Casing Ambient Diff. Temp. Temp Temp. ° C ° C ° C (S) (A) (DT) 1 45 30 15 2 45 30 15

You might also like

Download as xlsx, pdf, or txt
Download as xlsx, pdf, or txt
You are on page 1of 3

OUTER WALL CASING AMBIENT DIFF.

DIA TEMP. TEMP. TEMP TEMP.


S.No LOCATION
mm °C °C °C °C
( Do ) ( O ) ( S ) ( A ) ( DT )
1 Steam Line 168 350 45 30 15
2 Process steam line 88.9 160 45 30 15

( 2000 x K x ( O - S ) ) / ( F x ( S - A ) ) = ( Do + 2 x L ) ln (( Do + 2 x L ) / Do )

Insulation material ; LRB Mattress


Thermal Conductivity as per IS 8183
WIND EMMISSIVITY FILM MEAN THERMAL MIN. INSULN. DENSITY
VELOCITY OF SURFACE COEFFICIENT TEMP. CONDUCTIVITY THK. REQD. OF INSULN L.H.S
M/S Kcal/hm^2°c °C Kcal/hm² °C mm Kg/m^3
( V ) ( E ) ( F ) ( MT ) ( K ) ( L min ) ( Rho )
1 0.2 8 197.5 0.069402 118.00 100 352.79
1 0.2 8 102.5 0.045958 34.00 100 88.09

+ 2 x L ) / Do )
Note: Make LHS equal to RHS by changing L min
R.H.S

354.49
89.13

You might also like