Transpowr Acsr Bare Overhead Conductor To Can/Csa C61089: Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded
Transpowr Acsr Bare Overhead Conductor To Can/Csa C61089: Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded
Transpowr Acsr Bare Overhead Conductor To Can/Csa C61089: Aluminum Conductor Steel-Reinforced Concentric-Lay-Stranded
Overhead Conductors
12/12 73
Overhead Conductors Electric Utility
74
Electric Utility Overhead Conductors
Swan 4 21.1 6x0.0834 1x0.0834 0.0382 0.0328 0.250 6.36 0.414 0.422 0.505 125 0.0080 0.1109 0.7148
Swanate 4 21.1 7x0.0772 1x0.1029 0.0411 0.0328 0.257 6.54 0.414 0.422 0.505 125 0.0085 0.1096 0.7104
Sparrow 2 33.6 6x0.1052 1x0.1052 0.0608 0.0522 0.316 8.01 0.260 0.265 0.318 165 0.0101 0.1056 0.6785
Sparate 2 33.6 7x0.0974 1x0.1299 0.0654 0.0522 0.325 8.24 0.260 0.265 0.318 165 0.0107 0.1043 0.6741
Robin 1 42.4 6x0.1181 1x0.1181 0.0767 0.0657 0.354 9.00 0.206 0.210 0.252 190 0.0113 0.1029 0.6603
Raven 1/0 53.5 6x0.1327 1x0.1327 0.0968 0.0830 0.398 10.1 0.163 0.167 0.200 220 0.0127 0.1003 0.6421
Quail 2/0 67.4 6x0.1489 1x0.1489 0.1219 0.1045 0.447 11.3 0.130 0.132 0.158 250 0.0143 0.0976 0.6240
Pigeon 3/0 85.0 6x0.1672 1x0.1672 0.1537 0.1317 0.502 12.7 0.103 0.105 0.126 285 0.0161 0.0950 0.6059
Penguin 4/0 107.2 6x0.1878 1x0.1878 0.1939 0.1662 0.563 14.3 0.0816 0.0833 0.100 325 0.0180 0.0923 0.5877
Owl 266.8 135.1876 6x0.2109 7x0.0703 0.2368 0.2096 0.633 16.1 0.0647 0.0661 0.0791 385 0.0202 0.0896 0.5695
Waxwing 266.8 135.2 18x0.1217 1x0.1217 0.2210 0.2094 0.609 15.5 0.0649 0.0664 0.0794 410 0.0197 0.0903 0.5756
Spoonbill 266.8 135.2 22x0.1101 7x0.0612 0.2300 0.2095 0.624 15.9 0.0650 0.0664 0.0795 410 0.0207 0.0891 0.5717
Scaup 266.8 135.2 24x0.1054 7x0.0703 0.2366 0.2094 0.633 16.1 0.0650 0.0664 0.0795 415 0.0212 0.0886 0.5695
Partridge 266.8 135.2 26x0.1013 7x0.0788 0.2437 0.2095 0.642 16.3 0.0651 0.0665 0.0796 415 0.0217 0.0880 0.5673
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
75
Overhead Conductors Electric Utility
76
Electric Utility Overhead Conductors
Phoebe 300.0 152.0 18x0.1291 1x0.1291 0.2487 0.2356 0.646 16.4 0.0577 0.0591 0.0707 440 0.0209 0.0889 0.5664
Piper 300.0 152.0 30x0.1000 7x0.1000 0.2906 0.2356 0.700 17.8 0.0579 0.0591 0.0708 450 0.0241 0.0856 0.5537
Ostrich 300.0 152.0 26x0.1074 7x0.0835 0.2739 0.2355 0.680 17.3 0.0579 0.0592 0.0708 445 0.0230 0.0867 0.5582
