Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO.

3, JULY 2011 1829

Adaptive Protection of Parallel Transmission


Lines Using Combined Cross-Differential
and Impedance-Based Techniques
Majid Sanaye-Pasand, Senior Member, IEEE, and Peyman Jafarian, Student Member, IEEE

Abstract—This paper introduces a state-diagram-based pro- the relay location, is greatly useful for the protection of parallel
tective algorithm for parallel circuit transmission lines using transmission lines.
local information obtained at the relay bus. A new cross-dif- It is well known that if the conventional distance relay is ap-
ferential technique is proposed which compares the currents in
the corresponding phases of the parallel circuits in a 2-D space. plied to protect parallel lines assuming them as independent cir-
A companion impedance-based algorithm is used to cover the cuits, the relay performance would be degraded due to the ef-
evolving faults and some conditions in which the cross-differential fect of the mutual coupling between the parallel circuits. If the
technique is not able to discriminate the internal faults alone. setting of a distance relay is adjusted at 85% of the line posi-
The effect of the mutual coupling between parallel circuits on
the measured impedances is adaptively compensated according tive-sequence impedance, it might only cover 50% of the line
to the status of the parallel circuit currents in the segmented 2-D length when both parallel circuits are in operation. Meanwhile,
space. The proposed state-diagram-based algorithm combines the coverage of this relay could become more than 100% when
the outputs of the cross-differential and impedance-based tech- one of the parallel circuits is out of service and grounded at both
niques to provide a reliable response under all of the operating
ends [4].
statuses of the parallel circuits. Extensive simulation studies using
PSCAD/EMTDC software indicate that the proposed approach To measure the fault-loop impedance more accurately, the
provides very reliable protection for the double-circuit transmis- compensation of the adjacent line zero-sequence current is
sion lines. It covers intercircuit and evolving faults, and is able to suggested in [5]–[7]. Even though this approach obviates the
reliably select the faulted phases. distance relay underreach problem when both of the parallel
Index Terms—Adaptive protection, cross-differential technique, circuits are in operation, it may not be able to improve the
digital relaying, mutual coupling, parallel transmission lines. impedance estimation accuracy for the latter operating status
of the parallel lines (i.e., when one of the circuits is out of
service and grounded at both ends). This is due to the fact
I. INTRODUCTION
that the current transformers (CTs) are installed behind the
ARALLEL circuit transmission lines installed on the same
P towers are extensively utilized in high-voltage transmis-
sion systems due to their significant advantages (i.e., high-power
circuit breakers (CBs) and, therefore, when the CB is open, the
transmission-line current is not available [8].
To achieve the optimal performance for the distance protec-
transfer capability, availability, and sharing the same right of tion of parallel transmission lines under different possible con-
way). On the other hand, the different possible configurations figurations, an adaptive method based on the availability of the
of parallel circuits depending on the transmission-line operating adjacent line zero-sequence current is proposed in [9]. It adjusts
status, combined with the mutual coupling effect as well as pos- the relay operation using some extra input signals indicating the
sibility of the occurrence of intercircuit faults, make their pro- transmission-line operating status. This method covers a higher
tection a challenging problem [1]. percentage of the transmission line under different configura-
The longitudinal current differential technique using a com- tions compared to a fixed-set distance relay. Nevertheless, it
munication link between the transmission-line ends could pro- may not be able to correctly select the faulted phases in the
vide a secure and dependable solution for the protection of par- case of intercircuit faults between dissimilar phases of the par-
allel transmission lines [2], [3]. Nevertheless, the reliability of allel circuits. Meanwhile, when the adjacent line zero-sequence
this protective scheme is dependent on the reliability of the com- current is not available, the relay setting should be reduced too
munication channel. Therefore, a stand-alone protective algo- much so that external faults beyond the remote bus do not cause
rithm, which is only based on the local information obtained at first-zone false tripping due to the overreach problem.
The cross-differential technique is based on the comparison
Manuscript received September 18, 2010; revised December 13, 2010; ac- between the currents in the corresponding phases of the par-
cepted April 05, 2011. Date of publication May 19, 2011; date of current ver- allel circuits. It identifies an internal fault when the difference
sion June 24, 2011. Paper no. TPWRD-00715-2010.
The authors are with the School of Electrical and Computer Engi-
between the two circuits currents exceeds a certain threshold
neering, Control and Intelligent Processing Center of Excellence, College [10]–[12]. This technique is immune to the mutual coupling ef-
of Engineering, University of Tehran, Tehran 14395-515, Iran (e-mail: fect and provides faster operation speed compared to the dis-
msanaye@ut.ac.ir). tance algorithm. An alternative approach is to compare the mea-
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. sured impedances for the corresponding phases of the parallel
Digital Object Identifier 10.1109/TPWRD.2011.2142014 circuits [13]. Nevertheless, these techniques can be employed
0885-8977/$26.00 © 2011 IEEE
1830 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

