HG Power Transmission Sdn. BHD.: Method Statement
HG Power Transmission Sdn. BHD.: Method Statement
Description
1.0 Line Test
FIGURE 1
HG Power Transmission Sdn. Bhd.
1.7.1 Using the 5kV insulation test set, check the phasing of the
transmission line to ensure correct as per marking.
1.7.2 When inducted is voltage higher than 1 kV, the test can be
performed by grounding one point of the line under test. Connect
the yellow and blue to earth and underground the red phase (the
grounded phase has no voltage).
1.7.3 Repeat test no 11.5.3.2 for yellow and blue phasing check.
1.7.4 Record the result.
1.8.1 Using the 5 kV insulation test set, check the insulation of the
transmission line. Check for each phase to ground and phase-to-
phase conditions.
1.8.2 If induced voltage if higher than 1 kV in non-earthed condition, the
test cannot be performed. It will damage the test equipment. From
the results of the induced voltage measurement, it show the
conductor not shorted to ground.
1.9.1 Ground all three phases line at remote end. Check the induced
voltage in this condition. (Note : If the induced voltage is higher
than 100 V all the testing involve the impedance test cannot be
proceed)
1.9.2 Connect the surge/lighting arrester and injection test equipment
(T3000) as per FIGURE 2.
HG Power Transmission Sdn. Bhd.
T 3000 ZL
D-10A/D-90V
ZL
COMMON ZL
FIGURE 2
1.9.3 Before start injection, test current must be suitable with line length in
km as shown in table below
1.9.4 Inject the voltage to circuit (phase to phase) slowly increase the
voltage output and verify the corresponding line impedance and
angle. Stop injection when the value is stable. (Note : All the results
automatically calculated by T3000 set)
2.1.1 Ground all three phases line at remote end. Check the induced
voltage in this condition. (Note : If the induced voltage is higher
than 100 V all the testing involve the impedance test cannot be
proceed).
HG Power Transmission Sdn. Bhd.
ZL
T3000
D-10A / D-90V ZL
COMMON ZL
FIGURE 3
LINE 1
ZL
T 3000
D-10A / D-90V
ZL
COMMON
ZL
10A 10V
ZL LINE 2
ZL
ZL
HG Power Transmission Sdn. Bhd.
2.1.3 Before start injection, test current must be suitable with line length in km
as shown in table below.