Lsa 50.2
Lsa 50.2
Lsa 50.2
√: Possible mounting
General characteristics
Insulation class H Excitation system AREP or PMG
Winding pitch 2/3 AVR type R 450
Number of wires 6 - (option 12) Voltage regulation (*) ± 0.5 %
Protection IP 23 Short-circuit current 300% (3 IN) : 10s
Altitude ≤ 1000 m Total Harmonic Distortion THD (**) in no-load ....: < 3.5 %
Overspeed 2250 min-1 Total Harmonic Distortion THD (**) on linear load: < 3.5 %
Air flow 1.8m3/s, 50 Hz - 2.2m3/s, 60 Hz Waveform: NEMA = TIF (**) < 50
(*) Regulator input voltage, steady state, within the below total harmonic distortion (THD) limits.
(**) Total harmonic distortion between phases, no-load or on-load (non-distorting).
Efficiencies 50 Hz
94 P. F.: 0.8
94 93.7
P. F.: 0.8
93.7
93.2 93
93
0 200 400 600 800 1000 1200 1400 kVA 0 200 400 600 800 1000 1200 1400 1600kVA
L7 - (6 w)
L8 - (6 w)
15
L8 - (12 w)
VL10 - (6 w)
Voltage drop
10
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 kVA
kVA at P.F. 0.8
20 % M6 - (12 w) L7 - (6 w) L8 - (6 w) L8 - (12 w)
VL10 - (6 w)
15
Voltage rise
10
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 kVA
kVA at P.F. 0.8
25
20
Voltage drop
15
12%
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 kVA
1430 Locked rotor kVA
1 ) For a PF with a φ other than 0.6, multiply the kVA by K = Sin φ / 0.8
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
Example of calculation for a PF with a φ other than 0.6: motor starting kVA calculated at PF 0.4 = 1250 kVA
Calculation example for a different P.F. other than 0.6: Starter motor kVA calculated at 0.4 P.F. = 1250 kVA
Sin φ 0.4 = 0.9165 K = 1.145 corrected kVA = 1430 kVA Voltage drop for VL10 = 12 %.
➤ Sin P.F. 0.4 = 0.9165 ➤ K = 1.145 ➤ kVA corrected = 1430 kVA ➤ Voltage dip corresponding to VL10 = 12%.
2 ) For a voltage U other than 400 V (Y), 230 V ( ) at 50 Hz, multiply the kVA by (400/U) 2 or (230/U) 2.
2) For voltages other than 400V (Y), 230V (D) at 50 Hz, then kVA must be multiplied by (400/U)2 or (230/U)2.
Efficiencies 60 Hz
LSA 50.2 M6 - (version: 6 wires) P. F.: 1
LSA 50.2 L8 - (version: 6 wires)
96.3 97% 96.6
96.3 96.5
96% 96.3
96.6
P. F.: 1
95.7 P. F.: 0.8
96 96.1
95 95.3
95 95.3
95.6 95.2
95 94.8 95 95.4
P. F.: 0.8
94
94
93.2
93 92.7 93.7 93.3
93
200 400 600 800 1000 1200 1400 1600 1800 kVA 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 kVA
LSA 50.2 L7 - (version: 6 wires) P. F.: 1 LSA 50.2 VL10 - (version: 6 wires) 96.7 P. F.: 1
96.5
97%
96.4 96.4 96.7
96% P. F.: 0.8
96.7
95.2 96 P. F.: 0.8
95.8 95 96.1
95.4
95 95.5
95.8 95.6
95.5
95
94
93.2
94
93 93.8
92.7 93.4
93
200 400 600 800 1000 1200 1400 1600 1800 2000 kVA 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 kVA
93 94
93.5
92.2 93.1
92 93
0 200 91.8 400 600 800 1000 1200 1400 kVA 200 400 600 800 1000 1200 1400 1600 1800 2000kVA
L8 - (6 w)
L8 - (12 w)
15
VL10 - (6 w)
Voltage drop
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 kVA
kVA at P.F. 0.8
15
Voltage rise
10
0
0 250 500 750 1000 1250 1500 1750 2000 2250 2500 kVA
kVA at P.F. 0.8
25
Voltage drop
20
15
13%
10
0
0 500 1000 1500 2000 2500 3000 3500 4000 4500 5000 kVA
1786 Locked rotor kVA
1 ) For a PF with a φ other than 0.6, multiply the kVA by K = Sin φ / 0.8
1) For a starting P.F. other than 0.6, the starting kVA must be multiplied by K = Sine P.F. / 0.8
Example of calculation for a PF with a φ other than 0.6: motor starting kVA calculated at PF 0.4 = 1560 kVA
CalculationSin
example
φ 0.4 =for a different
0.9165 K P.F. other than
= 1.145 0.6: Starter
corrected kVA =motor kVA calculated
1786 kVA Voltageatdrop
0.4 for
P.F.VL10
= 1560 kVA
= 13 %.
