Emax-Air Circuit Breakers: E3 3200A Fixed and Drawout
Emax-Air Circuit Breakers: E3 3200A Fixed and Drawout
Emax-Air Circuit Breakers: E3 3200A Fixed and Drawout
UL 1066 E3
Levels of performance N-A S-A H-A V-A X-A
Frame Size [A] 2000 800 800 800 800
[A] 2500 1200 1200 1200 1200
[A] 1600 1600 1600 1600
[A] 2000 2000 2000 2000
[A] 2500 2500 2500
[A] 3200 3200 3200
Capacity of neutral pole for four-pole circuit breakers [%Iu] 100 100 100 100 100
Rated short circuit current
240V [kA] 65 85 85 125 200
480V [kA] 50 65 85 125 200
600V [kA] 50 65 85 100 14
Rated short time current [kA] 50 65 65 85 14
Connections PR123 trip units. The re-engineered hardware architecture
allows flexible and precise configuration. With the new
Rear connections-Horizontal ( standard on fixed breaker) or Emax modular trip units one can simply add the appropriate
Vertical module to satisfy your requirement: a great advantage, both
in terms of flexibility and customization.
Trip Unit
Weight (Ibs) 3P Fixed 145
The latest generation electronics from ABB have made it
3P Drawout 229
possible to design the new, revolutionary PR121, PR122 and
• Shunt trip/closing coil (YO/YC) and second shunt trip • Lock in open position: key
(YO2)
• Lock in open position: padlocks
• Undervoltage release (YU)
• Circuit breaker lock in racked-in/test
• Time-delay device for undervoltage release (D) IEC only isolated/racked-out position
• External current sensors for neutral conductor outside • Accessories for lock in test isolated/racked-out
circuit breaker (neutral CTS) position
• Homopolar toroid for the main power supply • Padlock device for safety shutter
grounding conductor (star center of the transformer)
• Mechanical lock for compartment door
• Mechanical operation counter
• Anti-racking-out device when the springs are charged
Indication (FAIL SAFE)
• Gear motor for the automatic charging of the closing • Protection for opening and closing pushbuttons
springs (M)
• Mechanical interlock
• Bell alarm
• Bell alarm with remote reset command
• Electrical signaling of circuit breaker open/closed
(Aux contacts - MOC)
• Electrical signaling of circuit breaker racked-in/test
isolated/racked-out (position contacts -TOC)
• Contact signaling closing springs charged
• Contact signaling undervoltage release de-energized
(C. Aux YU)