Company: Project: Engineering Contractor:

OFFSITES ENGINEERING WORKS


FOR THE ERBIL REFINERY
40,000 B/D EXPANSION PROJECT

Contract no.: 10J01762-01


Company doc. no.: Job no.: 10J01762 Engineering doc. no.:
N/A Sheet 1 of 30 10J01762-ICT-DS-000-008

OFFSITES ENGINEERING WORKS FOR THE


ERBIL REFINERY 40,000 B/D EXPANSION PROJECT

DATA SHEET FOR RADAR LEVEL TRANSMITTERS

D1 19/09/2011 Re-Approved for Design Lucarelli Pagliardini Cilia


D0 27/07/2011 Approved for Design Lucarelli Pagliardini Cilia
C0 30/03/2011 Issued for Company approval Mariotti Pagliardini Cilia
REV. DATE REVISION TITLE PREPARED CHECKED APPROVED

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 2 of 30 10J01762-ICT-DS-000-008

FIXED ROOF TANK APPLICATION


REFERENCE DRAWINGS

TANK TAG CAPACITY (m3) DIAMETER (mm) HEIGHT (mm)

01 FUEL OIL TK-02D 13000 33000 16000

02 FUEL OIL TK-02E 13000 33000 16000

03 FUEL OIL TK-02F 13000 33000 16000

04 DIESEL FUEL TK-04E 3000 19420 12000

05 DIESEL FUEL TK-04F 3000 19420 12000

06 DIESEL FUEL TK-04G 4250 21000 13000

07 DIESEL FUEL TK-04H 4250 21000 13000

08 FIREWATER TK-2511 6000 22310 16000

09 SOUR WATER TK-1101 100 6000 4000

10 PLANT FUEL (DIESEL) TK-2414 500 8720 8000

11 PLANT FUEL (FUEL OIL) TK-2416 500 8720 8000

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 3 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-02D 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-003 44 MATERIAL AISI 316 SS
03 SERVICE Fuel oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-02D 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Fuel oil 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.2 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 100 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 881 (@71°C) 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note1) 900 - 13600 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 130 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear / %
18 TANK HEIGHT (d) (mm) 16000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 33000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
D1
21 EXT. NOZZLE DIM. ( a, b) 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET for 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 4 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-02E 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-003 44 MATERIAL AISI 316 SS
03 SERVICE Fuel oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-02E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Fuel oil 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.2 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 100 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 881 (@71°C) 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 900 - 13600 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 130 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 16000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 33000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 5 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-02F 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-003 44 MATERIAL AISI 316 SS
03 SERVICE Fuel oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-02F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Fuel oil 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.2 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 100 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 881 (@71°C) 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 900 - 13600 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 130 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 16000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 33000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 6 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-04E 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-005_1 44 MATERIAL AISI 316 SS
03 SERVICE Diesel fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-04E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Diesel fuel 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 7 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-04F 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-005_1 44 MATERIAL AISI 316 SS
03 SERVICE Diesel fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-04F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Diesel fuel 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 8 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-04G 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-005_2 44 MATERIAL AISI 316 SS
03 SERVICE Diesel fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-04G 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Diesel fuel 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 11000 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 13000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 21000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 9 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-04H 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-005_2 44 MATERIAL AISI 316 SS
03 SERVICE Diesel fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-04H 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Diesel fuel 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 11000 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 13000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 21000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 10 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-2511 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-012_1 44 MATERIAL AISI 316 SS
03 SERVICE Firewater tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-2511 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID water 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 80 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 30 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 997 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 1200 - 15000 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 16000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 22310 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 11 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-1101 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-015 44 MATERIAL AISI 316 SS (NACE)
03 SERVICE Sour water tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-1101 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Sour water 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 80 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 57 54 FLANGE MATERIAL ASTM A 105 (NACE) *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 997 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 600 - 3400 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) 0.05 / 90 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 4000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 6000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 (NACE) 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82 SOUR SPEC Required, NACE MR0175


37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 12 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-2414 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-018 44 MATERIAL AISI 316 SS
03 SERVICE Plant fuel tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-2414 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Plant fuel (Diesel) 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 600 - 6800 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 130 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 8000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 8720 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 13 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FIXED ROOF TANK)


01 TAG NO. 3#-LIT-2416 43 TYPE CONE *
02 P&ID 10J01762-PRO-DW-000-018 44 MATERIAL AISI 316 SS
03 SERVICE Plant fuel tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-2416 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL (c) *

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged top of extension nozzle 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Plant fuel (Fuel Oil) 51 ANTENNA EXTENSION *
10 DIELECTR. CONST. (εR) 2.2 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 4” flanged, free propagation
12 OP. TEMPERATURE (°C) 100 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 881 (@71°C) 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 600 - 6800 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - EXTENSION NOZZLE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 130 (note 1) 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM (note1) Cone roof/cone curv. inward 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (d) (mm) 8000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 8720 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 EXT. NOZZLE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 EXT. NOZZLE DIM. ( a, b) D1 4” / 250 mm (note 3) 65 CONSUMPTION *
22 DIST. TO TANK WALL (c) ~ 1/6 of tank diameter (*) 66 LOAD LIMITATION *
INSTALLATION