Merlin 336.4 170.5 18x0.1367 1x0.1367 0.2789 0.2642 0.684 17.4 0.0515 0.0527 0.0631 475 0.0221 0.0876 0.5574
Woodcock 336.4 170.5 22x0.1237 7x0.0687 0.2903 0.2644 0.701 17.8 0.0516 0.0527 0.0631 475 0.0232 0.0865 0.5535
Widgeon 336.4 170.5 24x0.1184 7x0.0789 0.2985 0.2642 0.710 18.0 0.0516 0.0527 0.0631 475 0.0238 0.0859 0.5514
Linnet 336.4 170.5 26x0.1137 7x0.0884 0.3072 0.2643 0.720 18.3 0.0516 0.0528 0.0632 480 0.0244 0.0854 0.5492
Oriole 336.4 170.5 30x0.1059 7x0.1059 0.3259 0.2642 0.741 18.8 0.0516 0.0528 0.0632 480 0.0255 0.0843 0.5447
Chickadee 397.5 201.4 18x0.1486 1x0.1486 0.3295 0.3122 0.743 18.9 0.0436 0.0447 0.0534 525 0.0240 0.0857 0.5443
Stork 397.5 201.4 22x0.1344 7x0.0747 0.3428 0.3121 0.762 19.3 0.0436 0.0447 0.0535 530 0.0252 0.0846 0.5404
Brant 397.5 201.4 24x0.1287 7x0.0858 0.3527 0.3122 0.772 19.6 0.0436 0.0447 0.0534 530 0.0259 0.0840 0.5383
Ibis 397.5 201.4 26x0.1236 7x0.0961 0.3630 0.3123 0.783 19.9 0.0437 0.0447 0.0535 530 0.0265 0.0835 0.5361
Lark 397.5 201.4 30x0.1151 7x0.1151 0.3850 0.3121 0.806 20.5 0.0437 0.0447 0.0535 535 0.0277 0.0824 0.5316
Pelican 477.0 241.7 18x0.1628 1x0.1628 0.3955 0.3747 0.814 20.7 0.0363 0.0373 0.0446 590 0.0263 0.0836 0.5301
Toucan 477.0 241.7 22x0.1472 7x0.0818 0.4112 0.3744 0.834 21.2 0.0364 0.0373 0.0446 590 0.0276 0.0825 0.5262
Flicker 477.0 241.7 24x0.1410 7x0.0940 0.4233 0.3747 0.846 21.5 0.0364 0.0373 0.0446 595 0.0283 0.0819 0.5240
Hawk 477.0 241.7 26x0.1354 7x0.1053 0.4357 0.3747 0.858 21.8 0.0364 0.0373 0.0446 595 0.0290 0.0814 0.5218
Hen 477.0 241.7 30x0.1261 7x0.1261 0.4621 0.3747 0.883 22.4 0.0364 0.0373 0.0446 600 0.0304 0.0803 0.5174
Heron 500.0 253.4 30x0.1291 7x0.1291 0.4843 0.3927 0.904 23.0 0.0347 0.0356 0.0425 620 0.0311 0.0797 0.5137
Osprey 556.5 282.0 18x0.1758 1x0.1758 0.4612 0.4369 0.879 22.3 0.0311 0.0320 0.0383 645 0.0284 0.0818 0.5180
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
77
Overhead Conductors Electric Utility
78
Electric Utility Overhead Conductors
Parakeet 556.5 282.0 24x0.1523 7x0.1015 0.4939 0.4372 0.914 23.2 0.0312 0.0320 0.0383 655 0.0306 0.0801 0.5120
Dove 556.5 282.0 26x0.1463 7x0.1138 0.5083 0.4371 0.927 23.5 0.0312 0.0320 0.0383 655 0.0313 0.0796 0.5098
Eagle 556.5 282.0 30x0.1362 7x0.1362 0.5391 0.4371 0.953 24.2 0.0312 0.0320 0.0383 660 0.0328 0.0785 0.5053