only when both parallel circuits are in operation, and should be


disabled promptly under other operating statuses. In addition,
the cross-differential technique is not able to identify remote
faults occurring at the end part of the transmission line as well
as some intercircuit faults involving similar phases of both par-
allel circuits.
Reference [14] describes a nonpilot protection algorithm for
parallel transmission lines based on detecting the operation of Fig. 1. Circuit diagram of a typical double-circuit transmission line.
the remote CB. The superimposed currents are used to detect the
opening of the remote CB. Therefore, the second zone operation
A. Proposed 2-D Cross-Differential Technique
of the distance relay is accelerated for internal faults occurring
at the end part of the transmission line. However, the perfor- The relay under study is installed at bus S, and is composed
mance of this algorithm is not verified for the case of evolving of three identical units for the three phases. Each unit protects
faults, where the fault extends to the other phases after some the corresponding phases of the parallel circuits simultaneously.
time delay. Since an evolved fault causes some changes in the The basic principle of the cross-differential technique relies on
superimposed waveforms, it could be mistaken for the operation the symmetry of currents in the corresponding phases of the
of the remote CB and may lead to relay maloperation. parallel circuits. It can be simply described by the following
This paper introduces a state-diagram-based algorithm for relationships [12]:
the protection of double-circuit transmission lines. The pro- Trip circuit
posed algorithm combines the outputs of cross-differential and
Trip circuit (1)
impedance-based techniques to provide a fast and reliable pro-
tective scheme. A new cross-differential technique is proposed where and denote the currents in the corresponding phases
which compares the currents of corresponding phases of the of circuit 1 and circuit 2, respectively. If the difference between
parallel circuits in a 2-D space. The 2-D space is segmented the amplitudes of the parallel circuits currents exceeds the
into six areas covering all possible operating statuses of the threshold , a trip signal would be sent to the associated CB.
parallel circuits. A companion impedance-based algorithm is The threshold is set in accordance with the maximum asym-
used to cover the evolving faults and some conditions in which metry experienced during the nonfaulty condition. Meanwhile,
the cross-differential technique is not able to discriminate the when a remote fault occurs on one of the circuits, the difference
internal faults alone. The impedance-based algorithm adap- between the parallel circuits currents could also be less than the
tively compensates for the mutual coupling effect depending defined threshold. As a result, the cross-differential algorithm
on the status of the parallel circuits currents in the segmented cannot cover the total length of the transmission line.
2-D space. For some operating statuses in which one of the The cross-differential technique provides high sensitivity and
parallel circuits is out of service and grounded at both ends, fast fault clearing when both of the parallel circuits are in opera-
the zero-sequence current of the grounded circuit is estimated tion. Nevertheless, when one of the circuits is out of service, the
to avoid the relay overreach problem. The proposed state-dia- aforementioned criterion is not valid anymore. In these condi-
gram-based algorithm uses the sequences of transitions between tions, the cross-differential algorithm must be disabled promptly
different defined states to help discriminate the internal faults. to prevent the relay maloperation. As a result, this algorithm is
Furthermore, it covers the end part of the transmission line via not able to identify evolving faults, where the fault extends to
detecting the operation of the remote CB using the sequence of the other line subsequently.
transitions. Moreover, in the case of single-pole tripping schemes, the
Extensive simulation studies are carried out by using the conventional cross-differential technique may incorrectly trip
power system simulation software PSCAD/EMTDC to in- a healthy phase after opening the faulted phase by single-pole
vestigate the proposed algorithm performance under different operation of the associated CB. This problem arises when the
conditions. The obtained results show that the proposed algo- remote CB operates after some time delay. Fig. 2 depicts the
rithm provides very reliable protection for the double-circuit current waveforms of phase C for a phase-A-to-ground fault
transmission lines under all possible operating statuses. It on circuit 1 of the parallel transmission line shown in Fig. 1.
covers intercircuit and evolving faults, and is able to reliably The fault is cleared after some cycles by single-pole tripping of
select the faulted phases. the CB BR1 at bus S. It is found that when the faulted phase is
opened, the current in phase C of the healthy circuit increases
whereas the current in phase C of the faulted circuit decreases.
II. PROPOSED RELAY PRINCIPLES
This condition remains until the remote end breaker BR3 opens
Fig. 1 depicts the circuit diagram of a typical double-circuit the faulted phase as well, and may cause a false trip on phase C
transmission line, which will be referred to in the following de- of the healthy circuit. A similar problem could arise for intercir-
scriptions. It is assumed that the CBs operate in the single-pole cuit faults between dissimilar phases of parallel circuits.
tripping (SPT) mode. However, if SPT operation is not avail- A solution is to adjust the threshold value ( ) so that the
able, the proposed protective algorithm can also be employed so maximum asymmetry of currents in the healthy phases of the
that the CB opens all of the three phases whenever an internal parallel circuits during through and after single-phase faults re-
fault is identified by the algorithm. mains less than the defined threshold. Nevertheless, this ap-
SANAYE-PASAND AND JAFARIAN: ADAPTIVE PROTECTION OF PARALLEL TRANSMISSION LINES 1831

TABLE I
POSSIBLE SYSTEM CONDITIONS CORRESPONDING TO DIFFERENT AREAS OF
THE PROPOSED 2-D CROSS-DIFFERENTIAL RELAY

Fig. 2. Current waveforms of phase C for a phase-A-to-ground fault on the


circuit 1. (a) Current of circuit 1. (b) Current of circuit 2.

line). Meanwhile, the circular border considered for the area S1


provides high flexibility to define an appropriate threshold for
the previously described single-pole tripping case. This is due
to the fact that while the current of one of the parallel circuits
increases, the current in the twin phase of the other circuit de-
creases and, therefore, the locus of the parallel circuits currents
for the healthy phases would remain inside a circular area.
Another advantage of the proposed 2-D cross-differential al-
gorithm is that the transitions of trajectory of the parallel circuits
currents between different areas could be used to detect the op-
eration of remote breakers, by which the relay operation for the
remote faults could be accelerated.
The proposed approach covers all of the parallel circuits op-
erating statuses and it is not necessary to be disabled when one
of the circuits is out of service. However, in some areas (i.e.,
Fig. 3. Two-dimensional space segmentation of the proposed cross-differential S1, S2, S4, and S6), some additional criteria are required to dis-
algorithm.
criminate internal faults occurring on the protected transmission
line. This is due to the fact that in these areas, different scenarios
proach reduces the coverage of the cross-differential relay for are possible for the transmission system condition as presented
the end part of the parallel transmission line. in Table I.
To obviate the aforementioned problems, this paper pro-
poses comparing the currents of the parallel circuits in a 2-D B. Adaptive Compensation of the Adjacent Line Zero-Sequence
space. Fig. 3 illustrates the 2-D space segmentation of the Current
proposed cross-differential algorithm. As can be found, six The mutual coupling between parallel circuits affects the
areas are defined based on the possible transmission system phase voltages measured at the relay bus. As a result, a distance
conditions under different parallel circuits operating statuses. relay, which does not include the mutual coupling effect in
Table I describes the possible transmission system conditions calculation of the impedance, would measure the fault-loop
corresponding to each area. impedance inaccurately. The worst scenario is the occurrence
Unlike the conventional cross-differential algorithm, the pro- of faults when one of the parallel circuits is out of service and
posed algorithm is able to discriminate between the normal and grounded at both ends. In such a condition, the conventional
faulty conditions in which the difference between the currents distance relay would overreach, and external faults occurring
in corresponding phases of the parallel circuits is less than the beyond the remote bus may be seen inside the relay first pro-
threshold (e.g., remote faults at the end part of the transmission tective zone [5], [9].
1832 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

