VFL
Closed Circuit Cooling Towers
Product Detail
Engineering Data ....................................................................................... C2
Closed Circuit Cooling Towers
Structural Support .................................................................................... C5
Engineering Data
REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data
current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product
improvement, specifications, weights and dimensions are subject to change without notice. Up-to-date engineering
data and more can be found at www.BaltimoreAircoil.com.
VFL 24 X - VFL 48 X
VFL
1. Fluid in ND100; 2. Fluid Out ND100; 3.Access Door; 4. Make Up ND25; 5. Overflow ND50 for VFL 24X - VFL 36x and ND80 for VFL 48X; 6.
Drain ND50; 7. Vent ND15.
Spray
Operating Shipping Heaviest Air Fan Pump Coil
Model No. H L L2 W Water
Weight Weight Section Flow Motor Motor Volume
VFL (mm) (mm) (mm) (mm) Flow
(kg) (kg) (kg) (m3/s) (kW) (kW) (L)
(l/s)
VFL 241-H 1950 1280 1280 1855 3350 1820 1250 7,6 4 5,9 0,55 (1x) 176
VFL 242-H 2220 1460 1460 2015 3350 1820 1250 7,4 4 5,9 0,55 (1x) 229
VFL 242-J 2230 1490 1490 2015 3350 1820 1250 8,1 5,5 5,9 0,55 (1x) 229
VFL 243-J 2470 1670 1670 2230 3350 1820 1250 7,9 5,5 5,9 0,55 (1x) 282
VFL 361-L 2800 1810 1810 1855 4560 2730 1250 12,7 11 9,0 0,75 (1x) 258
VFL 361-M 2810 1820 1820 1855 4560 2730 1250 13,8 15 9,0 0,75 (1x) 258
VFL 362-M 3130 2090 2090 2090 4560 2730 1250 13,4 15 9,0 0,75 (1x) 338
VFL 363-K 3470 2280 2280 2350 4560 2730 1250 10,8 7,5 9,0 0,75 (1x) 418
VFL 363-M 3540 2350 2350 2350 4560 2730 1250 13,0 15 9,0 0,75 (1x) 418
VFL 481-M 3490 2170 2170 1855 5480 3650 1250 15,1 15 12,1 1,1 (1x) 341
VFL 482-L 3930 2490 2490 2090 5480 3650 1250 13,6 11 12,1 1,1 (1x) 448
VFL 483-L 4390 2830 2830 2350 5480 3650 1250 13,4 11 12,1 1,1 (1x) 556
VFL 483-M 4400 2840 2840 2350 5480 3650 1250 14,6 15 12,1 1,1 (1x) 556
VFL 484-M 4860 3170 3170 2560 5480 3650 1250 14,3 15 12,1 1,1 (1x) 664
Baltimore Aircoil
VFL - C 3
VFL 72 X - VFL 96 X
Spray
Operating Shipping Heaviest Air Fan Pump Coil
Model No. H L1 L2 W Water
Weight Weight Section Flow Motor Motor Volume
VFL (mm) (mm) (mm) (mm) Flow
(kg) (kg) (kg) (m3/s) (kW) (kW) (L)
(l/s)
VFL 721-L 5150 3150 3150 1855 4560 2730 2400 20,0 11 17,9 1,1 (2x) 258
VFL 721-M 5160 3160 3160 1855 4560 2730 2400 21,8 15 17,9 1,1 (2x) 258
VFL 721-O 5190 3190 3190 1855 4560 2730 2400 24,6 22 17,9 1,1 (2x) 258
VFL 722-N 5880 3700 3700 2090 4560 2730 2400 22,8 18,5 17,9 1,1 (2x) 338
VFL 722-O 5900 3720 3720 2090 4560 2730 2400 24,0 22 17,9 1,1 (2x) 338
VFL 723-L 6610 4210 4210 2350 4560 2730 2400 19,3 11 17,9 1,1 (2x) 418
VFL 723-O 6650 4250 4250 2350 4560 2730 2400 23,4 22 17,9 1,1 (2x) 418
VFL 724-O 7320 4790 4790 2560 4560 2730 2400 22,9 22 17,9 1,1 (2x) 498
VFL 961-P 6520 3850 3850 1855 5480 3650 2400 28,7 30 24,2 2,2 (2x) 341
VFL 962-N 7285 4360 4360 2090 5480 3650 2400 24,5 18,5 24,2 2,2 (2x) 448
VFL 962-O 7310 4400 4400 2090 5480 3650 2400 25,9 22 24,2 2,2 (2x) 448
VFL 962-P 7400 4500 4500 2090 5480 3650 2400 28,3 30 24,2 2,2 (2x) 448
VFL 963-O 8210 5060 5080 2350 5480 3650 2400 25,6 22 24,2 2,2 (2x) 556
VFL 963-P 8310 5160 5160 2350 5480 3650 2400 27,9 30 24,2 2,2 (2x) 556
VFL 964-P 9300 5810 5810 2560 5480 3650 2400 27,4 30 24,2 2,2 (2x) 664
General Notes
1. All location dimensions for coil connections are approximate and 5. Fan cycling results only in on-off operation. For additional steps
should not be used for prefabrication of connecting piping. of control, two-speed fan motors are available. More precise
capacity control can be obtained with modulation fan discharge
2. If discharge hoods with positive closure dampers are furnished, dampers or a BALTIGUARD® Drive System
see table in section Engineering Data – Straight Discharge Hood
with PCD for added weight and height. 6. Make up, overflow, suction, drain connections and access door
can be provided on side opposite to that shown; consult your
3. For external static pressure up to 125 Pa use next larger motor BAC Balticare representative.
size.
