1 Input Data: Profis Anchor 2.8.0

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

www.hilti-me.com Profis Anchor 2.8.

0
Company: CSCEC Page: 1
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

Specifier's comments:

1 Input data
Anchor type and diameter: HIT-RE 500 V3 + Rebar 16mm
Seismic/Filling set or any suitable annular gap filling solution
Effective embedment depth: hef,act = 200 mm (hef,limit = - mm)
Material: B500B
Evaluation Service Report: ETA 16/0143
Issued I Valid: 7/12/2017 | -
Proof: Engineering judgement SOFA BOND - based on ETAG BOND testing
Stand-off installation: eb = 0 mm (no stand-off); t = 3 mm
Anchor plate: lx x ly x t = 500 mm x 500 mm x 3 mm; (Recommended plate thickness: not calculated
Profile: no profile
Base material: cracked concrete, C35/45, fc,cube = 45.00 N/mm2; h = 300 mm, Temp. short/long: 30/40 °C
Installation: hammer drilled hole, Installation condition: Dry
Reinforcement: no reinforcement or reinforcement spacing >= 150 mm (any Ø) or >= 100 mm (Ø <= 10 mm)
with longitudinal edge reinforcement d >= 12

R
- The anchor calculation is based on a rigid baseplate assumption.

Geometry [mm] & Loading [kN, kNm]

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 2
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

2 Load case/Resulting anchor forces y


Load case: Design loads

Anchor reactions [kN] 1 2 3 4


Tension force: (+Tension, -Compression)
Anchor Tension force Shear force Shear force x Shear force y Tension
1 32.131 1.286 0.000 1.286
2 32.131 1.286 0.000 1.286
5 6
3 32.131 1.286 0.000 1.286
4 32.131 1.286 0.000 1.286
5 19.129 1.286 0.000 1.286 x
6 19.129 1.286 0.000 1.286
7 6.128 1.286 0.000 1.286 7 8
8 6.128 1.286 0.000 1.286
9 0.000 1.286 0.000 1.286
10 0.000 1.286 0.000 1.286
11 0.000 1.286 0.000 1.286
9 10
Compression 11 12
12 0.000 1.286 0.000 1.286

max. concrete compressive strain: 0.22 [‰]


max. concrete compressive stress: 6.74 [N/mm2]
resulting tension force in (x/y)=(0/172): 179.036 [kN]
resulting compression force in (x/y)=(0/-215): 175.866 [kN]

Anchor forces are calculated based on the assumption of a rigid baseplate.

3 Tension load (EOTA TR 029, Section 5.2.2)


Load [kN] Capacity [kN] Utilization bN [%] Status
Steel Strength* 32.131 79.286 41 OK
Combined pullout-concrete cone failure** 179.036 220.691 82 OK
Concrete Breakout Strength** 179.036 199.273 90 OK
Splitting failure** 179.036 202.713 89 OK
* anchor having the highest loading **anchor group (anchors in tension)

3.1 Steel Strength


NRk,s [kN] gM,s NRd,s [kN] NSd [kN]
111.000 1.400 79.286 32.131

3.2 Combined pullout-concrete cone failure


Ap,N [mm2] A0p,N [mm2] 2
t Rk,ucr,25 [N/mm ] scr,Np [mm] ccr,Np [mm] cmin [mm]
524,513 136,533 10.00 370 185 ∞
2 0
yc t Rk,cr [N/mm ] k y g,Np y g,Np
1.061 8.48 2.300 1.931 1.338
ec1,N [mm] y ec1,Np ec2,N [mm] y ec2,Np y s,Np y re,Np
0 1.000 60 0.755 1.000 1.000
N0Rk,p [kN] NRk,p [kN] gM,p NRd,p [kN] NSd [kN]
85.294 331.036 1.500 220.691 179.036

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 3
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