where and denote the zero-sequence currents of the


circuit 1 at the sending and receiving ends, respectively; and
are the positive- and zero-sequence impedances of the cir-
cuit 2; is the zero-sequence mutual coupling impedance
between the parallel circuits; and is the per-unit distance be-
tween the fault point and the relay location.
It should be noted that is not a local signal available at
the relay bus, and is an unknown parameter. However, when
an external fault occurs beyond the remote bus, the zero-se-
quence current of the grounded circuit can be estimated accu-
rately by only using the local measurements

(3)
Fig. 4. Two possible conditions in which one of the parallel circuits is out of
service. (a) Switched-off circuit is grounded at both ends. (b) Switched-off cir- The overreach problem is not acceptable for a protective
cuit is open at both ends.
scheme. Using the zero-sequence current estimated by (3), the
undesired distance relay overreach can be prevented. In other
A compensating factor using the adjacent line zero-sequence words, external faults beyond the remote bus will not cause
current improves the impedance calculation accuracy for the false tripping on the protected parallel lines. However, in the
faulted circuit. However, this approach might cause false trip- case of internal faults, the zero-sequence current estimated by
ping on the healthy circuit for a close-in fault on one of the par- (3) is not accurate. In these conditions, the estimated current is
allel lines. Therefore, an extra criterion is required to determine higher than the actual value. Therefore, since the zero-sequence
the faulted circuit and apply the mutual coupling compensation current of the grounded circuit is in opposite direction to that of
only for the faulted circuit [9]. the circuit in service, the measured impedance would be greater
The proposed 2-D cross-differential technique provides a than the actual value and the distance relay would underreach. It
suitable approach to decide whether the impedance should should be considered that in this case, the underreach problem
be calculated including the mutual coupling compensation or is not as serious as the relay overreach problem. Moreover,
without compensation. For this purpose, when the locus of for internal faults occurring at the end part of the transmission
the parallel circuits currents lies inside the second or third line, the error caused by neglecting the effect of the remote-end
areas, the impedance of the circuit 1 is calculated including zero-sequence current ( ) is not considerable and, therefore,
the mutual coupling compensation, whereas the compensa- the result of using (3) becomes more accurate.
tion is not applied in impedance calculation for the circuit 2. Fig. 4 depicts two possible conditions in which one of the
Similarly, when the currents locus lies inside the fifth or sixth parallel circuits is out of service. In both of these cases, the
areas, the impedance of circuit 2 is calculated including the zero-sequence current of the switched-off circuit is not acces-
mutual coupling compensation, whereas the compensation is sible by the relay. In the first case shown in Fig. 4(a), the zero-se-
not applied in impedance calculation for circuit 1. For the cases quence current could flow in the grounded circuit whereas for
in which the currents locus lies inside the first or forth areas, the second case shown in Fig. 4(b), the zero-sequence current is
the mutual coupling compensation is included for both of the zero. By virtue of the arrangement of the voltage transformers at
parallel circuits. the relay bus, one can distinguish between these two conditions.
However, in some operating statuses, the zero-sequence cur- When the switched-off circuit is grounded at both ends, the mea-
rent of the adjacent line may not be accessible by the relay. This sured voltage by the relay is nearly zero. On the contrary, when
is due to the arrangement of the current transformers at the relay the line ends are open, the measured voltage is equal to that in-
bus. As shown in Fig. 4, the current transformers are installed duced due to the mutual coupling between the parallel circuits.
behind the CBs and, therefore, when the CB is open, the current Therefore, in the proposed algorithm, the zero-sequence current
of the respective line is not accessible by the relay. Unfortu- is estimated by (3) for the case of the grounded line, and is con-
nately, such a condition arises for the worst scenario in which sidered zero for the case of the nongrounded line.
one of the circuits is switched-off and grounded at both ends.
III. PROPOSED STATE-DIAGRAM-BASED
A solution is to install additional CTs so that the transmis-
DECISION-MAKING LOGIC
sion-line currents are always available. However, this solution
might not be practical. An alternative approach is proposed A. State-Diagram-Based Algorithm
in this paper which estimates the zero-sequence current of
To combine the outputs of the cross-differential and the
the grounded circuit using the local information accessible by
impedance-based techniques, a state-diagram-based algorithm
the relay. Referring to Fig. 4(a), if circuit 2 is out of service
is proposed in this paper. This way, the sequence of different
and grounded at both ends, its zero-sequence current can be
events in the transmission system could be recognized, which
estimated by
helps the relay to make fast and reliable decisions. It should be
considered that combining the outputs of different relays using
(2) a simple “OR” logic does not solve the problems that they may
SANAYE-PASAND AND JAFARIAN: ADAPTIVE PROTECTION OF PARALLEL TRANSMISSION LINES 1833

