Product 2009911738599531
Product 2009911738599531
Application
Applied to power distribution of AC 50Hz/60Hz, rated operational voltage 400/
690V, rated current 200A~6300A and lower
For power distribution and protecting circuit and power supply equipment aganist
harm from overload, undervoltage, short circuit, earthing, and other faults
Circuit breaker which ampere frame size is under 630A can protect motor aganist
overload,undervoltage and shortcircuit
Core parts use intelligent control unit which has accurate discrimination protection, it
can avoid unnecessary power failure and enhance the reliability of power supply
system
42 Delixi Electric
CDW7
Standard: IEC 60947-2
Delixi Electric 43
CDW7
Standard: IEC 60947-2
Protection characteristics
Keypad
Measure key l, used to switch to the default measurement menu.
Set key 2, used to switch to the parameter setting menu.
Protection Key 3, used to switch to the protection parameter setting menu.
Info key 4, used to switch to the historical record and maintenance menu.
Up, Move up the cursor through the menu items on the current level, or
increment the value of the selected parameter.
Down, Move down the cursor through the menu items on the current
level, or decrement the value of the selected parameter.
Exit, exit from the current level and return to the upper level, or cancel the
current parameter selection.
Select, Select to enter into the next level from the current item, or select the
current parameter, or store the change.
44 Delixi Electric
CDW7
Standard: IEC 60947-2
Delixi Electric 45
CDW7
Standard: IEC 60947-2
46 Delixi Electric
CDW7
Standard: IEC 60947-2
ECWS- H
Different curves Four phase current (I1, Up to 8 fault logs LCD display of MCR and out-of-limit
available for long time I2, I 3, IN) and earth Up to 8 alarm logs Chinese GUI tripping protection
delay protection current Up to 8 position logs LED indication DO Signal alarm function
Different curves Thermal capacity Historical current peak Key operation Communication function
available for inverse Contact equivalence
short time delay protec- Number of operating
tion cycles
Definite short time delay Clock function
protection Self-diagnosis function
Instantaneous protection
Current unbalance (open
phase) protection
Earth protection
Earth fault alarm
Neutral phase protection
Load monitor
ECW - M Long time delay protec- Max. phase current Fault log Digital display DO Signal alarm function
tion Four phase current (I1, Self-diagnosis LED indication MCR and out-of-limit
Definite time delay + I2, I 3, IN) and earth function Key operation tripping protection
inverse time delay for current Feature test Digital setting of Earth fault or leakage
short time delay protec- function protection param- protection (either)
tion eters
Instantaneous protection
Earthing protection
Load monitor
ECW - H Different curves Four phase current (I1, Up to 8 fault logs LCD display of Over-voltage protection
available for long time I2, I 3, IN) and earth Up to 8 alarm logs Chinese GUI Under-voltage protection
delay protection current Up to 8 position logs LED indication Voltage unbalance
Different curves Thermal capacity Historical current Key operation protection
available for inverse peak Over-currency protection
short time delay protec- Contact equivalence Under-frequency
tion Number of operating protection
Definite short time delay cycles Phase protection
protection Fault clock function Inverse power protection
Instantaneous protection Self-diagnosis fault Demand protection
MCR and out-of-limit log Zonal system interlock
tripping protection Self-diagnosis protection
Current unbalance (open function Communication function
phase) protection Feature test
Earth protection function
Earth fault alarm
Neutral phase protection
Load monitor
Delixi Electric 47
CDW7
Standard: IEC 60947-2
CDW7-1000 CDW7-2000~6300
ECWS-H intelligent control- ECW-M intelligent controllers ECW-H intelligent controllers
lers
Ir1=(0.4~1)ln Ir1=(0.4~1)ln Ir1=(0.4~1)ln
1.05 Ir1 h 2h 2h 2h
1.3 Ir1 h 2h 1h 1h
1.5Ir1 8,12.8,19.2,32,48,64,80, 15,30,60,120,240,480 15,30,60,120,240,360,480,
108,144,224,320,480,640, 600,720,840,960
800,960,1120
2.0Ir1 3.32,5.32,8.00,13.32,20.00, 8.4,16.9,33.8,67.5,135,270 8.4,16.9,33.8,67.5,135,202.