23 MEASURING DISTANCE (e) (mm) HOLD (note 1) 67 DIAGNOSTIC/ERROR SIGNAL *


24 FLANGE MATERIAL ASTM A 105 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent * 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 14 of 30 10J01762-ICT-DS-000-008

FLOATING ROOF TANK APPLICATION


REFERENCE DRAWINGS

TANK TAG CAPACITY (m3) DIAMETER (mm) HEIGHT = c (mm)

01 CRUDE OIL TK-01E 15000 35000 17000

02 CRUDE OIL TK-01F 15000 35000 17000

03 CRUDE OIL TK-01G 15000 35000 17000

04 CRUDE OIL TK-01H 15000 35000 17000

05 KERO/JET FUEL TK-05D 2500 17000 12000

06 KERO/JET FUEL TK-05E 2500 17000 12000

07 KERO/JET FUEL TK-05F 2500 17000 12000

08 NAPHTHA TK-03D 3000 19420 12000

09 NAPHTHA TK-03E 3000 19420 12000

10 HDT NAPHTHA TK-03F 2000 15000 12000

11 GASOLINE TK-012E 3000 19420 12000

12 GASOLINE TK-012F 3000 19420 12000

13 GASOLINE TK-012G 3000 19420 12000

14 GASOLINE TK-012H 3000 19420 12000

15 SLOP TK-06C 2500 17000 12000

16 SLOP TK-06D 2500 17000 12000

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 15 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-01E 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-002_1 44 MATERIAL AISI 316 SS
03 SERVICE Crude oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-01E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Crude oil 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 10÷30 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
840 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 3000 - 14500 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 17000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 35000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 18000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 16 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-01F 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-002_1 44 MATERIAL AISI 316 SS
03 SERVICE Crude oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-01F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Crude oil 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 10÷30 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 840 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 3000 - 14500 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 17000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 35000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 18000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 17 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-01G 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-002_2 44 MATERIAL AISI 316 SS
03 SERVICE Crude oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-01G 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Crude oil 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 10÷30 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 840 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 3000 - 14500 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 17000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 35000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 18000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 18 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-01H 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-002_2 44 MATERIAL AISI 316 SS
03 SERVICE Crude oil storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-01H 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Crude oil 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 10÷30 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
840 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 3000 - 14500 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 17000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 35000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 18000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 19 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-05D 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-006 44 MATERIAL AISI 316 SS
03 SERVICE Kero/ jet fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-05D 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Kero/ jet fuel 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 1.8 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 764 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 17000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 20 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-05E 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-006 44 MATERIAL AISI 316 SS
03 SERVICE Kero/ jet fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-05E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Kero/ jet fuel 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 1.8 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 764 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 17000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 21 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-05F 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-006 44 MATERIAL AISI 316 SS
03 SERVICE Kero/ jet fuel storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-05F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Kero/ jet fuel 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 1.8 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 764 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 17000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 22 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-03D 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-007 44 MATERIAL AISI 316 SS
03 SERVICE naphtha storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-03D 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID naphtha 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 665 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 23 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-03E 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-007 44 MATERIAL AISI 316 SS
03 SERVICE naphtha storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-03E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID naphtha 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 665 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 24 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-03F 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-008 44 MATERIAL AISI 316 SS
03 SERVICE HDT naphtha storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-03F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID HDT naphtha 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
711 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 2000 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 15000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 25 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-012E 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-009_1 44 MATERIAL AISI 316 SS
03 SERVICE gasoline storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-012E 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID gasoline 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 730 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 2000 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 26 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-012F 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-009_1 44 MATERIAL AISI 316 SS
03 SERVICE gasoline storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-012F 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID gasoline 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
730 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 2000 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 27 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-012G 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-009_2 44 MATERIAL AISI 316 SS
03 SERVICE gasoline storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-012G 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID gasoline 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
730 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 2000 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 28 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-012H 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-009_2 44 MATERIAL AISI 316 SS
03 SERVICE gasoline storage tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-012H 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID gasoline 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 2.0 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷50 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -
14 DENSITY @ T&P (kg/ m3)

PROBE
730 56 MATERIAL -
D1
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 2000 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 19420 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 29 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-06C 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-010 44 MATERIAL AISI 316 SS
03 SERVICE slop tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-06C 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Kerosene, fuel oil, diesel.. 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 1.8÷2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷60 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 665÷814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 17000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011


OFFSITES ENGINEERING WORKS FOR THE ERBIL REFINERY 40,000 B/D EXPANSION PROJECT
DATA SHEET FOR RADAR LEVEL TRANSMITTERS
Company doc. no.: Rev.: C0 D0 D1 Engineering doc. no.:
N/A Sheet 30 of 30 10J01762-ICT-DS-000-008

