Corrientes Del Segmento 1
Corrientes Del Segmento 1
Corrientes Del Segmento 1
M1
P= 1500 KW
V= 13.8 KV
FP= 0.90
X´´d= 25%
(1500𝐾𝑊)
𝑀1 = = 69.728293𝐴
(√3)(13.8𝐾𝑉)(0.90)
(1500𝐾𝑊)
𝑀1 = = 69.728293𝐴
(√3)(13.8𝐾𝑉)(0.90)
(75𝐾𝑉𝐴)
𝐶1 = = 3.137773𝐴
(√3)(13.8𝐾𝑉)
TR2
VL=69KV
69𝐾𝑉
VF = = 39.837168 𝐾𝑉
√3
(39.837168𝐾𝑉)
= 199.185840 Ω ≌ 200Ω
200 𝐴
Corrientes del segmento 2
M2
P= 15,000 KW
V= 4.16 KV
FP= 0.80
X´´d= 20%
M3
P= 10,000 KW
V= 4.16 KV
FP= 0.77
X´´d= 25%
(15,000𝐾𝑊)
𝑀2 = = 2602.239795 𝐴
(√3)(4.16𝐾𝑉)(0.80)
(10,000𝐾𝑊)
𝑀3 = = 1802.417174 𝐴
(√3)(4.16𝐾𝑉)(0.77)
TR3
VL=69KV
69𝐾𝑉
VF = = 39.837168 𝐾𝑉
√3
(39.837168𝐾𝑉)
= 265.58112 Ω ≌ 300Ω
150 𝐴
Corrientes del segmento 3
C-A= 120 MW
C-B= 90 MV
VB= 33 KV
FP= 0.55
TR4
VL=69KV
69𝐾𝑉
VF = = 39.837168 𝐾𝑉
√3
(39.837168𝐾𝑉)
= 159.348672 Ω ≌ 200Ω
250 𝐴
Corrientes del segmento 4
M4
P= 1,000 HP
V= 6.9 KV
FP= 0.90
X´´d= 15%
M5
P= 1,000 HP
V= 6.9 KV
FP= 0.90
X´´d= 15%
(1000𝐾𝑊)(0.746)
𝑀4 = = 69.356409 𝐴
(√3)(6.9𝐾𝑉)(0.90)
(1000𝐾𝑊)(0.746)
𝑀5 = = 69.356409 𝐴
(√3)(6.9𝐾𝑉)(0.90)
TR5
VL=69KV
69𝐾𝑉
VF = = 39.837168 𝐾𝑉
√3
(39.837168𝐾𝑉)
= 265.58112 Ω ≌ 300Ω
150 𝐴
Corrientes del segmento 5
C= 60 KVA
VB= 13.8 KV
FP= 0.80
(60 𝐾𝑉𝐴)
𝐶3 = = 2.510218 𝐴
(√3)(13.8𝐾𝑉)
TR6
VL=69KV
69𝐾𝑉
VF = = 39.837168 𝐾𝑉
√3
(39.837168𝐾𝑉)
= 199.18584 Ω ≌ 200Ω
200 𝐴
Sumatoria de cargas para la selección del transformador principal (tr1)
TR1
𝐼𝑇𝑅𝐹𝑇 = 3011.605589 𝐴
500 𝑀𝑉𝐴
𝑇𝑅1 = (0.08) = 0.10 𝑃. 𝑈
375 𝑀𝑉𝐴
500 𝑀𝑉𝐴
𝑇𝑅2 = (0.0585) = 6.5 𝑃. 𝑈
4.5 𝑀𝑉𝐴
500 𝑀𝑉𝐴
𝑇𝑅3 = (0.0585) = 0.73 𝑃. 𝑈
40 𝑀𝑉𝐴
500 𝑀𝑉𝐴
𝑇𝑅4 = (0.0491) = 0.13 𝑃. 𝑈
187.5 𝑀𝑉𝐴
500 𝑀𝑉𝐴
𝑇𝑅5 = (0.0585) = 14.625 𝑃. 𝑈
2 𝑀𝑉𝐴
500 𝑀𝑉𝐴
𝑇𝑅6 = (0.0585) = 390 𝑃. 𝑈
0.075 𝑀𝑉𝐴