encounter in the protection of parallel lines individually. For TABLE II


example, if an impedance relay is used to protect the paralleled TRANSMISSION-LINE CONDITIONS UNDER DEFINED STATES
lines beside a cross-differential relay, it may cause a false trip on
the healthy line for a close-in fault on the adjacent line. As the
second example, when one of the paralleled lines is switched
off, the conventional cross-differential techniques should be
disabled promptly to avoid generating false trip on the line in
service. As the third example, when a remote fault occurs at
the end part of the transmission line, none of the conventional
cross-differential and impedance-based techniques are able to
discriminate the fault.
The proposed impedance-based distance algorithm consists
of two modules called and assigned for protection of
circuit 1 and circuit 2, respectively. Each of the impedance mod-
ules itself is composed of six elements. For each phase, three of
these elements cover all possible fault types in which the phase
under protection gets involved in the fault (e.g., for phase A, curs on circuit 1, the locus of the parallel circuits currents would
-G, - , and - elements of are used). The output move from the normal condition (i.e., the area S1), and lie inside
of each element becomes high when one of the following cri- the area S3. In this condition, an internal fault on circuit 1 is con-
teria is satisfied. cluded and a trip command would be sent to the associated CB
• The measured impedance by the element is located inside BR1. When BR1 opens, the current in the associated phase of
the first protective zone. the faulted circuit would decrease to almost zero, and the system
• The measured impedance by the element is located inside state would transit to state 6. During the transient interval, the
the second protective zone and its associated timer has ex- currents locus could lie inside the area S5 for a short period. The
pired. current amplitude in the twin phase of the healthy circuit might
Unlike the conventional distance relay in which a multiphase remain above the normal condition until the fault is cleared by
fault is detected if the output of any of the phase-to-phase opening the remote CB BR3. During state 6, the impedance
elements becomes high, the proposed algorithm identifies module continuously measures the line impedance and if
multiphase faults using the output of the phase units. The its output becomes high, an evolving fault would be concluded.
phase-to-phase elements of each unit are responsible to only As previously mentioned, does not include compensation
determine whether the fault involves the phase under protection for the mutual coupling effect. This is done to avoid generating
of any of the parallel circuits or not. This way, the outputs of false trips on the healthy circuit when close-in faults occurs on
impedance modules are supervised by the cross-differential the other circuit.
technique through the state-diagram-based algorithm to ensure If the fault evolves to the same phase of the circuit 2 before
correct identification of faulted phases in the case of intercircuit opening BR1, the currents locus would transit from state 3 to
faults. Meanwhile, the mutual coupling effect between the state 4. In this condition, the output is used to identify the
parallel circuits is adaptively compensated based on condition evolved fault on circuit 2 and to trip the associated CB BR2.
of the parallel circuits currents in the segmented 2-D space. Similarly, in the case of faults on circuit 2, the locus of the
For ease of illustration, some notations are adopted throughout current amplitudes of the parallel circuits lies inside the area S5
this paper to indicate the method of compensating the mutual and, consequently, a trip command would be sent to the associ-
coupling effect. Hereafter, and denote the impedance ated circuit breaker BR2. When BR2 opens, the current in the
modules whose fault-loop impedances are calculated without associated phase would decrease to zero, and the system state
compensating the mutual coupling effect between the parallel would transit to state 2. During state 2, the impedance module
circuits. and indicate that the mutual coupling effect continuously measures the line impedance and if its output
is compensated using the measured zero-sequence currents, becomes high, an evolving fault would be concluded.
and and indicate that the estimated zero-sequence 2) Part II: Fig. 5(b) illustrates the second part of the pro-
current of the adjacent circuit is used to calculate the fault-loop posed state-diagram-based algorithm. The locus of the parallel
impedance. circuits currents could lie inside the area S4 under different sce-
As presented in Table II, six states are defined based on the narios (i.e., remote faults occurring on one of the parallel lines,
different conditions of the locus of the parallel circuits currents intercircuit faults involving similar phases of both circuits, and
in the segmented 2-D space. The proposed state-diagram-based external faults). Table III summarizes the possible sequences of
algorithm is designed by performing extensive analysis and sim- state transitions for different scenarios.
ulation studies under different conditions. Fig. 5 depicts the pro- The proposed algorithm uses the sequences of the state tran-
posed algorithm, which is divided into three parts for ease of il- sitions to identify remote faults occurring at the end part of the
lustration, and each part is explained separately. transmission line, which cannot be covered by the conventional
1) Part I: Fig. 5(a) illustrates the first part of the proposed al- cross-differential and impedance-based relays. As an example,
gorithm. It covers internal faults occurring on one of the parallel a remote fault on circuit 1 is rapidly identified as a close-in fault
circuits when both of the circuits are in operation. If a fault oc- by the relay installed at the remote bus. Therefore, the remote
1834 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

TABLE III
STATE TRANSITIONS FOR DIFFERENT SCENARIOS OF PART II

would decrease, and the system state would transit to the state 2
or the state 3 depending on the loading condition [Fig. 5(b)]. In
such a condition, a remote fault on circuit 1 is concluded and a
trip command would be issued to CB BR1.
Similarly, when a remote fault occurs on circuit 2, the remote
relay trips CB BR4 and, consequently, the system state transits
to state 5 or state 6 depending on the loading condition. In this
condition, a remote fault on circuit 2 is concluded and a trip
command would be issued to CB BR2.
In the case of external faults, the state diagram transits
from state 1 to state 4. It remains in state 4 until the fault is
cleared by the associated protective relay. When the external
fault is cleared, the state transits back to state 1. Meanwhile,
the impedance modules and provide backup protection
for the remote transmission line. These modules measure the
impedance, including the mutual coupling effect compensation
using the measured zero-sequence currents. If an external fault
is not cleared before expiration of the second zone timers of
and , CBs BR1 and BR2 would be tripped to isolate the
fault.
In the case of inter-circuit faults involving similar phases of
both circuits, the locus of the parallel circuits currents could also
lie inside the area S4. These faults are covered by the impedance
modules and . The impedance modules and pro-
vide fast operation speed for faults occurring in their first pro-
tective zone, and cover the end part of the transmission line in
their second protective zone. It should be considered that these
intercircuit faults rarely occur in practice due to the arrangement
of the three phases on the tower structure.
3) Part III: The third part of the proposed algorithm is il-
Fig. 5. Proposed state-diagram-based algorithm. (a) Part I. (b) Part II.
(c) Part III. lustrated in Fig. 5(c). It is used to protect the transmission line
when one of the parallel circuits is out of service. As previously
mentioned, the zero-sequence current of the switched-off circuit
relay would trip the associated CB BR3. When BR3 opens, the may not be accessible by the relay due to the arrangement of the
current in the twin phase of the healthy circuit (i.e., circuit 2) current transformers. As an example, when circuit 2 is switched
SANAYE-PASAND AND JAFARIAN: ADAPTIVE PROTECTION OF PARALLEL TRANSMISSION LINES 1835

