Chiller controller

SCHAV

SI-TEC CO., LTD [Seungil Electronics]


Contents

1. Applications

2. Features

3. Specifications

4. Display

SI-TEC CO., LTD [Seungil Electronics]


1. Applications

Refrigerator

Chiller

Boiler

Absorption chiller/heater

Air compressor

AHU

Cold storage

Heat pump

Ice bank

Other HVAC systems

SI-TEC CO., LTD [Seungil Electronics]


2. Features

Applicable for various systems

- Heat pump GEO/AIR source

- Selective between Temperature /Pressure control

- Master – Slave Function by linking two controller

- Part winding operation

- BITZER Compressor available (STEP)

- 3Way valve for HWS(Hot water supply)

ALARM

- Maximum 20 alarms listing from latest alarm

- Memorize A/I, D/I, D/O data when Alarm occurs

- Indicates alarm occur time and clearing time

- Manual unlock after clearing alarm factor for stability

Schedule

- 21 schedule registration (3 each week)

- Selective Daily/Weekly/Yearly schedule

- 27 holiday registration available for yearly schedule

- Temperature & Pressure value selective while schedule operation

SI-TEC CO., LTD [Seungil Electronics]


Energy efficiency

- Pump and condensing fan energy saving

(Stop compressor after certain delaying time.)

- Setting energy saving timer for delaying stop of compressor

- Energy saving logic for liquid injection and defrost

- 25% operation available for life extension

- Various modes that optimized for STEP operation

Selective pressure measurement

- Bar / Mpa / Kgf converting

- Setting max & min value for output of pressure sensor (4~20mA)

Communication

- Multi communication channel for remote display & monitoring system

through MODBUS

- SMS service, web monitoring system available through Web-alimi

composition

SI-TEC CO., LTD [Seungil Electronics]


3. Specifications

Set model number principle

Model Type Display Sensor


SCHAV - HS - NH - NS
HL NV SS
CS TH 00~FF
CL
HA
HB
CA
CB

HS HEAT PUMP STEP


HL HEAT PUMP STEPLESS
CS CHILLER STEP
CL CHILLER STEPLESS
HA HEATPUMP STEP – 2CYCLE
HB HEATPUMP STEPLESS – 2CYCLE
CA CHILLER STEP
CB CHILLER STEPLESS

SI-TEC CO., LTD [Seungil Electronics]


SPEC

SPECIFICATION
INPUT POWER Free voltage (100~250VAC, 50~60Hz)
OUTPUT VOLTAGE Same with Input power
D/O 16 Ports (Relay 7A 250V)
D/I 16 Ports (24V supply port 2EA)
A/O 2 Ports (0~10V, 4~20mA selective)
A/I 12 Ports (PT100:9EA / 4~20mA:2EA / CT:1EA)
COMMUNICATION 4 Ports (RS485)
CIRCUMSTANCE Indoor
Operation Temp. -20℃ ~ 70℃
Operation Humidity Under 95%
Storage Temp. -30℃ ~ 80℃

SI-TEC CO., LTD [Seungil Electronics]


4. Display

- AVDP-NH

- AVDP-TH

SI-TEC CO., LTD [Seungil Electronics]


Attachment

1. CHILLER STEP

Port Number SIGNAL Port Number SIGNAL


DI1 LOAD PUMP OCR DO1 LOAD PUMP
DI2 LOAD PUMP WFS DO2 COMP1 MAIN
DI3 COMP1 OCR DO3 COMP1 STAR
DI4 COMP1 HP DO4 COMP1 DELTA
DI5 COMP1 LP DO5 COMP1 25%
DI6 COMP1 OIL LEVEL DO6 COMP1 50%
DI7(*2) COMP1 OIL PRESURE DO7 COMP1 75% / SV
DI8 COMP2 OCR DO8 COMP1 SV/LI
DI9 COMP2 HP DO9 COMP2 MAIN
DI10(*1) COMP2 LP DO10 COMP2 STAR
DI11(*1) COMP2 OIL LEVEL DO11(*3) COMP2 DELTA
DI12(*1) COMP2 OIL PRESURE DO12 COMP2 25%
DI13(*2) NOT USE DO13(*2) COMP2 50%
DI14(*2) REVERSE POWER DO14(*1) COMP2 75% SV
DI15(*3) FREEZE AND BURST ALARM DO15 COMP2 SV / LI
DI16 REMOTE SIGNAL DO16 TOTAL ALARM

Port Number SIGNAL


AI1 LOAD PUMP OUTPUT
AI2(*3) LOAD PUMP INPUT
AI3(*1) COMP1 DISCHARGE GAS
AI4 COMP2 DISCHARGE GAS
AI5(*1) NOT USE
AI6(*2) NOT USE
AI7(*2) NOT USE
AI8 NOT USE
AI9(*6) ROOM TEMPERATURE
AI10(*4) PRESURE SENSOR
AI11 PRESURE SENSOR (SPARE)
AI12 CT (SPARE)
Attachment

