.5 2.5 0.125 10 10 3L
Gauge –1…10 10 0.5 40 10 3P
Gauge –1…40 40** 2 160 10 3S
Gauge –1…100 100** 5 400 10 3U
Gauge –1…400 400** 20 600 10 3Z
1000 1000
860 860
790
500 500
Standard
EEx ia IIC T4/T6
0 0 EEx d IIC T4/T6
11,5 13 20 30 45 U/V 11,5 20 30 45 U/V
14
Accuracy Reference conditions DIN IEC 770 TU=25°C (77°F)
Accuracy data adopted after entering »Low sensor
calibration« and»High sensor calibration« for zero and
nominal value
Linearity including hysteresis and reproducibility to TD 10:1: ± 0.1 % of set span*
based on the limit point method to IEC 770 for TD 10:1 to 20:1:
±0.1 % x [nominal value/(set span* x 10)] of set span*
Explanation of terms: Linearity at low absolute pressure ranges (due to absolut: for > 30 mbar to <100 mbar: ±0.3 %
Turndown (TD) = performance limits of currently available DKD for ≤ 30 mbar: ±1 % of set span*
nominal value/set span* calibration rigs)
Response time PMC 731: 500 ms,
PMP 731: 400 ms
set span*
Warm-up time 2s
Installation conditions Any position, zero point shift due to position can be
corrected, no effect on span
Ambient conditions
15
Mechanical Construction Design
Housing Housing can be rotated,
Gaskets Temperature Separated electronics and connection compartments,
for PMC 731 limits Optional electrical connection via M 20 x 1.5 with cable
gland or G ½, ½ NPT thread, also via PROFIBUS-PA
1 FPM, Viton –20…+100°C M12 plug or Foundation Fieldbus 7/8" or
(–4…+212°F) Harting Han7D plug
6 FPM, Viton –10…+60°C Terminal connection for wire cross section 0.5…2.5 mm2
cleaned for (+14…+140°F) (AWG 20…13)
oxygen service
Compound Weight:
V70G3 – Aluminium housing with process connection G½: 1.3 kg
– Stainless steel housing with process connection G½: 2.9 kg
A FPM, Viton –10…+100°C
oil- and (+14…+212°F) Process connections All common thread versions and flush-mounted connections
grease-free
Compound
V70G3 Materials
2 NBR –20…+100°C Housing – Cast aluminium housing with protective polyester-based
Compound (–4…+212°F) powder coating RAL 5012 (blue), cover RAL 7035 (grey),
8307 saltwater spray test DIN 50021 (504 h) passed
7 FFKM, Kalrez +5…+100°C – Stainless steel 1.4435 (AISI 316L)
Compound (+41…+212°F)
Nameplates 1.4301 (AISI 304)
4079
4 EPDM –30…+100°C 1) Process connections PMC 731 1.4435 (AISI 316L) or Hastelloy 2.4819 (C276) or PVDF2)
Compound (–40…+212°F) PMP 731 1.4435 (AISI 316L) or Hastelloy 2.4819 with Hastelloy
EPDM 13-70 diaphragm
D PTFE+ –20…+85°C Process diaphragm PMC 731 Al2O3 Aluminium oxide ceramic
Hastelloy C4 (–4…+185°F) PMP 731 1.4435 (AISI 316L) or Hastelloy 2.4819 (C276)
For constructive reasons can only Gaskets PMC 731 FPM Viton, FPM Viton cleaned for oxygen service3),
be exchanged for the same FPM Viton oil and grease-free, NBR, Kalrez, EPDM,