off, its phase currents are measured as zero, and the state tran-
sits to state 2. During state 2, continuously measures the
line impedance, and if its output becomes high, a fault would
be concluded. uses the estimated zero-sequence current to
compensate for the mutual coupling effect, where the distance
relay first zone overreach is prevented to avoid false tripping due
to external faults beyond the remote bus.
Similarly, when circuit 1 is switched off, the state transits to
state 6. During state 6, the impedance module continuously Fig. 6. One-line diagram of the simulated transmission system.
measures the line impedance and protects the transmission line
in operation.
power system simulation software PSCAD/EMTDC is used to
B. Implementation of the Proposed Algorithm perform the simulations. The sampling frequency is considered
As described, the proposed algorithm uses the sequences of to be 1440 Hz, which corresponds to the sampling rate of 24
transitions between the defined states to recognize different sce- samples per cycle. The simulation data are used in a MATLAB
narios and make its decision. For this purpose, a buffer is used program to implement the proposed algorithm.
to store the state transitions. The buffer length is selected as six, The signals fundamental phasors are extracted by using
and it is refreshed whenever the state changes. For each new the full-cycle Fourier algorithm (FCDFT). The phasor esti-
relay input sample, the present state is checked and if it is dif- mation error due to the decaying dc component is eliminated
ferent from the last state stored in the top cell of the buffer, the by using the method proposed in [16]. The first zone setting
buffer would be shifted and the present state would be stored at of the impedance-based relays is adjusted at 90% of the line
its top cell. positive-sequence impedance.
For the cross-differential module, a counter-based algorithm The performance of the proposed protective algorithm is
is used to determine the area in which the locus of the par- tested under different operating statuses of the parallel circuits.
allel circuits currents is located. This is done to provide a ro- Various simulation studies are carried out by changing the
bust algorithm during transient transitions between the states. fault location, the fault resistance, the fault type, and the fault
One counter is assigned for each of the six defined areas. Each inception angle. For each fault, all three units assigned for
counter is increased by one, whenever a new sample lies inside the three phases are simultaneously checked to ensure the
the corresponding area. Otherwise, if a counter is greater than correct response of the proposed algorithm in the selection
zero and the new sample is not located inside its corresponding of the faulted phases, which is necessary for the purpose of
area, it would be decreased by two. An area index is used in single-pole tripping. The obtained results are described in the
the relay and is changed to point to a new area when the corre- following text. It should be noted that many simulation studies
sponding counter exceeds a certain threshold. were also performed for different loading conditions, and for
Similarly, a counter-based algorithm is used for the all of these cases, the proposed algorithm was able to correctly
impedance-based modules. The output of each impedance identify the fault. However, due to the limited space, just
module becomes active only if the number of measured some representative cases are presented to verify the proposed
impedance samples located inside the relay zone is greater algorithm performance.
than a certain threshold. This way, a robust fault detection
algorithm against the fault-induced transients is obtained for A. Close-In Faults
the impedance relays.
Some of the obtained results for close-in faults on the trans-
The state-diagram-based algorithm continuously checks the
mission line AB are presented in Table IV. It should be noted
present state and accordingly performs the corresponding sub-
that since both of parallel circuits are identical, only the simula-
routine. In each subroutine, the state buffer is used to recognize
tion results for faults on circuit 1 are presented here. As previ-
the sequence of various events and make the final decision.
ously mentioned, the proposed protective algorithm consists of
three identical units for protecting the three phases. Each unit
IV. SIMULATION STUDIES AND ANALYSIS protects the corresponding phases of the parallel circuits. In the
Extensive simulation studies are carried out to evaluate the case of multiple-phase faults, all three phases are tripped. How-
performance of the proposed algorithm. The circuit diagram of ever, in order to verify the proposed algorithm ability for the
the transmission system under study is depicted in Fig. 6, in classification of different fault types, the last column shows the
which denotes the relay which protects the parallel trans- faulted phases identified by the proposed algorithm.
mission line AB. The frequency-dependent distributed model The problem associated with the close-in faults on parallel
of the transmission line is used to accurately include the in- transmission lines is false tripping on the healthy circuit, which
fluence of the generated transients after the fault occurrence. is caused by compensating the faulted circuit zero-sequence cur-
Meanwhile, an appropriate model of the capacitor voltage trans- rent in calculation of the healthy circuit impedances. Fig. 7 de-
former (CVT) is employed to include the CVTs influences on picts the impedance trajectory of the circuit 2 measured by the
the measured voltage waveforms [15]. The parameters of the A-G element for the sixth case presented in Table IV. As can
simulated transmission system are given in the Appendix . The be seen in Fig. 7(a), if the healthy line impedance is calculated
1836 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