2. CHILLER STEPLESS

Port Number SIGNAL Port Number SIGNAL


DI1 LOAD PUMP OCR DO1 LOAD PUMP
DI2 LOAD PUMP WFS DO2 COMP1 MAIN
DI3 COMP1 OCR DO3 COMP1 STAR
DI4 COMP1 HP DO4 COMP1 DELTA
DI5 COMP1 LP DO5 COMP1 START
DI6 COMP1 OIL LEVEL DO6 COMP1 INCREASE
DI7(*2) COMP1 OIL PRESURE DO7 COMP1 DECREASE
DI8 COMP2 OCR DO8 COMP1 SV/LI
DI9 COMP2 HP DO9 COMP2 MAIN
DI10(*1) COMP2 LP DO10 COMP2 STAR
DI11(*1) COMP2 OIL LEVEL DO11(*3) COMP2 DELTA
DI12(*1) COMP2 OIL PRESURE DO12 COMP2 START
DI13(*2) NOT USE DO13(*2) COMP2 INCREASE
DI14(*2) REVERSE POWER DO14(*1) COMP2 DECREASE
DI15(*3) FREEZE AND BURST ALARM DO15 COMP2 SV / LI
DI16 REMOTE SIGNAL DO16 TOTAL ALARM

Port Number SIGNAL


AI1 LOAD PUMP OUTPUT
AI2(*3) LOAD PUMP INPUT
AI3(*1) COMP1 DISCHARGE GAS
AI4 COMP2 DISCHARGE GAS
AI5(*1) NOT USE
AI6(*2) NOT USE
AI7(*2) NOT USE
AI8 NOT USE
AI9(*6) ROOM TEMPERATURE
AI10(*4) PRESURE SENSOR
AI11 PRESURE SENSOR (SPARE)
AI12 CT (SPARE)
Attachment

3. Heat pump STEP

Port Number SIGNAL Port Number SIGNAL


DI1 PUMP OCR DO1 LOAD PUMP
DI2 PUMP WFS DO2 MAIN COMP
DI3 COMP OCR DO3 COMP STAR
DI4 COMP HP DO4 COMP DELTA
DI5 COMP LP DO5 COMP 25%
DI6 OIL LEVEL DO6 COMP 50%
DI7(*2) OIL PRESSURE DO7 COMP 75%
DI8 REVERSE POWER DO8 COMP SOL VALVE
DI9 FREEZE&BURST DO9 COMP LIQUID INJECTION
DI10(*1) FAN OCR DO10 FOUR WAY VALVE
DI11(*1) GEO PUMP OCR DO11(*3) THREE WAY VALVE
DI12(*1) GEO PUMP WFS DO12 HEAT MODE SIGNAL
DI13(*2) DEFROST SIGNAL DO13(*2) FAN
DI14(*2) MANUAL DEFROST SIGNAL DO14(*1) GEO PUMP
DI15(*3) HOT WATER SIGNAL DO15 BITZER(Y4)
DI16 REMOTE SIGNAL DO16 TOTAL ALARM

Port Number SIGNAL


AI1 PUMP OUT
AI2(*3) HOT WATER
AI3(*1) GEO PUMP OUT
AI4 PUMP IN
AI5(*1) GEO PUMP IN
AI6(*2) OUTDOOR TEMPERATURE
AI7(*2) DEFROST TEMPERATURE
AI8 DISCHARGE GAS TEMPERATURE
AI9(*6) ROOM TEMPERATURE
AI10(*4) LOW PRESSURE SENSING
AI11 HIGH PRESSURE SENSING
AI12 CT SENSING
Attachment

4. Heat pump STEPLESS

Port Number Contents Port Number Contents


DI1 LOAD PUMP OCR DO1 LOAD PUMP
DI2 LOAD PUMP WFS DO2 COMP MAIN
DI3 COMP OCR DO3 COMP STAR
DI4 COMP HP DO4 COMP DELTA
DI5 COMP LP DO5 COMP START
DI6 COMP OIL LEVEL DO6 COMP INCREASE
DI7(*2) COMP OIL PRESURE DO7 COMP DECREASE
DI8 REVERSE POWER DO8 COMP SOL VALVE
DI9 FREEZE AND BURST DO9 COMP LIQUID INJECTION
DI10(*1) FAN OCR DO10 FOUR WAY VALVE
DI11(*1) GEO PUMP OCR DO11(*3) THREE WAY VALVE
DI12(*1) GEO PUMP WFS DO12 HEAT MODE SIGNAL
DI13(*2) DEFROST SIGNAL DO13(*2) FAN
DI14(*2) MANUAL DEFROST SIGNAL DO14(*1) GEO PUMP
DI15(*3) HOT WATER SIGNAL DO15 NOT USE
DI16 REMOTE SIGNAL DO16 TOTAL ALARM

Port Number Contents


AI1 LOAD PUMP OUTPUT
AI2(*3) HOT WATER TANK
AI3(*1) GEO PUMP OUTPUT
AI4 LOAD PUMP INPUT
AI5(*1) GEO PUMP INPUT
AI6(*2) OUTDOOR TEMPERATURE
AI7(*2) DEFROST TEMPERATURE
AI8 COMP DISCHARGE GAS
AI9(*6) ROOM TEMPERATURE
AI10(*4) PRESURE SENSOR
AI11 PRESURE SENSOR (SPARE)
AI12 CT (SPARE)