3.3 Concrete Breakout Strength


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm]
945,000 360,000 300 600
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N
0 1.000 60 0.834 1.000 1.000
k1 N0Rk,c [kN] gM,c NRd,c [kN] NSd [kN]
7.200 136.610 1.500 199.273 179.036

3.4 Splitting failure


Ac,N [mm2] A0c,N [mm2] ccr,sp [mm] scr,sp [mm] y h,sp
1,282,600 577,600 380 760 1.160
ec1,N [mm] y ec1,N ec2,N [mm] y ec2,N y s,N y re,N k1
0 1.000 60 0.864 1.000 1.000 7.200
N0Rk,c [kN] gM,sp NRd,sp [kN] NSd [kN]
136.610 1.500 202.713 179.036

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 4
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

4 Shear load (EOTA TR 029, Section 5.2.3)


Load [kN] Capacity [kN] Utilization bV [%] Status
Steel Strength (without lever arm)* 1.286 36.667 4 OK
Steel failure (with lever arm)* N/A N/A N/A N/A
Pryout Strength** 15.430 557.826 3 OK
Concrete edge failure in direction ** N/A N/A N/A N/A
* anchor having the highest loading **anchor group (relevant anchors)

4.1 Steel Strength (without lever arm)


VRk,s [kN] gM,s VRd,s [kN] VSd [kN]
55.000 1.500 36.667 1.286

4.2 Pryout Strength (Concrete Breakout Strength controls)


Ac,N [mm2] A0c,N [mm2] ccr,N [mm] scr,N [mm] k-factor
1,102,500 360,000 300 600 2.000
ec1,V [mm] y ec1,N ec2,V [mm] y ec2,N y s,N y re,N
0 1.000 0 1.000 1.000 1.000
N0Rk,c [kN] gM,c,p VRd,cp [kN] VSd [kN]
136.610 1.500 557.826 15.430

5 Combined tension and shear loads (EOTA TR 029, Section 5.2.4)

bN bV a Utilization bN,V [%] Status


0.898 0.035 1.000 78 OK
(bN + bV) / 1.2 ≤ 1.0

6 Displacements (highest loaded anchor)


Short term loading:
NSk = 23.800 [kN] dN = 0.284 [mm]
VSk = 0.952 [kN] dV = 0.038 [mm]
dNV = 0.287 [mm]
Long term loading:
NSk = 23.800 [kN] dN = 0.450 [mm]
VSk = 0.952 [kN] dV = 0.057 [mm]
dNV = 0.453 [mm]

Comments: Tension displacements are valid with half of the required installation torque moment for uncracked concrete! Shear displacements are
valid without friction between the concrete and the anchor plate! The gap due to the drilled hole and clearance hole tolerances are not included in
this calculation!

The acceptable anchor displacements depend on the fastened construction and must be defined by the designer!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 5
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

7 Warnings
• The anchor design methods in PROFIS Anchor require rigid anchor plates per current regulations (ETAG 001/Annex C, EOTA TR029, etc.). This
means load re-distribution on the anchors due to elastic deformations of the anchor plate are not considered - the anchor plate is assumed to be
sufficiently stiff, in order not to be deformed when subjected to the design loading. PROFIS Anchor calculates the minimum required anchor plate
thickness with FEM to limit the stress of the anchor plate based on the assumptions explained above. The proof if the rigid base plate assumption
is valid is not carried out by PROFIS Anchor. Input data and results must be checked for agreement with the existing conditions and for
plausibility! 
• Checking the transfer of loads into the base material is required in accordance with EOTA TR 029, Section 7!
• The design is only valid if the clearance hole in the fixture is not larger than the value given in Table 4.1 of EOTA TR029! For larger diameters of
the clearance hole see Chapter 1.1. of EOTA TR029!
• Your design has selected filled holes. Please ensure that there is a proper method to fill the annular gap between the fixture and HIT-RE 500 V3
+ Rebar 16mm, and contact Hilti in case of any questions.
• The accessory list in this report is for the information of the user only. In any case, the instructions for use provided with the product have to be
followed to ensure a proper installation.
• Characteristic bond resistances depend on short- and long-term temperatures.
• The design method SOFA assumes that no hole clearance between the anchors and the fixture is present. This can be achieved by filling the gap
with mortar of sufficient compressive strength (e.g. by using the HILTI Seismic/Filling set) or by other suitable means
• The compliance with current standards (e.g. EC3) is the responsibility of the user
• An SLS-check is not performed for SOFA and has to be provided by the user!

