FDB2 - A0 (A60) Fire and Gas Damper
FDB2 - A0 (A60) Fire and Gas Damper
FDB2 - A0 (A60) Fire and Gas Damper
FDB2
A0(A60) Fire And Gas Damper
Halton FDB2 fire dampers are type-approved class • Type-approved by most recoganized classification
A0(A60) fire and gas dampers for use in offshore and societies, class A0 - A60 fire and gas damper when
marine ventilation systems. The FDB2 can be installed suitably insulated
in rectangular or circular ducts. All fire dampers have a • Blades contain silicone (effective up to 300 ºC)
fusible link and they prevent the spread of fire and gases for low leakage in normal conditions and thermal
(low-leakage model) within the ventilation ductwork. expansion graphite seals (effective from 150 ºC)
When the blades are in the open position, the device to increase tightness even up to 50% in a case of
does not cause significant pressure loss, noise or flow fire. Tightness substantially better than NORSOK
disturbance. Fire dampers are set from outside and can requirements
be installed in any position. An open-closed indicator is • Nominal fuse release temperature 50 ºC, 74 ºC
visible on the outside of the damper. Fire dampers with or 100 ºC. Other temperatures available
non-standard dimensions can be supplied on request. • Low weight due to patented double skin blade
structure
• Automatic electrical, pneumatic or spring system
available
• Maximum duct pressure 5000 Pa and maximum air
velocity 15 m/s
DIMENSIONS S L
10
ø1
n*150
S, ACCORDING TO SOLAS
ACTUATOR
150
H+58
H+4
ØD
A
150
n*150
MIN. 50
150 150
361, S=3
10
n*150 n*150
18 MIN. 50
B+4 365, S=4
10 10 370, S=5
30 R B+58
2
CLOSE OPEN 5. OPTION:
SOLENOID VALVE
3 6
1 2 3 4 5 6 7 8 9 10 6. MALE CONNECTOR
8
7. DOUBLE NIPPLE 6 4
THERMAL SWITCH
ELMWOOD D070 (72°C)
8. PLASTIC TUBE
9. OPTION: 6
OPEN/CLOSED SWITCHES 3 8
6 10
10. OPTION:
MANUAL VALVE
6
11. PRESSURE REGULATOR
3 8
6 5
FUSIBLE LINK 12. MALE ELBOW
OPTION: 50/74/100°C
24V DC
230 VAC
13. SPEED CONTROLLER
6
3 8
1
S1
NOTICE !
S2
S3
S4
S5
S6