TABLE IV TABLE V
PROPOSED ALGORITHM RESPONSE FOR CLOSE-IN FAULTS ON CIRCUIT 1 PROPOSED ALGORITHM RESPONSE FOR REMOTE FAULTS ON CIRCUIT 1

faults. If a close-in fault occurs on the circuit 1 when both of


the parallel circuits are in operation, the locus of the parallel cir-
cuits currents falls inside the area S3. As a result, referring to the
proposed algorithm shown in Fig. 5(a), the protective algorithm
identifies the fault rapidly. In this condition, the impedance of
line 2 is calculated without compensation.
For the first case of Table IV, the proposed algorithm identi-
fies the faulted phase in 10.4 ms by using the output of the pro-
posed cross-differential technique. Thereafter, unit A of the pro-
posed protective algorithm continuously checks the impedance
of circuit 2 to detect whether the fault will evolve to phase A of
circuit 2 or not.
When circuit 2 is switched off, the locus of the parallel
circuits currents lies inside area S6. In these conditions (i.e.,
cases 10–19 of Table IV), the impedance module uses the
estimated zero-sequence current of circuit 2 to compensate
for the mutual coupling effect. As previously described, if the
switched-off circuit is grounded at both ends, its zero-sequence
Fig. 7. Measured impedance trajectory of the circuit 2 for a phase-A-to-ground current is estimated by (3), and if the switched-off circuit is
close-in fault on circuit 1. (a) With compensating the mutual coupling effect. (b) open, its zero-sequence current is considered zero.
Without compensation.
In all of the studied cases, the proposed protective algorithm
operates very reliably. It is able to well classify the faulted
with the compensation of the faulted circuit zero-sequence cur- phases, and no false trip is caused on the healthy phases. The
rent, the distance relay would incorrectly trip phase A of the proposed algorithm provides a correct response before, during,
healthy circuit. and after the fault-clearing interval.
Since the proposed algorithm uses the state diagram to de-
cide whether the line impedance should be calculated with the B. Remote Faults
mutual coupling compensation or without compensation, it pro- Table V presents some of the obtained results for remote
vides a very reliable response in identification of the close-in faults occurring at the end part of circuit 1. It should be consid-
SANAYE-PASAND AND JAFARIAN: ADAPTIVE PROTECTION OF PARALLEL TRANSMISSION LINES 1837

Fig. 9. Impedance of circuit 1 measured by the AG element for the external


fault on transmission-line BC. (a) Measured impedance by the conventional
relay. (b) Measured impedance by the proposed algorithm.
Fig. 8. Locus of the current amplitudes in phase A of the parallel circuits for
the sixth case of Table V.
part of the transmission line is protected by the relay second pro-
tective zone.
ered that a remote fault is rapidly identified by the remote relay
installed at bus B as a close-in fault. In the performed simulation C. External Faults
studies, it is assumed that the operation time of the remote end Various simulation studies were performed to investigate the
breakers is two cycles. proposed algorithm performance for the case of external faults.
When both of the parallel circuits are in operation, the locus If both of the parallel circuits are in operation, the lines im-
of the parallel circuits currents lies inside area S4 after the occur- pedances are calculated including compensation for the mu-
rence of a remote fault on any circuit. This condition indicates tual coupling effect which provides an accurate estimation of
that the transmission-line current is higher than the normal con- the fault location. If one of the parallel circuits is out of ser-
dition which might be caused by an external fault beyond the vice and grounded at both ends, the zero-sequence current of
remote bus or an internal fault at the end part of the transmis- the grounded circuit is not accessible by the relay due to the ar-
sion line. The proposed state-diagram-based algorithm uses the rangement of the current transformers.
sequences of transitions between the defined states to detect the Fig. 9 depicts the measured impedance for an external
operation of remote CBs due to internal faults. This way, the phase-A-to-ground fault on the transmission line BC at 5 km
relay operation is accelerated for the remote faults without using away from bus B, when circuit 2 is out of service and grounded
any communication link. at both ends. As can be seen, the impedance measured by the
As an example, the locus of the parallel line currents for the conventional distance relay is seen inside the relay first protec-
sixth case of Table V is depicted in Fig. 8. In this case, a remote tive zone due to the mutual coupling effect between parallel
phase-A-to-ground fault occurs at 125 km away from the bus circuits and, therefore, the relay overreaches. On the contrary,
A. The fault is cleared by opening the remote CB BR3 after two if the impedance is calculated by the proposed impedance
cycles. As can be seen, when opens the faulted phase, the module , which uses the zero-sequence current estimated by
locus of the parallel circuits currents moves from the area S4 to (3) to compensate for the mutual coupling effect, the overreach
the area S3. Consequently, the proposed algorithm identifies the problem is prevented. The estimated zero-sequence current of
fault as an internal remote fault on the circuit 1. For this case, the grounded circuit is depicted in Fig. 10. As can be seen,
the relay operation time is about 54.2 ms, whereas the operation for external faults, the proposed method provides accurate
time of the conventional distance relay scheme for such a fault estimation of the grounded circuit zero-sequence current.
is up to several hundreds of milliseconds.
When one of the parallel circuits is out of service, the trans- D. High-Resistance Faults
mission line is protected by the impedance module or , as Table VI presents some of the obtained results for the case of
shown in Fig. 5(c). As previously mentioned, if the switched-off high-resistance faults. Although a reasonable value for the fault
circuit is grounded at both ends, for the case of internal faults, resistance in reality is rarely more than 50 , higher values of
the zero-sequence current of the grounded circuit estimated by fault resistance are also considered in the performed studies to
(3) is not accurate, which leads to the relay underreach. Never- investigate the proposed algorithm performance.
theless, the farther the fault occurs, the more accurate the estima- The proposed cross-differential technique provides high
tion is obtained for the grounded circuit zero-sequence current. capability and sensitivity for discrimination of high-resistance
For the simulated parallel transmission system, it was found that faults. As a result, when both parallel lines are in operation,
if the first zone setting of the impedance relay is adjusted at 90% the proposed protective algorithm is able to well identify
of the line positive-sequence impedance, is able to cover high-resistance faults occurring on the protected transmis-
83% of the line length by its first protective zone. The remaining sion line. As an example, for the second case of Table VI, a
1838 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

TABLE VII
PROPOSED ALGORITHM RESPONSE FOR INTERCIRCUIT FAULTS

Fig. 10. Estimated zero-sequence current of circuit 2 for the external fault on
the transmission-line BC.