-none- 605.0 306.6 22x0.1658 7x0.0921 0.5216 0.4750 0.940 23.9 0.0287 0.0295 0.0352 685 0.0311 0.0797 0.5076
Peacock 605.0 306.6 24x0.1588 7x0.1059 0.5370 0.4753 0.953 24.2 0.0287 0.0295 0.0352 690 0.0319 0.0792 0.5054
Squab 605.0 306.6 26x0.1525 7x0.1186 0.5522 0.4749 0.966 24.5 0.0287 0.0295 0.0352 690 0.0327 0.0786 0.5032
Wood Duck 605.0 306.6 30x0.1420 7x0.1420 0.5860 0.4751 0.994 25.2 0.0287 0.0294 0.0352 695 0.0342 0.0776 0.4987
Duck 605.0 306.6 54x0.1058 7x0.1058 0.5366 0.4750 0.953 24.2 0.0288 0.0296 0.0353 690 0.0321 0.0790 0.5054
Kingbird 636.0 322.3 18x0.1880 1x0.1880 0.5274 0.4997 0.940 23.9 0.0272 0.0281 0.0335 705 0.0304 0.0803 0.5075
Goldfinch 636.0 322.3 22x0.1700 7x0.0944 0.5483 0.4994 0.963 24.5 0.0273 0.0281 0.0335 710 0.0319 0.0792 0.5036
Rook 636.0 322.3 24x0.1628 7x0.1085 0.5643 0.4996 0.977 24.8 0.0273 0.0281 0.0335 710 0.0327 0.0786 0.5015
Grosbeak 636.0 322.3 26x0.1564 7x0.1216 0.5808 0.4995 0.990 25.2 0.0273 0.0281 0.0335 715 0.0335 0.0781 0.4993
Scoter 636.0 322.3 30x0.1456 7x0.1456 0.6160 0.4995 1.019 25.9 0.0273 0.0280 0.0335 720 0.0351 0.0770 0.4948
Egret 636.0 322.3 30x0.1456 19x0.0874 0.6135 0.4995 1.019 25.9 0.0273 0.0280 0.0335 715 0.0351 0.0770 0.4948
Goose 636.0 322.3 54x0.1085 7x0.1085 0.5640 0.4993 0.977 24.8 0.0274 0.0281 0.0336 710 0.0330 0.0784 0.5015
Flamingo 666.6 337.8 24x0.1667 7x0.1111 0.5917 0.5238 1.000 25.4 0.0260 0.0268 0.0320 730 0.0335 0.0781 0.4978
Gannet 666.6 337.8 26x0.1601 7x0.1245 0.6086 0.5234 1.014 25.8 0.0261 0.0268 0.0320 735 0.0343 0.0775 0.4956
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
79
Overhead Conductors Electric Utility
80
Electric Utility Overhead Conductors
Stilt 715.5 362.5 24x0.1727 7x0.1151 0.6350 0.5622 1.036 26.3 0.0242 0.0250 0.0298 765 0.0347 0.0773 0.4923
Starling 715.5 362.5 26x0.1659 7x0.1290 0.6535 0.5620 1.051 26.7 0.0243 0.0250 0.0299 765 0.0355 0.0767 0.4901
Redwing 715.5 362.5 30x0.1544 19x0.0926 0.6897 0.5617 1.081 27.5 0.0236 0.0243 0.0290 770 0.0369 0.0758 0.4856
-none- 715.5 362.5 42x0.1305 7x0.0725 0.5907 0.5618 1.001 25.4 0.0243 0.0251 0.0299 755 0.0329 0.0785 0.4977
Crow 715.5 362.5 54x0.1151 7x0.1151 0.6347 0.5619 1.036 26.3 0.0243 0.0251 0.0299 765 0.0350 0.0771 0.4923
Macaw 795.0 402.8 42x0.1376 7x0.0764 0.6566 0.6245 1.055 26.8 0.0218 0.0227 0.0270 810 0.0346 0.0773 0.4895
Tern 795.0 402.8 45x0.1329 7x0.0886 0.6674 0.6243 1.063 27.0 0.0219 0.0227 0.0270 810 0.0352 0.0769 0.4882