RADAR LEVEL TRANSMITTER (TOP LEVEL, FLOATING ROOF TANK)


01 TAG NO. 3#-LIT-06D 43 TYPE ARRAY or CONE *
02 P&ID 10J01762-PRO-DW-000-010 44 MATERIAL AISI 316 SS
03 SERVICE slop tank 45 BEAM DIAMETER / ANGLE *
04 LINE/EQUIPMENT NO. TK-06D 46 MOUNTING NOZZLE MAX HEIGHT *
05 MANUFACTURER/MODEL N. * 47 MIN. REQ. DIST. TO TANK WALL -

ANTENNA
06 TYPE Radar transmitter 48 DIMENSION *
07 MOUNTING Flanged on still pipe 49 MAX. GENERATED POWER LEVEL *
GENERAL

08 AMBIENT TEMPERATURE 0÷50°C 50 MAX. ALLOW. PRESS./TEMP. *


09 FLUID Kerosene, fuel oil, diesel.. 51 ANTENNA EXTENSION -
10 DIELECTR. CONST. (εR) 1.8÷2.1 52 PROCESS SEAL (MAT./THICKNESS) *
11 ELE.CONDUCTIVITY (µS/cm) - 53 ANTENNA INSTALLATION 6” Flanged on still pipe
12 OP. TEMPERATURE (°C) 38÷60 54 FLANGE MATERIAL ASTM A 105 *
13 OP. PRESSURE (bar g) ATM 55 TYPE -

PROBE
14 DENSITY @ T&P (kg/ m3) 665÷814 56 MATERIAL -
Min Norm Max 57 DIMENSION -
15 LEVEL RANGE (mm) (note 1) 800 - 10200 58 PROCESS SEAL (MAT./THICKNESS)
STORAGE TANK - STILL PIPE 59 TYPE/COMUNICATION Smart / HART protocol
16 DESIGN PRESS./TEMP. (bar g/°C) ATM / 90 60 INDICATOR Digital LCD remote display
17 VESSEL SHAPE / BOTTOM Floating roof tank 61 DISPLAY SCALE/UNIT Linear /%
18 TANK HEIGHT (c) (mm) 12000 62 ROTATABLE HEAD Yes
TRANSMITTER

19 TANK DIAMETER (mm) 17000 63 OUTPUT SIGNAL 4-20 mA (two wire)


20 STILL PIPE Flanged, RF ANSI 300# 64 SUPPLY VOLTAGE 24 VDC (loop powered)
21 STILL PIPE DIM. ( a, b) 6” / 13000 mm (note 3) 65 CONSUMPTION *
22 FLANGE MATERIAL ASTM A 105 66 LOAD LIMITATION *
INSTALLATION

23 67 DIAGNOSTIC/ERROR SIGNAL *
24 68
EXTERNAL CHAMBER 69
25 NOMINAL SIZE - 70
26 MATERIAL - 71 MATERIAL/DIMENSION Aluminium / Mfr. Std.
ENCLOSURE

27 PROCESS CONN. SIZE/TYPE - 72 CABLE ENTRY NO./TYPE (*) / ISO M20x1.5mm


28 CONNECTION ORIENTATION - 73 MECHANICAL PROTECTION IP 65 (min)
29 CONN. DISTANCE - 74 ELECTRICAL CERTIFICATION Ex-d IIB T3 / ATEX 94/9/EC
30 CONNECTION MATERIAL - 75 PROTECTIVE COATING/COLOR Epoxy / Mfr. Std.
31 PROTECTIVE COATING/COLOR - 76 SPURIOUS ECHOES REMOVAL Required
32 CONNECTION SIZE/TYPE DRAIN - 78 TROPICALIZATION Required
33 DRAIN VALVE INCLUDED - 79 TAG – DATA PLATE/MTL. Required / SS
34 TECHNOLOGY EMPLOYED FMCW or Equivalent 80 TWO WIRE REMOTE INDICATOR Required Ex-d IIB T3
ACCESSORIES

35 CALIBRATED RANGE 0÷100% * 81 INDICATOR MOUNTING BRACKET For 2” standpipe


INSTRUMENT CHARACT.

36 CHARACTERISTIC Linear 82
37 ACCURACY/RESOLUTION (*) / (*) 83
38 LOWER/UPPER RANGE LIMITS Mfr. Std. 84
39 MIN/MAX SPAN Mfr. Std. 85
40 ZERO/SPAN ADJUSTEMENT Yes 86
41 MAX RATE OF LEVEL CHANGES * 87
42 UPPER / LOWER DEAD ZONE * 88
NOTES:
(*) Supplier to fill in / confirm.
(1) Data are preliminary and shall be confirmed / provided by tank Manufacturer.
(2) The following documents shall be included in the supply: Technical bulletins, O&M manuals, calibration certificates, mechanical and electrical protection certificates,
material certificates as required on purchaser requisition documents.
(3) Data to be communicated to the tank Manufacturer.

File name: 10J01762-ICT-DS-000-008-D1.doc Printed on 20/09/2011