COMPLIANCE STATEMENT

Specification Ref. : QCS2014 - Section 23 - Part 4

S. No. SPECIFICATION REQUIREMENT PROPOSAL COMPLY REMARKS


4.5 FIRE HYDRANTS USPVH - USA

4.5.1 General

Fire hydrants shall be installed in locations as stated in the


1 Project Documentation unless otherwise directed by the Civil Under Contractor Scope Comply
Defence Department.

A certificate shall be obtained from the manufacturer stating


2 that the fire hydrants to be supplied are suitable for use in Same will be provided Comply
Qatar.
Fire hydrants shall be installed in accordance with the
3 Instllation instructions will be provided Comply
manufacturer’s instructions.

4.5.2 High Pressure Dry Barrel Hydrant


Proposed Sentinel 250 Fire Hydrant made comlete The long-life plastic drain valve facings
with removable/replaceable nozzles and hydrant provides seal reliability.
High pressure dry barrel hydrants shall come complete with
seat, top stop nut, Simple two piece design Sentinel 250 Fire Hydrant safety stem coupling
removable/replaceable nozzles and hydrant seat, top stop Comply with
1 standpipe coupling for easy repair traffic section, made out of stainless steel with a simjple
nut, easily repaired traffic section, nozzle section with 360° remarks
nozzle section with 360° rotation, main valve design which tears clearly with no loose piece
rotation, main valve opening and bronze drain plug.
opening (4½" & 5¼”) and Long-life plastic drain to fall into the main valve / Damage the drain
valve facings. valve facings.
Working pressure of the hydrant shall be 14 bar and the Working pressure of Sentinel 250 fire hydrant is
2 testing pressure shall be 28 bar unless otherwise stated in 250 psig (17 barg) and the testing pressure is Comply
the Project Documentation or agreed with the Engineer. 500psi (34 barg)
COMPLIANCE STATEMENT
Specification Ref. : QCS2014 - Section 23 - Part 4

S. No. SPECIFICATION REQUIREMENT PROPOSAL COMPLY REMARKS


Proposed Sentinel 250 Fire Hydrant Made to
comply with the requirements of ANSI/AWWA
The hydrant shall comply with ASNI/AWWA C502 and shall
3 C502, UL 246, FM 1510 in a U.S. ISO 9001 Comply
be UL listed and FM approved.
certified factory
UL/FM & QCDD Approbed

4 Materials for the hydrants shall be as follows:

Upper barrel, bonnet, nozzle section, Shoe and


nozzle section, barrels, stand pipe flanges, breakable flange,
operating nut are made of Ductile Iron, lower barrel
a base, main valve flange, weather-shield operating nut and Comply
of Cast Iron, Stainless Steel safety coupling, Traffic
bonnet all shall be ductile iron
feature Coupling Cast Iron, nozzles are bronze

Reversible Compression-Type Main Valve is made


main valve disc shall be ductile iron core and fully Closes under pressure for tight seal; reversible
b of rubber ASTM D2000, Lower valve plate of Cast -
encapsulated in EPDM rubber design provides a convenient replacement
Iron, upper valve plate of bronze

c caps shall be cast iron Cast Iron Caps Comply

Two-part Epoxy coated inside and out to all Iron


coating above ground shall be fusion bonded epoxy inside parts. Upper Barrel has additonal Polyeurethane Coating is two-part, sprayed and infra-red
d Comply
and out Enamel coating for improved resistance to UV baked instead of fusion bonded
fading and gloss retention

coating below ground shall be bitumen or fusion bonded Two-part Epoxy coated inside and out to all Iron Coating is two-part, sprayed and infra-red
e Comply
epoxy parts baked instead of fusion bonded
COMPLIANCE STATEMENT
Specification Ref. : QCS2014 - Section 23 - Part 4

S. No. SPECIFICATION REQUIREMENT PROPOSAL COMPLY REMARKS


The long-life plastic drain valve facings
provides seal reliability.
nozzles, valve seat ring, drain ring, drain bushings and plugs, Nozzles, valve seat ring, drain ring, hold-down nut Comply with Sentinel 250 Fire Hydrant safety stem coupling
f
stem nut, stem bushing and thrust nut shall be bronze are all bronze, Long-life plastic drain valve facings. remarks made out of stainless steel with a simjple
design which tears clearly with no loose piece
to fall into the main valve / Damage the drain
valve facings.
g stop nut, cap chain, bolts and nuts shall be zinc plated steel All Zinc Plated Steel Comply
stem rod coupling, standpipe lock rings, nozzle lock screw,
h lock plate, lock plate screw and spider bolt shall be stainless All stainless steel Comply
steel
Gaskets and "O" rings are made of Rubber ASTM
i barrel gaskets and cap gaskets shall be nitrile rubber. Comply
D2000
Each hydrant shall be clearly marked, either integrally
with the stated components or on a
5
plate of durable material securely fixed to that
component, as follows:
the number of the standard to which the hydrant conforms
a Comply Comply
and the date of the standard
b the manufacturer’s name or trade mark Comply Comply

The Sentinel 250 Fire Hydrant provided with QR


the identification number (the reference used by the Tags. This tags provides on-the-spot, field access
c manufacturer allowing identification for the supply of spares, to each hydrant’s vital statistics, including the Comply
etc). model, nozzle and operating nut size, bury depth,
type/size of shoe, and much more

GATE VALVES (STOP VALVES) QCS Section 23 Part 4 4.2.8


COMPLIANCE STATEMENT
Specification Ref. : QCS2014 - Section 23 - Part 4

S. No. SPECIFICATION REQUIREMENT PROPOSAL COMPLY REMARKS

Stop valves shall be UL listed and FM approved. They


should be the gate valve type, designed specifically for fire All Proposed Gate Valves are UL Listed and FM
1 line applications, where a positive indication of the open or Approved QCDD Approved Rated Pressure of Comply
closed position is necessary. The valve shall have flanged 350 Psi
ends, an iron body and a working pressure of 12 bar.