Puffin 795.0 402.8 22x0.1901 7x0.1056 0.6857 0.6244 1.077 27.4 0.0218 0.0226 0.0269 815 0.0357 0.0766 0.4862
Cuckoo 795.0 402.8 24x0.1820 7x0.1213 0.7053 0.6244 1.092 27.7 0.0218 0.0225 0.0269 815 0.0366 0.0760 0.4840
Condor 795.0 402.8 54x0.1213 7x0.1213 0.7050 0.6241 1.092 27.7 0.0219 0.0226 0.0270 815 0.0368 0.0759 0.4840
Drake 795.0 402.8 26x0.1749 7x0.1360 0.7263 0.6247 1.107 28.1 0.0218 0.0225 0.0269 820 0.0375 0.0755 0.4818
Mallard 795.0 402.8 30x0.1628 19x0.0977 0.7669 0.6245 1.140 28.9 0.0218 0.0225 0.0269 825 0.0392 0.0744 0.4773
-none- 874.5 443.1 42x0.1443 7x0.0802 0.7222 0.6869 1.106 28.1 0.0199 0.0207 0.0246 855 0.0363 0.0762 0.4820
Crane 874.5 443.1 54x0.1273 7x0.1273 0.7760 0.6870 1.145 29.1 0.0199 0.0206 0.0246 865 0.0386 0.0748 0.4766
-none- 900.0 456.0 42x0.1464 7x0.0813 0.7433 0.7070 1.122 28.5 0.0193 0.0201 0.0239 870 0.0369 0.0758 0.4797
Ruddy 900.0 456.0 45x0.1414 7x0.0943 0.7556 0.7067 1.131 28.7 0.0193 0.0201 0.0239 875 0.0374 0.0755 0.4785
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
81
Overhead Conductors Electric Utility
82
Electric Utility Overhead Conductors
Phoenix 954.0 483.4 42x0.1507 7x0.0837 0.7877 0.7492 1.155 29.3 0.0182 0.0190 0.0226 905 0.0380 0.0752 0.4752
Rail 954.0 483.4 45x0.1456 7x0.0971 0.8011 0.7493 1.165 29.6 0.0182 0.0190 0.0226 905 0.0385 0.0748 0.4739
Towhee 954.0 483.4 48x0.1410 7x0.1097 0.8156 0.7495 1.175 29.8 0.0182 0.0190 0.0226 910 0.0391 0.0745 0.4726
Redbird 954.0 483.4 24x0.1994 7x0.1329 0.8466 0.7495 1.196 30.4 0.0182 0.0189 0.0225 915 0.0400 0.0739 0.4697
Cardinal 954.0 483.4 54x0.1329 7x0.1329 0.8462 0.7491 1.196 30.4 0.0182 0.0189 0.0226 915 0.0404 0.0738 0.4697
Snowbird 1033.5 523.7 42x0.1569 7x0.0872 0.8535 0.8117 1.203 30.5 0.0168 0.0176 0.0209 950 0.0395 0.0743 0.4689
Ortolan 1033.5 523.7 45x0.1515 7x0.1010 0.8677 0.8116 1.212 30.8 0.0168 0.0176 0.0209 950 0.0401 0.0739 0.4676
Whooper 1033.5 523.7 48x0.1467 7x0.1141 0.8830 0.8114 1.223 31.1 0.0168 0.0176 0.0209 955 0.0407 0.0736 0.4663
Curlew 1033.5 523.7 54x0.1383 7x0.1383 0.9167 0.8116 1.245 31.6 0.0168 0.0175 0.0209 960 0.0420 0.0728 0.4635
Beaumont 1113.0 564.0 42x0.1628 7x0.0904 0.9192 0.8742 1.248 31.7 0.0156 0.0164 0.0195 990 0.0410 0.0734 0.4631
(Avocet)
Bullfinch 1113.0 564.0 48x0.1523 7x0.1185 0.9516 0.8744 1.269 32.2 0.0156 0.0164 0.0195 1000 0.0423 0.0727 0.4605