gasket. PTFE+Hastelloy C4, Chemraz (see table on left side
"gaskets for PMC 731")
C Chemraz –10…+100°C
PMP 731 FPM Viton, PTFE+Hastelloy C4, Copper (see table on left
Compound (+14…+212°F)
side "gaskets for PMP 731")
Chemraz 505
O-ring for cover gasket NBR
Mounting accessories Bracket for pipe and wall mounting 1.4301
Measuring cell
16
4…20 mA with HART protocol
Power Supply Power voltage – Non-Ex: 11.5…45 V DC
– Ex d[ia]: 13…30 V DC
– Ex ia: 11.5…30 V DC
Overvoltage category III to DIN EN 61 010-1
Ripple No effect for 4…20 mA signal up to ±5% residual ripple
within permissible range
Ripple with Smart transmitters HART:
max. ripple (measured at 500 Ω) 47…125 Hz: USS=200 mV;
max. noise (measured at 500 W) 500 Hz…10 kHz:
Ueff=2.2 mV
PROFIBUS-PA
Power voltage – Non-Ex: 9…32 V DC
– Ex ia: 9…24 V DC
Current consumption 10 mA ±1 mA (for Ex see Safety Instructions XA…)
Power up current Corresponds to Table 4, IEC 1158-2
Foundation Fieldbus
Power voltage – Non Ex: 9…32 V DC
– Ex ia: 9…24 V DC
Current consumption 11 mA ±1 mA
Power up current Corresponds to Table 4, IEC 1158-2
17
Product Structure Cerabar S PMC 731
PMC 731
Certificates, Approvals, Protection
R Standard
C ATEX II 3 G, EEx nA II T6
G Cenelec EEx ia IIC T4/T6 and ATEX II 1/2 G
I Cenelec EEx d [ia] IIC T61) and ATEX II 2 G (not with flush-mounted process connections, with cable entry M 20x1.5, G ½, ½ NPT)
O FM IS (non-incendive) CL. I, II, III; Div. 1, Groups A…G1) 1)
Certificate not with electronics version
S CSA IS (non-incendive) CL. I, II, III; Div. 1, Groups A…G1) PROFIBUS-PA
Housing: Aluminium Housing: Stainless steel (AISI 316L)
with display module without display module with display module
3 Cable gland M 20x1.5 4 Cable gland M 20x1.5 R Cable gland M 20x1.5
5 Cable entry ½ NPT 6 Cable entry ½ NPT S Cable entry ½ NPT
7 Cable entry G ½ 8 Cable entry G ½ T Cable entry G ½
K Harting Han7D plug L Harting Han7D plug U PROFIBUS-PA plug M12
M PROFIBUS-PA plug M12 N PROFIBUS-PA plug M12 V Foundation Fieldbus plug 7/8"
P Foundation Fieldbus plug 7/8" Q Foundation Fieldbus plug 7/8"
Accessories
1 None
2 Bracket for pipe and wall mounting
3 3.1.B Inspection certificate for all parts in contact with the medium made of 1.4435 (AISI 316L)
4 3.1.B Inspection certificate for all parts in contact with the medium made of 1.4435 (AISI 316L) and bracket
Process Connection
Thread, Material
1M G ½ (external) DIN 16 288; 1.4435 (AISI 316L)
2M G ½ (external) DIN 16 288; Hastelloy C276
5M G ½ (external) DIN 16 288; PVDF2) (max. 20 bar/300 psi, max. –10…+60°C/+14…+140°F))
1P G ½ (external), G ¼ (internal); 1.4435 (AISI 316L)
2)
1R G ½ (external), Ø 11.4 mm (internal); 1.4435 (AISI 316L) Note the Safety Instructions (XA)
1N ½ NPT (external), ¼ NPT (internal); 1.4435 (AISI 316L) and electrostatic charging!