Fastening meets the design criteria!

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 6
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

8 Installation data
Anchor plate, steel: - Anchor type and diameter: HIT-RE 500 V3 + Rebar 16mm
Profile: no profile Installation torque: -
Hole diameter in the fixture: df = 16 mm Hole diameter in the base material: 20 mm
Plate thickness (input): 3 mm Hole depth in the base material: 200 mm
Recommended plate thickness: not calculated Minimum thickness of the base material: 240 mm
Drilling method: Hammer drilled
Cleaning: Compressed air cleaning of the drilled hole according to instructions for use is required

8.1 Recommended accessories

Drilling Cleaning Setting


• Suitable Rotary Hammer • Compressed air with required accessories • Dispenser including cassette and mixer
• Properly sized drill bit to blow from the bottom of the hole • For deep installations, a piston plug is
• Proper diameter wire brush necessary
• Seismic/Filling set
• Torque wrench
y

250 250

25
1 2 3 4

150

250

5 6
150

7 8
250
150

9 10 11 12
25

25 150 150 150 25

Coordinates Anchor [mm]


Anchor x y c-x c+x c-y c+y Anchor x y c-x c+x c-y c+y
1 -225 225 - - - - 7 -225 -75 - - - -
2 -75 225 - - - - 8 225 -75 - - - -
3 75 225 - - - - 9 -225 -225 - - - -
4 225 225 - - - - 10 -75 -225 - - - -
5 -225 75 - - - - 11 75 -225 - - - -
6 225 75 - - - - 12 225 -225 - - - -

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan
www.hilti-me.com Profis Anchor 2.8.0
Company: CSCEC Page: 7
Specifier: Project: R881-3C2 PROJECT fi
Address: Sub-Project I Pos. No.: Street lighting pole
Phone I Fax: | Date: 3/13/2019
E-Mail:

9 Remarks; Your Cooperation Duties


• Any and all information and data contained in the Software concern solely the use of Hilti products and are based on the principles, formulas and
security regulations in accordance with Hilti's technical directions and operating, mounting and assembly instructions, etc., that must be strictly
complied with by the user. All figures contained therein are average figures, and therefore use-specific tests are to be conducted prior to using
the relevant Hilti product. The results of the calculations carried out by means of the Software are based essentially on the data you put in.
Therefore, you bear the sole responsibility for the absence of errors, the completeness and the relevance of the data to be put in by you.
Moreover, you bear sole responsibility for having the results of the calculation checked and cleared by an expert, particularly with regard to
compliance with applicable norms and permits, prior to using them for your specific facility. The Software serves only as an aid to interpret norms
and permits without any guarantee as to the absence of errors, the correctness and the relevance of the results or suitability for a specific
application.
• You must take all necessary and reasonable steps to prevent or limit damage caused by the Software. In particular, you must arrange for the
regular backup of programs and data and, if applicable, carry out the updates of the Software offered by Hilti on a regular basis. If you do not use
the AutoUpdate function of the Software, you must ensure that you are using the current and thus up-to-date version of the Software in each case
by carrying out manual updates via the Hilti Website. Hilti will not be liable for consequences, such as the recovery of lost or damaged data or
programs, arising from a culpable breach of duty by you.

Input data and results must be checked for agreement with the existing conditions and for plausibility!
PROFIS Anchor ( c ) 2003-2009 Hilti AG, FL-9494 Schaan Hilti is a registered Trademark of Hilti AG, Schaan