Finch 1113.0 564.0 54x0.1436 19x0.0862 0.9851 0.8742 1.292 32.8 0.0156 0.0163 0.0194 1005 0.0436 0.0720 0.4577
Oxbird 1192.5 604.2 42x0.1685 7x0.0936 0.9847 0.9366 1.292 32.8 0.0146 0.0154 0.0183 1035 0.0424 0.0726 0.4577
Bunting 1192.5 604.2 45x0.1628 7x0.1085 1.0014 0.9367 1.302 33.1 0.0146 0.0154 0.0182 1035 0.0431 0.0723 0.4564
Cormorant 1192.5 604.2 48x0.1576 7x0.1226 1.0190 0.9364 1.313 33.4 0.0146 0.0154 0.0182 1040 0.0437 0.0719 0.4551
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
83
Overhead Conductors Electric Utility
84
Electric Utility Overhead Conductors
Scissortail 1272.0 644.5 42x0.1740 7x0.0967 1.0502 0.9988 1.334 33.9 0.0137 0.0145 0.0172 1075 0.0438 0.0719 0.4526
Bittern 1272.0 644.5 45x0.1681 7x0.1121 1.0679 0.9988 1.345 34.2 0.0137 0.0145 0.0172 1080 0.0445 0.0715 0.4514
Diver 1272.0 644.5 48x0.1628 7x0.1266 1.0873 0.9991 1.357 34.5 0.0137 0.0145 0.0171 1080 0.0452 0.0712 0.4500
Pheasant 1272.0 644.5 54x0.1535 19x0.0921 1.1258 0.9993 1.381 35.1 0.0137 0.0144 0.0171 1090 0.0466 0.0705 0.4472
Ringdove 1351.5 684.8 42x0.1794 7x0.0997 1.1163 1.0616 1.375 34.9 0.0129 0.0137 0.0162 1115 0.0452 0.0712 0.4479
Dipper 1351.5 684.8 45x0.1733 7x0.1155 1.1348 1.0614 1.386 35.2 0.0129 0.0137 0.0162 1120 0.0459 0.0708 0.4466
-none- 1351.5 684.8 48x0.1678 7x0.1305 1.1551 1.0615 1.398 35.5 0.0129 0.0137 0.0162 1120 0.0466 0.0705 0.4453
Martin 1351.5 684.8 54x0.1582 19x0.0949 1.1958 1.0614 1.424 36.2 0.0129 0.0136 0.0161 1130 0.0480 0.0698 0.4425
Popinjay 1431.0 725.1 42x0.1846 7x0.1026 1.1820 1.1241 1.415 35.9 0.0121 0.0131 0.0154 1155 0.0465 0.0705 0.4434
Bobolink 1431.0 725.1 45x0.1783 7x0.1189 1.2014 1.1237 1.427 36.2 0.0121 0.0130 0.0154 1155 0.0472 0.0702 0.4422
Wagtail 1431.0 725.1 48x0.1727 7x0.1343 1.2235 1.1243 1.439 36.5 0.0121 0.0130 0.0153 1160 0.0479 0.0698 0.4408
Plover 1431.0 725.1 54x0.1628 19x0.0977 1.2665 1.1241 1.465 37.2 0.0122 0.0129 0.0153 1170 0.0494 0.0691 0.4380
-none- 1510.5 765.4 42x0.1896 7x0.1053 1.2472 1.1862 1.454 36.9 0.0115 0.0124 0.0146 1190 0.0478 0.0699 0.4392
Nuthatch 1510.5 765.4 45x0.1832 7x0.1221 1.2682 1.1862 1.466 37.2 0.0115 0.0124 0.0146 1195 0.0485 0.0696 0.4379
Parrot 1510.5 765.4 54x0.1672 19x0.1003 1.3362 1.1861 1.505 38.2 0.0115 0.0123 0.0145 1210 0.0508 0.0685 0.4338
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.