➤ Sin P.F. 0.4 = 0.9165 ➤ K = 1.145 ➤ kVA corrected = 1786 kVA ➤ Voltage dip corresponding to VL10 = 13%.
2 ) For a voltage U other than 480 V (Y), 277 V ( ), 240 V (YY - 12 wires only) at 60 Hz
2) For voltages other than 480V (Y), 277V (D), 240V (YY) at 60 Hz, then kVA must be multiplied by (480/U)2 or (277/U)2 or (240/U)2.
multiply the kVA by (480/U) 2 or (277/U) 2 or (240/U) 2 .
100000
1000
time (ms)
100000
Symmetrical
LSA 50.2 M6
Asymmetrical
10000
Current (A)
1000
time (ms)
100000
1000
1000
time (ms)
100000
Symmetrical
LSA 50.2 VL10
Asymmetrical
10000
Current (A)
1000
time (ms)
8
Cable
output
753
Access to
A.V.R.
1203
Ø N - 0.127
- 0.050
Ø BX - 0.100
Ø 368
ØP
0
Ø 786
Ø 284
450 - 2
+1
M12
PMG option
25
Access to
rectifiers 100
8 Air outlet 1 hole M24 Air inlet 600 50
50
210 470 240 700
7 800 1 hole Ø 35 214 36 S DIA, XBG eq. sp. hole on M PCD
Ø 160
Ø 100
Ø 140
Ø 170
Ø 145
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Flange S.A.E. 18 Flange S.A.E. 21
Type Xr Lr M J Xr Lr M J
LSA 50.2 S4 564 1320.5 833 18.17 549 1320.5 831 18.62
LSA 50.2 M6 608 1420.5 934 20.6 593 1420.5 932 21.09
LSA 50.2 L7 643 1520.5 1005 22.23 627 1520.5 1003 22.68
LSA 50.2 L8 667 1520.5 1082 24.6 652 1520.5 1081 25.05
LSA 50.2 VL 10 714 1620.5 1192 27.27 698 1620.5 1191 27.72
NOTE : Dimensions are for information only and may be subject to modifications. Contractual 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.
The torsional analysis of the transmission is imperative. All values are available upon request.
Cable
210 output
753
Access to
A.V.R.
Ø120 m6
Ø 787.4 - 0.127
1203
18 109
0
2x2 hole Ø 35
Ø 880
Ø 368
2x2 hole M24
32
Ø 786
450 - 1
0
M12
PMG option
25
Access to
rectifiers 100
Air outlet Air inlet 600 50
50
285 685 700
7 425 405 60 214 36
210
Ø 188.5
Ø 120
Ø 130
Ø 160
Ø 100
Ø 145
Ø 140
Ø 170
Lr
Centre of gravity: Xr (mm), Rotor length: Lr (mm), Weight: M (kg), Moment of inertia: J (kgm2): (4J = MD2)
Type Xr Lr M J
LSA 50.2 S4 590 1509 761 16.58
LSA 50.2 M6 632 1609 862 19.05
LSA 50.2 L7 667 1709 932 20.63
LSA 50.2 L8 690 1709 1010 23
LSA 50.2 VL10 736 1809 1120 25.67
NOTE : Dimensions are for information only and may be subject to modifications. Contractual 2D drawings can be downloaded from the Leroy-
Somer site, 3D drawing files are available upon request.
The torsional analysis of the transmission is imperative. All values are available upon request.
Linkedin.com/company/Leroy-Somer
Twitter.com/Leroy_Somer_en
Facebook.com/LeroySomer.Nidec.en
YouTube.com/LeroySomerOfficiel
© Nidec 2017. The information contained in this brochure is for guidance only and does not form part of
any contract. The accuracy cannot be guaranteed as Nidec have an ongoing process of development