NFPA 72 AND ADA DEVICE

INSTALLATION REQUIREMENTS

CONDUIT

INSTALL PER
NATIONAL ELECTRIC CODE

MOUNT AUDIBLE
MOUNT ON A
& VISUAL DEVICES
APPROVED
ON APPROVED
BOX
BOXES.
AIR SUPPLY DIFFUSER OR
RETURN AIR OPENING
SMOKE/ HEAT
DETECTOR

0'-6" MINIMUM 0'-4" MINIMUM,


0'-4" MINIMUM 3'-0" MINIMUM
1'-0" MAXIMUM
HORN/ STROBE
EXIT

GRAPHIC
HORN SMOKE/ HEAT
ANNUNCIATOR DETECTOR
CONTROL
PANEL
STROBE

96" MAXIMUM
TOP OF DEVICE

MANUAL PULL STATION


80" MINIMUM
BOTTOM OF DEVICE

HINGED SIDE 5'-0" MAXIMUM


5'-6"

3'-8"
(3'-6" MINIMUM,
4'-0" MAXIMUM)

FINISHED
FLOOR

CITY OF RALEIGH FIRE DEPARTMENT DESCRIPTION: REVISIONS: DATE: DRAWING NO.

FIRE PROTECTION DIVISION


310 WEST MARTIN ST. RALEIGH, NC 27602
FIRE ALARM DEVICE MOUNTING 7-1-06 FP-26
W. WARREN LL