85
Overhead Conductors Electric Utility
86
Electric Utility Overhead Conductors
Lapwing 1590.0 805.7 45x0.1880 7x0.1253 1.3354 1.2491 1.504 38.2 0.0109 0.0118 0.0139 1230 0.0497 0.0690 0.4339
Hornbill 1590.0 805.7 48x0.1820 7x0.1416 1.3590 1.2488 1.517 38.5 0.0109 0.0118 0.0139 1235 0.0505 0.0686 0.4326
Falcon 1590.0 805.7 54x0.1716 19x0.1030 1.4072 1.2489 1.544 39.2 0.0109 0.0117 0.0138 1245 0.0521 0.0679 0.4297
-none- 1590.0 805.7 72x0.1486 7x0.0991 1.3028 1.2488 1.486 37.7 0.0109 0.0119 0.0140 1225 0.0489 0.0694 0.4358
Chukar 1780.0 901.9 84x0.1456 19x0.0874 1.5118 1.3978 1.601 40.7 0.00978 0.0107 0.0126 1320 0.0534 0.0673 0.4241
Seahawk 1869.0 947.0 68x0.1658 7x0.0921 1.5147 1.4681 1.603 40.7 0.00931 0.0104 0.0122 1340 0.0524 0.0678 0.4239
Mockingbird 2034.5 1030.9 72x0.1681 7x0.1121 1.6671 1.5980 1.681 42.7 0.00855 0.00967 0.0113 1410 0.0553 0.0665 0.4165
Roadrunner 2057.5 1042.5 76x0.1645 19x0.0768 1.7035 1.6155 1.700 43.2 0.00845 0.00953 0.0111 1425 0.0562 0.0662 0.4147
Bluebird 2156.0 1092.4 84x0.1602 19x0.0961 1.8309 1.6931 1.762 44.8 0.00807 0.00909 0.0106 1470 0.0588 0.0651 0.4091
Kiwi 2167.0 1098.0 72x0.1735 7x0.1157 1.7758 1.7022 1.735 44.1 0.00803 0.00918 0.0107 1460 0.0570 0.0658 0.4115
Thrasher 2312.0 1171.5 76x0.1744 19x0.0814 1.9145 1.8156 1.802 45.8 0.00752 0.00868 0.0101 1520 0.0595 0.0648 0.4055
Joree 2515.0 1274.4 76x0.1819 19x0.0849 2.0827 1.9751 1.880 47.7 0.00692 0.00813 0.00937 1590 0.0621 0.0639 0.3989
(4) Code words shown denote ACSR with regular-strength Class A galvanized steel core (S1A). See the Options section to find the appropriate code word modifier designation for
alternative design options.
(5) Based on a conductivity of 61.0% IACS at 20˚C for aluminum and ignores the effects of the steel core. To convert to ohms/mile, multiply by 5.28. To convert to ohms/km, multiply by
3.281.
(6) Based on a conductor temperature of 75˚C at 60 Hz and the following conditions: 32˚C ambient temperature, 1.98 ft/sec (0.6 m/s) crosswind (90˚ to conductor), 0.5 coefficient of
emissivity, 0.5 coefficient of absorbtivity, 42˚ northern latitude, sea level elevation, 90˚ azimuth of line (East-West), clear atmosphere, and a date and time of noon on July 1 (resulting
in 95.0 W/ft² of solar and sky radiated heat). Actual ampacity will differ based on local conditions. For specific ampacities, please contact your General Cable sales representative.
(7) Values for inductive reactance and capacitive reactance are expressed in terms of a 1 ft radius (30.48 cm). To convert the Geometric Mean Radius (GMR) to cm, divide the value by
0.03821. To convert inductive reactance to ohm/km, multiply the value by 3.281. To convert capacitive reactance to ohm/km, divide the value by 3.281.