VOCATIONAL TRAINING CENTER AT LADIYAPUR, FARIDABAD

DESIGN DATES-: 26/08/2017

PURLIN C/C OF = 0.9 M


PURLIN LENGTH = 0.86 M
WIND SPEED AT FARIDABAD = 47m/sec = vb

DESIGN WIND SPEED


VZ = Vb k1 k2 k3
k1= Risk factor =1
Factor k2 = 0.98
Factor k3 = 1
Vz = 47x1x0.95x1 = (43.7)

Design wind pressure = 0.6x(43.7)2


tan Ø = 1/ 29.25 = 6˚) = 1146 N/ m2

Which is very small

Then For worst case -(0.8+0.2) = -1-


Both sides

Then Line load or sheets = 750 N / m2


Self wt of sheet = 4.77 kg/m2 = 47 w/ m2

Imposed load of purlin


1146 (0.86+0.2) = 1146 N/ m2

Total load = 1943 N/ m2

Design of purlin = WL/ 10

= 1943X0.86 / 10X1000 = 1670 N.M


= 1.67 KN.M

Sector modulars = (1.67 x 10)6 / 165 = (10.127 x 102)

For ISMC = 75 = 24.8 cm2>10.127 Hence Safe

Since the Building is old one & Hence New N Girder is to be provided for roof slope in existing old building there for
since girder to be provided for same roof slope load & as on the basis of purlin calculation.