Professional Documents
Culture Documents
Stair Pressurization - DAR ELHANDASA
Stair Pressurization - DAR ELHANDASA
Design Conditions
No. of Story 7
Height Per Story 5 M
Leakage Area Between Building & outside Per Story (Abo) 0.04 M2
Leakage Area Between Stairwell & Building Per Story (Asb) 0.02582 M2
Door Area 1 M2
Design Conditions
Outside Design Temprature 46 C°
Building Design Temprature 22 C°
No. of Story 6
Height Per Story 3.2 M
Flow Area Between Elevator & Building Per Story (Aeb) 0.042 M2
Flow Area Between Building & Outside Per Story (Abo) 0.05175 M2
Flow Area Between Elevator & Building Per Story (Aeb) 0.042 M2
Pressure Diffrence Between Elevator & Outside at the Floor Above Ground (dPeot) 36 Pa
Q(Flow Rate Required For The Rest of the Building) 732 L/s
Design Conditions
No. of Story 1
Height Per Story 3.2 M
Leakage Area Between Building & outside Per Story (Abo) 0.05375 M2
Leakage Area Between Lobby & Building Per Story (Asb) 0.048442 M2
Stairwell Wall
1 Tight 0.000014
2 Average 0.00011
3 Loose 0.00035
Doors
1 Single Leaf 0.024
2 Double Leaf 0.048
Elevator Wall
1 Tight 0.00018
2 Average 0.00084
3 Loose 0.0018
Floors
1 Tight 0.0000066
2 Average 0.000052
3 Loose 0.00017