26.66,33.30,45.00,60.00, 5,270,337.5,405,472.5,540
93.32,133,200,266,333,
400,433
3.0Ir1 1.25,2.00,3.00,5.00,7.50,
10.0,12.5,16.8,22.5,35.0,
50.0,75.0,100,125,150,162
0.1s~1s (Rank difference 0.1s) 0.1~0.4s (Rank difference 0.1s) 0.1s~1s(Rank difference 0.1s)
48 Delixi Electric
CDW7
Standard: IEC 60947-2
Auxiliary functions
AC 380V AC220V
(0.35~0.7)Ue (0.35~0.7)Ue
(0.85~1.1)Ue (0.85~1.1)Ue
0.35Ue 0.35Ue
36VA 24VA
5VA 5VA
Delixi Electric 49
CDW7
Standard: IEC 60947-2
AC-15 DC-13
10 1
1 1
U/Ue 1 1
cos 0.95 0.3 6Pe
I/Ie 10 1.1
U/Ue 1.1 1.1
cos T0. 0.3 6Pe
10 10
50 Delixi Electric
CDW7
Standard: IEC 60947-2
Delixi Electric 51
CDW7
Standard: IEC 60947-2
CDW7-1000A drawout type circuit breaker outline and horizonal/vertical wiring Unit:mm
L L1 L2 L3 L4 n H
200, 400 3P 284 194 - 55 63 6 6
630 284 194 - 75 83 12 8
800, 1000 284 194 - 75 83 12 10
200, 400 4P 354 264 70 55 63 8 6
630 354 264 70 75 83 16 8
800, 1000 354 264 70 75 83 16 10
52 Delixi Electric
CDW7
Standard: IEC 60947-2
CDW7-2000A~3200A
CDW7-2000 mounting dimension is same regardless of different current used in"horizonal-wiring" or"vertical-wiring"
Delixi Electric 53
CDW7
Standard: IEC 60947-2
CDW7-2000A~6300A
CDW7-2000A~6300A drawout type circuit breaker outline and horizonal/vertical connection Unit:mm
L1 L2 L3 L4 L5 W1 W2 b In A a
CDW7-2000 3P 375 335 292 265 247 461 507 179 400~800 10
375 335 292 265 247 461 507 179 1000~1600 15
4P 470 430 292 360 247 461 507 179 2000 20
CDW7-3200 3P 435 395 352 325 307 471 517 189 2000~2500 20
4P 550 510 352 440 307 471 517 189 3200~4000 30
CDW7-6300 3P 813 773 352 703 307 494 540 212 4000 20
(4000/5000A) 4P 928 888 352 818 307 494 540 212 5000~6300 30
CDW7-6300 3P 928 888 352 818 307 494 540 212 5000~6300 30
note: 1) CDW7-2000 the mounting dimension is same regardless of different current used in"horizonal-connected" or "vertical-connected"
54 Delixi Electric
CDW7
Standard: IEC 60947-2
CDW7-1000
CDW7-1000A CDW7-1000A
CDW7-2000~6300
CDW7-2000~6300A
CDW7-2000~6300A
Delixi Electric 55
CDW7
Standard: IEC 60947-2
56 Delixi Electric
CDW7
Standard: IEC 60947-2
Pin functions: Note: 1. If the control voltage values of Q, F, X, and M are different to each
Pin 1# and 2#: Auxiliary power input,pin 1# is other, these components can be connected to different power supply units; in the
positive for DC input application, the shunt release and closing electromagnet shall be connected
Pin 3#, 4#, 5#: Fault trip contact output (4# is serially with normally open and normally closed auxiliary contacts (the part
common terminal); contact capacity: AC380V, 16A enclosed by dotted lines shall be connected by the user; the part represented by a
Pin 6# and 7#, 8# and 9#: Two groups of auxiliary two-dot chain line is the wiring of circuit 51);
contacts for breaker status; contact capacity: Note 2: The pin 35# can be connected to the power supply directly (automatic
AC380V, 16A pre-energy storage) or connected serially to a normally open button and then to
the power supply (manual pre-energy storage);
12#,13#(Contact1)and 14#,15#(Contact2)and 16#,
Note 3: If the user requests, pin #6~#7 can be connected to normally closed
17#(Contact3)and 18#,19#(Contact4):Output of
contacts;
four groups of signal for controllers,contact
Note 4: The ECW power supply module I is a DC power supply module, and it
capacity:4A/240V 7A/24VDC
can be omitted if the power supply is AC power supply; the polarity and lead-ins/
20#: Earth protection
lead-outs shall not be reversed (for draw-out type circuit breakers, the lead-outs
21#~24#:input of voltage signal (Note:the order cant
of the power supply module has been connected before the circuit break is
be wrong)
shipped from the factory);
Note 5: In case of circuit 47, the auxiliary contacts are four closed and four
Components: open contacts; pin #25 and #26 are input terminals of an external current trans-
Q - Under-voltage release former , used for earth fault protection as (3P+N)T type ;
F - Shunt release Note 6: In case of circuit 51, the auxiliary contacts are six closed and six open
X – Closing electromagnet contacts (or five closed and five open contacts); pin #25, #26, and #51 form
DF - Auxiliary switch normally open and normally closed contacts;
M - Motor Note 7: If Profibus or any other protocol is used, ECW-H + DP conversion module
SB1—Button for closing and other conversion modules must be ordered; ECW power supply module lV and
SB2—Button for shunt ECW201 relay module must be ordered separately;
Note 8:Pin #12~#19 input/output contacts can be user-defined programmable
signal contacts.
Delixi Electric 57
CDW7
Standard: IEC 60947-2
58 Delixi Electric
CDW7
Standard: IEC 60947-2
Delixi Electric 59
CDW7 Series Air Circuit Breakers
Order Instructions
Under-voltage trip
Under-voltage time-delay trip 1s 3s 5s
60 Delixi Electric