7. Shipping/operating weights indicated are for units without
4. For indoor applications of fluid coolers, the room may be used as accessories such as sound attenuators, discharge hoods, plume
a plenum with ductwork attached to the discharge only. If inlet abatement coils, etc. Consult factory certified prints to obtain
ductwork is required, an enclosed fan section must be specified; weight additions and the heaviest section to be lifted.
consult your BAC Balticare representative for details.
Sound Attenuation
HD Horizontal Intake Sound Attenuation
VFL
1.Discharge attenuator, 2. Access Door, 3. Intake Attenuator; W & H = Unit Dimensions (See Engineering Data).
Baltimore Aircoil
VFL - C 5
Structural Support
REMARK: Do not use for construction. Refer to factory certified dimensions & weights. This brochure includes data
current at time of publication, which should be reconfirmed at the time of purchase. In the interest of product
improvement, specifications, weights and dimensions are subject to change without notice. Up-to-date engineering
data and more can be found at www.BaltimoreAircoil.com.
The recommended support arrangement for units consists of parallel I-beams running the full length of the unit, spaced as shown in the following
drawing. Besides providing adequate support, the steel also serves to raise the unit above any solid foundation to ensure access to the bottom
of the unit. To support units in an alternate steel support arrangement, consult your BAC Balticare Representative.
1. (4) Ø 22 mm mounting holes; 2. Support Beams; 3. Fan Side; 4. Outline of Unit; 5. Outline of Attenuator “HD” (optional).
Notes:
1. The recommended support arrangement for these units consists accordance with standard structural practice. For the maximum
of two parallel I-beams extending the full length of the unit. allowable deflection of beams under the unit refer to above table.
Supports and anchor bolts are to be designed and furnished by
others. 4. All mounting holes have a diameter of 22 mm at the locations
shown.
2. All supporting beams are to be flush and level at top and must be
oriented relative to gage line as shown. 5. If vibration isolators are used, a rail or channel must be provided
between the unit and the isolators to provide continuous unit
3. Recommended design loads for each unit support beam should support. Additionally the support beams must be designed to
be 70% of the total unit operating weight applied as a uniform accommodate the overall length and mounting hole location of
load to each of the unit beams. Beams should be designed in the isolators that may differ from those of the unit. Refer to
vibration isolator drawings for these data.
Engineering Specifications
1.0 Closed Circuit Cooling Tower
1.0 General: Furnish and install ____factory assembled, forced draft, compound and the exterior protected with the Baltiplus Corrosion
centrifugal fan, closed circuit cooling tower(s) with vertical air Protection.
discharge, conforming in all aspects to the specifications and (Alternate1.3.) Corrosion Resistant Construction: Unless
schedules as shown on the plans. Overall dimensions shall not otherwise noted in this specification, all steel panels and structural
exceed approximately ____mm long x ____mm wide x ____ mm members shall be protected with the BALTIBOND® Corrosion
high. The total connected fan kW shall not exceed ____kW. The total Protection System. The system shall consist of Z600 metric hot-dip
connected pump kW shall not exceed ____kW. The closed circuit galvanized steel prepared in a four-step (clean, pre-treat, rinse, and
VFL
cooling tower(s) shall be Baltimore Aircoil Company Model(s) dry) process with an electrostatically sprayed, thermosetting hybrid
________________. polymer fuse-bonded to the substrate during a thermally activated
1.2. Thermal Capacity (water as heat transfer fluid): The closed- curing stage and monitored by a 23-step quality assurance program.
circuit cooling tower(s) shall be warranted by the manufacturer to cool (Alternate 1.3) Corrosion Resistant Construction: Unless
______l/s of _______ water from ____°C to ____°C at ____°C otherwise noted in this specification, all steel panels and structural
entering wet-bulb temperature. members shall be constructed of Type 304 or 316 stainless steel and
(Alternate1.2.) Thermal Capacity (aqueous glycol solution as heat assembled with stainless steel nut and bolt fasteners.
transfer fluid): The closed circuit cooling tower(s) shall be warranted 1.4. Quality Assurance: The closed circuit cooling tower
by the manufacturer to cool ________l/s of _____% by volume manufacturer shall have a management system certified by an
ethylene/propylene glycol solution from ______°C to _____°C at accredited registrar as complying with the requirements of ISO-
_____°C entering wet-bulb temperature. Coil pressure drop shall not 9001:2000 to ensure consistent quality of its products and services.
exceed ________bar.
1.5. Warranty: The manufacturer’s standard equipment warranty
1.3. Corrosion Resistant Construction: Unless otherwise noted in shall be for a period of not less than one year from date of startup or
this specification, all steel panels and structural members shall be eighteen months from date of shipment, whichever occurs first.
constructed of heavy-gauge Z600 metric hot-dip galvanized steel,
with all sheared edges given a protective coating of zinc-rich
Baltimore Aircoil
VFL - C 7
5.0 Access
5.1 Basin Access: Circular access doors shall be provided for easy routine maintenance.
access to the make-up water assembly and suction strainer for
6.0 Sound
5.1 Sound Level: To maintain the quality of the local environment, cooling tower operating at full fan speed shall not exceed the sound
the maximum sound pressure levels (dB) measured 15 m from the levels detailed below.
Discharge
Air Inlet
End
Back