TABLE VI
PROPOSED ALGORITHM RESPONSE FOR HIGH-RESISTANCE FAULTS ON S4 to the area S3, and, therefore, the internal fault is identified
CIRCUIT 1 by the proposed protective algorithm.
In the other operating statuses of the parallel line, in which
one of the circuits is out of service, the proposed algorithm uses
the output of impedance-based modules to identify the internal
faults. Therefore, the first zone coverage of the protective algo-
rithm would be reduced by the increase of the fault resistance.
The worst condition for a high-resistance fault is the occur-
rence of the fault at the end part of the transmission line. The
quadrilateral characteristic used for the single-phase-to-ground
elements of the distance modules provides higher capability in
discrimination of high-resistance faults. It is able to identify
high-resistance faults up to several tens of ohms. The proposed
algorithm also covers very high-resistance faults in its backup
protective zones, although these faults rarely occur in prac-
tice. For example, the 11th and 15th cases of Table VI present
the simulation results for phase-A-to-ground faults, for which
the fault resistance is 100 . In these two case, the fault is
identified by the relay second protective zone. It should be
considered that the higher the fault resistance, the less the
fault current amplitude is. Therefore, the operation time of the
second zone is satisfactory for the cases of very high resistance
faults.

E. Intercircuit Faults
Many different simulation studies were performed to eval-
uate the proposed algorithm performance for intercircuit faults
phase-B-to-ground fault occurs at 80 km from the bus A. The where both of the parallel circuits get involved in the fault.
fault resistance is 200 . The proposed algorithm is able to Some of the obtained results are presented in Table VII. These
identify this fault in 18.1 ms. faults are common in double-circuit transmission lines installed
For the faults occurring at the end part of the protected trans- on the same towers. Since in the case of intercircuit faults, the
mission line, the proposed algorithm is able to identify very impedance measured by the distance relay is not directly the
high-resistance faults after clearing the fault by the remote CB. fault-loop impedance, identification of the faulted phases may
As an example, for the seventh case of Table VI, a high-resis- become difficult by the conventional impedance-based protec-
tance fault occurs at 129 km from the bus A on the circuit 1. The tive schemes. As an example, for an fault (i.e., an inter-
fault resistance is 200 . It is assumed that the remote CB circuit fault between phase A of circuit 1 and phase B of circuit
operates in two cycles. When the fault is cleared by opening 2), the conventional distance relay scheme issues three-phase
, the locus of the parallel line currents moves from the area trips on both parallel circuits.
SANAYE-PASAND AND JAFARIAN: ADAPTIVE PROTECTION OF PARALLEL TRANSMISSION LINES 1839

impedance modules are incorporated into the decision-making


logic. As stated in Section III-A, in each phase unit, elements of
the impedance-based modules just determine whether the fault
involves the phase under protection or not. Unit B of the pro-
posed algorithm is responsible for determining whether the fault
involves phase B of any of the parallel circuits or not. Therefore,
although for this fault, the impedance measured by the -
element of the may be seen inside the relay zone, no trip
signal is issued for phase A of circuit 2.

F. Evolving Faults
Evolving faults in which the fault evolves to the other phases
after some time delay are common in transmission systems.
Fig. 11. Measured impedances by A-B elements of the conventional distance
relay for the intercircuit A B G fault on the transmission line. (a) Impedance
Therefore, a protective scheme should be able to identify the
of circuit 1. (b) Impedance of circuit 2. faulted phases reliably not only for the initial incidence of a fault
but also throughout the entire duration of the fault. Many simu-
lations were performed to study the proposed algorithm perfor-
The proposed protective technique uses three independent mance for the case of evolving faults. Various conditions were
units for protection of the three phases. In each unit, the modeled in which the initial fault evolves to the other phases
proposed 2-D cross-differential technique protects the corre- after 10–50 ms. It was found that the proposed algorithm is able
sponding phases of both parallel circuits and supervises the to well classify the faulted phases for all conditions of evolving
companion impedance-based modules. Unlike the conventional faults. Meanwhile, it does not cause any false trip on healthy
distance relay in which a multiphase fault is detected if the phases during the transient interval of the fault-clearing process.
output of any of the phase-to-phase elements becomes high,
the proposed algorithm identifies multiphase faults by using V. CONCLUSION
the output of the phase units. For all of the studied cases, This paper introduces an adaptive protective algorithm for
the proposed algorithm is able to classify intercircuit faults parallel circuit transmission lines using the local information
very reliably and rapidly. The faulted phase of each circuit is obtained at the relay bus. The proposed algorithm uses the
correctly identified and single-pole tripping can be used just for state diagram to combine the outputs of cross-differential
the faulted phases. and impedance-based techniques. A new cross-differential
If an intercircuit fault occurs between two dissimilar phases technique is proposed which compares the corresponding
of the paralleled lines, the fault is identified by the cross-dif- phase currents of the parallel circuits in 2-D space. Unlike the
ferential modules of the associated phase units. Fig. 11 depicts conventional cross-differential technique, it is not necessary
the impedances measured by the A-B elements of the conven- to disable the proposed algorithm when one of the parallel
tional distance relay for the third case of Table VII. It is found circuits is switched off. The impedance-based algorithm is
that the conventional distance relay scheme incorrectly iden- supervised by the cross-differential technique and adaptively
tifies this fault as a phase-to-phase AB fault on both circuits. compensates the mutual coupling effect depending on the status
On the contrary, the proposed algorithm can correctly identify of the parallel circuits currents in the segmented 2-D space. For
the faulted phases based on outputs of the 2-D cross-differen- some operating statuses in which one of the parallel circuits is
tial modules of units A and B. For such a fault, the outputs out of service and grounded at both ends, the zero-sequence
of the impedance-based modules are not required for making current of the grounded circuit is estimated to obviate the
a decision. undesired overreach problem of the conventional distance
If an intercircuit fault including similar phases of the paral- relay. The state-diagram-based algorithm uses the sequences
leled lines occurs, the outputs of the impedance-based modules of transitions between different defined states to recognize the
are also incorporated into the decision logic. This is due to the possible different scenarios and makes the relay final decision.
fact that for these conditions, the difference between the corre- The performed simulation studies show that the proposed pro-
sponding phase currents of the paralleled lines is too small, and tective algorithm is able to classify the faulted phases very reli-
the currents locus lies inside area 4. For instance, in the fifth ably. When both of parallel circuits are in operation, the pro-
case of Table VII, which is an intercircuit fault, the posed algorithm operates quite fast, mostly in less than one
currents locus of the unit A lies inside area 3 while the currents cycle due to the high sensitivity of the cross-differential tech-
locus of unit B lies inside area 4. For this fault, the cross-differ- nique. Meanwhile, it provides a correct response during the tran-
ential module of unit A identifies an internal fault on circuit 1 sient interval of the fault-clearing process. In contrast to most
and makes a decision without using the impedance-based mod- other algorithms, the proposed algorithm covers intercircuit and
ules outputs. But the cross-differential module of unit B cannot evolving faults correctly and reliably. Moreover, it covers the
discriminate the fault alone. Referring to the proposed algo- end part of the transmission line by detecting the operation of
rithm shown in Fig. 5(b), in this condition, the outputs of the the remote-end CBs.
1840 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY 2011