2N ½ NPT (external), ¼ NPT (internal); Hastelloy C276
1A ½ NPT (external), Ø 11.4 mm (internal); 1.4435 (AISI 316L)
1S PF ½ (external) JIS B0202; 1.4435 (AISI 316L)
1K PT ½ (external), Ø 11.4 mm (internal) JIS B0203; 1.4435 (AISI 316L)
1T M 20x1.5 (external) DIN 16288; 1.4435 (AISI 316L)
Ceramic sensor flush-mounted (not with FPM Viton gasket, cleaned for oxygen service, gasket version 6)
Hygienic Connections Flanges
AH DN 40, DIN 11851, PN 40 EK DN 50, PN 40, DIN 2527, Form B (without raised face)
AL DN 50, DIN 11851, PN 40 EU DN 80, PN 40, DIN 2527, Form B (without raised face)
KL DRD-Flange , D=65 mm KJ 2", 150 lbs ANSI B.16.5, raised face
LL Varivent D=68 mm KK 2", 300 lbs ANSI B.16.5, raised face
(for pipes DN 40 … DN 125) DL ISO 2852 Clamp 2", PN 40
RI RF-Flange JIS 10K 50A
Threaded boss
AG G 1½ AR G2
BF 1½ NPT BR 2 NPT
XK M 44x1.25 9Y Others
18
Dimensions of Housing
Dimensions
PMC 731 Connection Electronics ENDRESS+HAUSER
CERABAR
compartment compartment Order Code xxxxxxxxxxxxxx
Ser.-No. x xx xxxx
P –1…2 bar
Housing: CERABAR Pmin Span 100 mbar
Pmax 20 bar
• Electronics and
KEMA Nr. Ex-94.D.8801
4 . . . 20 mA HART U 10,5…45 V
EEx ia IIC T6, -40°C TA 40°C Mat. 1.4571 / AL2O3 / FPM
EEx ia IIC T4, -40°C TA 70°C
• can be rotated
Prüfer:
through 270°
• Material:
cast aluminium with
powdered polyester 0 - 10 bar
coating or Z S
135
stainless steel 1.4435
18
(AISI 316L)
• Cable gland or optional
cable entry, see
M5
product structure
page 18 Threaded connection:
Process connections see below
• below: thread Flush-mounted connection:
• Page 20: flush-mounted see page 20
Conversion factors
1 mm = 0.039 in G½ external G ½, internal G ¼ external G ½, internal Ø 11.4 mm
1 in = 25.4 mm Versions 1M, 2M, 5M Version 1P Version 1R
17
Ø4
17
20
20
17
20
13
Ø3 G¼ Ø 11.4
5
Ø6 Ø 17 Ø 17,5
G½ G½ G½
25
20
20
Ø 11.4 Ø 11.4
¼ NPT ½ NPT
Process connections ½ NPT
Thread:
• Material:
1.4435 (AISI 316L) or external M 20x1.5
external PF ½ external PT ½, internal Ø 11.4 mm
Hastelloy 2.4819 Version 1T
Version 1 S Version 1K
(C276) oder PVDF
• Process gasket: FPM
Viton, FPM Viton
cleaned for oxygen
13,2
17
20
23
Chemraz, NBR,
Kalrez, EPDM
Ø 11.4
3
Ø3 Ø3
Ø5 PT ½ Ø6
Note on selection JIS B 0203-1982
Large internal diameters PF ½ M 20 x 1.5
are recommended for JIS B 0202-1982
highly-viscous media.
19
Flush-Mounted Process Connections DIN 11851, DN 50 DIN 11851, DN 40 ISO 2852, Clamp 2", PN 40
Version AL Version AH Version DL
112
Hygienic Connections 98 (without display)
104
0 - 10 bar
Housing: Z S
• Electronics and
connection
compartment
163
separated
• can be rotated
through 270°
163
163
• Material:
11
11
cast aluminium with
25
25
powdered polyester
Ø 26
coating or Ø 26 Ø 26 Ø 64
stainless steel 1.4435 Ø 61 Ø 48
(AISI 316L) Rd 78 x 1/6 Rd 65 x 1/6
• Cable gland
or optional cable
Varivent D=68 mm DRD D=65 mm
entry, see product
Version LL Version KL
structure page 18
• Surface height of 4 x Ø 11.5
parts in contact with
163
163
medium Ra ≤ 0.8 µm
Material sanitary Ø 26 Ø 26
connections Ø 68 Ø 65
• 1.4435 (AISI 316L) Ø 84
• Dry measuring cell, Ø 105
without filling fluid
187
187
187
22
27
28
25
Ø 26 Ø 26 Ø 26
G 1½ 1½ NPT Ø 40,5
Ø 55 M 44x1.25
G2 2 NPT
Version AR Version BR
70 AF 70 AF
187
187
30
30
Ø 26 Ø 26
G2 2 NPT
Ø 68 Ø 68
Material of threaded Ø 84 Ø 84
boss
1.4435 (AISI 316L)
20
Flanges Conversion factors DIN 2527, Form B, DN 50 PN 40 ANSI 16.5 2" 150 lbs (300 lbs), RF
1 mm = 0.039 in Version EK Version KJ, KK
1 in = 25.4 mm
6.42 in
163
Dimensions are in mm.
