CALCULATION
1 ) REFERENCE STANDARD :
MV CABLE SIZING :
IEC 60502-1
IEC 60502-2
IEC 60332
IEC 60287-3-1
IEC 60865-1-Part. 1
IEC 60949
LV CABLE SIZING :
IEC 60287
2.1.2. LV Cables
Type of cables:
Core Stranded copper, class 2
Shape Round
Rated voltage [Uo/U (Um)] 0.6 / 1 kV
Maximum permissible core temperature:
Normal conditions (permanently energized) 90°C
Fault current conditions 250°C
Insulation XPLE
External sheath PVC (IEC 60332)
Armoured No
Standard IEC 60502-1 / IEC 60364-5-52
2.6) De-rating factor for different laying methods : As per Cable manufacturer data sheet.
2.7) Current carrying capacities, AC Resistance at 90 deg. C and Reactance values : As per Cable
manufacturer data sheet.
2.8.1 Voltage drop during normal (Steady state condition) shall be restricted to 4%
2.8.2 Voltage drop during starting (Starting condition) shall be restricted to 15%
3) FORMULAS :
D = De-rating factor
Z = Impedance
4.2 Cable vendor data sheets shall be enclosed during detail engineering.
4.3 Tabular List of all cable sizing sheet shall be enclosed during detail engineering.
4.1) Sample Cable Sizing Calculation
General Specification
1. Maximum voltage drop
2. Interupting Capacity
3. Derating factor for cable As per IEC Standard & Manufacturer's data
Formula
Drive A
Motor Specificaton
Motor Name Conveyor drive A
Base voltage (V) 400 V
Motor Capacity (P) 75 KW
Frequency 50 Hz
Type of motor Squirrel Cage Type
Motor Starting Current (I (ST)) 6 times FLC
Motor PF 0.85
Efficiency (IE2 class as per IEC) 0.85
Motor Starting PF (assumed) 0.40 (squirrel cage motor)
Cable specification
Selected Cable Cu,3c x 70 sqmm (armoured)
Current rating for selected cable (ground) 209 A
Max length of motor cable (estimated) 126 m
Resistance of cable (ohm/km) 0.268
ohm/km
Reactance of cable (ohm/km) 0.075
ohm/km
Short Circuit withstand 8.05 kA / 1 second
Derating factor 0.90
Number of runs 1.00
Calculation
Calculation for Ampacity of conductor
1
Full Load Current (I (FLC)) 149.8 A
Thermal Ampacity selected cable 188 A
Thermal Ampacity selected cable > Full Load Current (Condition Satisfy)