[6] A. G. Phadke and L. Jihuang, “A new computer based integrated dis-


tance relay for parallel transmission lines,” IEEE Trans. Power App.
Syst., vol. PAS-104, no. 2, pp. 445–452, Feb. 1985.
[7] Y. Liao and S. Elangovan, “Digital distance relaying algorithm for first-
zone protection for parallel transmission lines,” Proc. Inst. Elect. Eng.,
Gen., Transm. Distrib., vol. 145, no. 5, pp. 531–536, Sep. 1998.
[8] IEEE Guide for Protective Relay Applications to Transmission Lines,
IEEE Std. C37.113-1999, Sep. 1999.
[9] Y. Hu, D. Novosel, M. M. Saha, and V. Leitloff, “An adaptive scheme
for parallel-line distance protection,” IEEE Trans. Power Del., vol. 17,
no. 1, pp. 105–110, Jan. 2002.
[10] M. I. Gilany, O. P. Malik, and G. S. Hope, “A laboratory investigation
of a digital protection technique for parallel transmission lines,” IEEE
Trans. Power Del., vol. 10, no. 1, pp. 187–193, Jan. 1995.
[11] M. M. Eissa and 0. P. Malik, “A new digital directional transverse di-
rectional current protection technique,” IEEE Trans. Power Del., vol.
11, no. 3, pp. 1285–1291, Jul. 1996.
[12] A. H. Osman and O. P. Malik, “Protection of parallel transmission line
using wavelet transform,” IEEE Trans. Power Del., vol. 19, no. 1, pp.
49–55, Jan. 2004.
[13] M. M. Eissa and O. P. Malik, “Laboratory investigation of a distance-
protection technique for double circuit lines,” IEEE Trans. Power Del.,
vol. 19, no. 4, pp. 1629–1635, Oct. 2004.
Fig. 12. Configuration and parameters of the simulated double-circuit trans- [14] Z. Q. Bo, X. Z. Dong, B. R. J. Caunce, and R. Millar, “Adaptive non-
mission line. communication protection of double-circuit line systems,” IEEE Trans.
Power Del., vol. 18, no. 1, pp. 43–49, Jan. 2003.
[15] D. A. Tziouvaras et al., “Mathematical models for current, voltage, and
coupling capacitor voltage transformers,” IEEE Trans. Power Del., vol.
APPENDIX 15, no. 1, pp. 62–72, Jan. 2000.
[16] Y. S. Cho, C. K. Lee, G. Jang, and H. J. Lee, “An innovative decaying
The equivalent source impedances are as follows: dc component estimation algorithm for digital relaying,” IEEE Trans.
Power Del., vol. 24, no. 1, pp. 73–78, Jan. 2009.

Majid Sanaye-Pasand (M’98–SM’05) received the


electrical engineering degree from the University
The configuration and parameters of the transmission line of Tehran, Tehran, Iran, in 1988, and the M.Sc. and
Ph.D. degrees from the University of Calgary, Cal-
under study are presented in Fig. 12. gary, AB, Canada, in 1994 and 1998, respectively.
His areas of interest include power system analysis
and control, digital protective relays, and application
REFERENCES of artificial intelligence. Currently, he is a Professor at
the School of Electrical and Computer Engineering,
[1] A. Apostolov, D. Tholomier, S. Sambasivan, and S. Richards, “Protec- University of Tehran, where he is also with the Con-
tion of double circuit transmission lines,” in Proc. 60th Annu. Conf. trol and Intelligent Processing Center of Excellence.
Protect. Relays Eng., TX, May 2007, pp. 85–101.
[2] S. Dambhare, S. A. Soman, and M. C. Chandorkar, “Adaptive current
differential protection schemes for transmission-line protection,” IEEE
Trans. Power Del., vol. 24, no. 4, pp. 1832–1841, Oct. 2009.
[3] S. Dambhare, S. A. Soman, and M. C. Chandorkar, “Current differen- Peyman Jafarian received the B.Sc. and M.Sc. de-
tial protection of transmission line using the moving window averaging grees in electrical engineering (Hons.) from the K. N.
technique,” IEEE Trans. Power Del., vol. 25, no. 2, pp. 610–620, Apr. Toosi University of Technology, Tehran, Iran, in 2003
2010. and 2006, respectively, and the Ph.D. degree from the
[4] A. G. Jongepier and L. van der Sluis, “Adaptive distance protection University of Tehran in 2010.
of a double-circuit line,” IEEE Trans. Power Del., vol. 9, no. 3, pp. His research interests include power system pro-
1289–1295, Jul. 1994. tection and control, digital protective relays, and real-
[5] P. G. McLaren, I. Fernando, H. Liu, E. Driks, and G. W. Swift, “En- time control of flexible ac transmission systems.
hanced double circuit line protection,” IEEE Trans. Power Del., vol.
12, no. 3, pp. 1100–1108, Jul. 1997.

You might also like