FM 200 Calculation and Flow Rate
FM 200 Calculation and Flow Rate
6 System flow calculation shall be within the manufacturer’s list from NFPA
2001.
As per National Fire Protection Association Code 2001 "NFPA2001"
Page 2001-13 Sec 3-2.1
7 FM200 concentration for class “A” fire is 7%. From manufacturer’s list.
As per KIDDE FM200 ESC Modular balanced Fire suppression System
Page 117 Table 3-2.1
8 Nozzle choice and location shall be in accordance with nozzle’s list limitation.
= 2.65 m x 3.20 m
= 8.48 m2
Room volume (V) = Area x Height
= 8.48 m2 x 2.97 m
= 25.186 m3
W =
25.19 7
( )
0.1374 100 7
= 13.79 Kg
Total Weight of FM- 200 required ( W)
Take Weight of FM- 200 Cylinder = 15.00 Kg
As per KIDDE Page 120 Table 3.6-1 Refer to attachment no. (24).
W =
30.30 7
( )
0.1374 100 7
W =
22.03 7
( )
0.1374 100 7
W =
31.21 7
( )
0.1374 100 7
W =
W =
178.60 7
( )
0.1374 100 7
= 0.1374
W =
444.5 7
( )
0.1374 100 7
W =
51.24 7
( )
0.1374 100 7
W =
51.24 7
( )
0.1374 100 7
W =
58.56 7
( )
0.1374 100 7
Qty. of Nozzles
As per KIDDE Page 129 Table 3.13.2.1 1 No. with thread size 2”.
Total Weight of FM- 200 required ( W) Refer to attachments No. (25-1).
FM-200 Calculations for Electrical Room No (006) At Ground Floor:
W =
58.56 7
( )
0.1374 100 7
Qty. of Nozzles
As per KIDDE Page 129 Table 3.13.2.1 1 No. with thread size 2”.
Total Weight of FM- 200 required ( W) Refer to attachments No. (25-1).
W =
40.40 7
( )
0.1374 100 7
W =
55.05 7
( )
0.1374 100 7
W =
32.79 7
( )
0.1374 100 7
W =
98.38 7
( )
0.1374 100 7
V C
( )
S 100 C
W =
58.56 7
( )
0.1374 100 7
W =
50.50 7
( )
0.1374 100 7
V C
( )
S 100 C
W =
48.80 7
( )
0.1374 100 7
W =
48.80 7
( )
0.1374 100 7
W =
48.80 7
( )
0.1374 100 7
W =
48.80 7
( )
0.1374 100 7
= 2.50 m x 4.00 m
= 10.00 m2
W =
48.80 7
( )
0.1374 100 7