20
(0.88 in)
Ø 26 Ø 1.06 in
0.75 in
Ø 102
Ø 3.62 in
Ø125 – 4 x Ø 18
Ø 165
Ø 4.75 in – 4 x 0.75 in
(Ø 5.00 in – 8 x 0.75 in)
Ø 6.00 in (6.50 in)
Values in brackets apply to version KK:
2" 300 lbs ANSI B16.5
157
167
14
24
Ø 26
Ø 70
Ø142
Ø 120 – 4 x Ø 19
Ø160
Ø 155
Flange material Ø 200
1.4435 (AISI 316L)
21
Product Structure
Cerabar S PMP 731
PMP 731
Certificates, Approvals, Protection
R Standard
C ATEX II 3 G, EEx nA II T6
G Cenelec EEx ia IIC T4/T6 and ATEX II 1/2 G
I Cenelec EEx d IIC T5/T61) and ATEX II 2 G (with cable entry M 20x1.5, G ½, ½ NPT only)
D EEx ia IIC T4/T6, Zone 0
1)
Q FM explosion proof CL. I, II, III Div. 1, Groups A…G1) (with cable entry ½ NPT only) Certificate not with electronics version
O FM IS (non-incendive) CL. I, II, III; Div. 1, Groups A…G PROFIBUS-PA
U CSA explosion proof CL. I, II, III, Div. 1 Groups B…G1) (with cable entry ½ NPT only)
S CSA IS (non-incendive) CL. I, II, III; Div. 1, Groups A…G
Accessories
1 None
2 Bracket for pipe and wall mounting
3 3.1.B Inspection certificate for all parts in contact with the medium made of 1.4435
4 3.1.B Inspection certificate for all parts in contact with the medium made of 1.4435
and bracket
5 NACE MR0175/3.1.B material, Inspection Certificate EN 10204
6 NACE MR0175/3.1.B material mounting bracket, Inspection Certificate EN 10204
22
Dimensions of Housing
Dimensions
PMP 731 Connection
compartment
electronics
compartment
ENDRESS+HAUSER
CERABAR
Order Code xxxxxxxxxxxxxx
Ser.-No. x xx xxxx
CERABAR P –1…2 bar
Pmin Span 100 mbar
KEMA Nr. Ex-94.D.8801 Pmax 20 bar
EEx ia IIC T6, -40°C TA 40°C 4 . . . 20 mA HART U 10,5…45 V
EEx ia IIC T4, -40°C TA 70°C Mat. 1.4571 / AL2O3 / FPM
U 30 V, I 300 mA, P 1 W
connection
compartment
separated
• can be rotated
through 270° 0 - 10 bar
Z S
• Material:
132
cast aluminium with 18
powdered polyester
coating or
27 AF
M5
stainless steel 1.4435
(AISI 316L) max. torque
• Cable gland 40 Nm
or optional cable
entry, see product
structure page 22
≈160
≈160
≈160
17
Ø 18 Ø 18
Ø8 Ø8
20
20
21
3
3
Ø3 Ø4 Ø3
5
3
Ø6 ½ NPT Ø5
G½ PF ½
JIS B 0202-1982
PT ½ external M 20x1.5
Version 1K Version 1T
Material Process
≈160
≈160
connection and
adapter
• 1.4435 (AISI 316L)
17
3
13,2
Ø 17.7
Ø8
20
20
Ø4 Ø3
5
PT ½ Ø6
JIS B 0203-1982 M 20x1.5
27
132
132
G½
2,5
17
17
14
14
14
22
23
Endress+Hauser
GmbH+Co. KG
Instruments International
P.O. Box 2222
D-79574 Weil am Rhein
Germany
Tel. (0 76 21) 9 75-02
Fax (0 76 21) 9 75-3 45
http://www.endress.com
info@ii.endress.com
Endress + Hauser
The Power of Know How
05.02/PT1
TI 216P/00/en/08.02
CCS/CV5