Professional Documents
Culture Documents
2012 ELECTRA 262 WG D1.33 High-Voltage On-Site Testing With Partial Discharge Measurement
2012 ELECTRA 262 WG D1.33 High-Voltage On-Site Testing With Partial Discharge Measurement
TECHNICAL BROCHURE
WG
High-Voltage On-Site Testing with D1.33
Partial Discharge Measurement
Members
Groupe d’Action 05
R. Pietsch, Convenor (DE): 2007-2010,
W. Hauschild, Convenor (DE): 2004-2007,
J. Blackett (AU), R. Bodega (NL), A. Claudi (DE), M. Gamlin (CH),
B. Finlay (AU), E. Gockenbach (DE), E. Gulski (NL), R.A. Jongen (CH),
Th. Leibfried (DE), E. Lemke (DE), S. Meijer (NL), P. Mohaupt (AT),
M. Muhr (AT), F. Petzold (DE), E. Pultrum (NL), G. Rizzi (IT),
Th. Strehl (DE), C. Sumereder (AT),
S. Tenbohlen (DE), P. Werle (DE)
During the life cycle of high voltage (HV) apparatus • the expectations from testing depend on the
or systems (Fig. 1), many tests and measurements are test procedure as selected for the particular
performed to characterize the insulation condition. component;
The results of these tests and measurements should • some degradation and breakdown risks may be
be compiled in a “life data record”, which supplies related to the level and the duration of withstand
information on trends of diagnostic indicator values. voltage stresses as applied during on-site testing;
The HV on-site test with PD measurement has an • voltage withstand testing at the selected voltage
intermediate position between routine tests and level gives go/no-go information for this test
in-service monitoring measurements (on-line or voltage level and requires confirmation by
off-line): methods such as PD measurement of possible
field strength effects on the insulation system.
In addition to type and routine testing, HV on-site
testing is an important part of quality assurance. The different aims of HV testing on the one hand
On-site tests are applied: and insulation diagnostics/monitoring on the other
• as a part of commissioning of equipment on hand may have caused the sometimes quite different
site to demonstrate that the transport from philosophies (Table 1). But the common physical
manufacture to site and erection on-site have background of the measured phenomena is the
not caused any critical defects, which lower the behaviour of dielectrics in the electric field. Therefore,
dielectric withstand voltage of the insulation the tests and measurements in the factory and on-site
below coordination withstand level Ucw ; (off-line or in-service) should be harmonized. This
• after repair on site to demonstrate that the offers an improvement of on-site test procedures
equipment has been successfully repaired; supported by PD measurement.
• for diagnostic purposes in the framework of
the asset management program by providing PD measurements play an important role in both
reference values of diagnostic indicators quality assurance tests and monitoring for condition
(e.g. partial discharge values and dielectric assessment. In contrast to diagnostics of integral
parameters) for later trending of test results. On dielectric parameters, such as tan δ, εr and dielectric
site tests are normally applied after a warning response, which are characteristics of the whole dielectric
is received from the condition monitoring volume, partial discharges are related to local insulation
program. defects. Such “weak-points”, are a part of the insulation
system, where under certain stress circumstances of e.g.
Furthermore it has to be considered that depending mechanical, chemical, thermal or electrical character a
on the particular condition of the HV component: severe PD activity prior breakdown may occur.
In case of new insulation, critical defects are the result period – the previous mentioned “weak point”. In other
of assembling failures which can be found by a routine words, partial discharges indicate the non-reversible
test consisting of the HV withstand test combined destruction of solid or mixed insulation. This is
with PD measurement. In case of the insulation of HV important for both the detection of production faults
equipment in service (which has been tested successfully by means of quality assurance test and the recognition
and which operates for years) a critical defect might be of weak points/defects caused by aging during service
caused by high electrical, thermal or mechanical stresses by means of diagnostic tests. Consequently, all HV
or by the “aging” of the insulation itself. This means the withstand tests, also if performed on site, should be
partial discharges are symptoms and sometimes also combined with PD measurement.
the results of this “integral” process in the volume of
the insulation, which causes – over a more or less long During the HV dielectric withstand test, the
Figure 2: Figure 3:
Life time characteristic of a solid insulation Test cycle for withstand test with PD measurement
Abbreviations:
W - withstand voltage test (e.g. 60 s, AC) ACRF - frequency-tuned resonant circuit for AC voltage generation
PD - voltage test with PD measurement MV - medium voltage
DM - voltage test with dielectric measurement (mainly tan δ), HV - high-voltage
no withstand test
ACTC - transformer circuit for AC voltage generation 1) applied in the past and no longer recommended
ACRL - inductance-tuned resonant circuit for AC voltage generation 2) mainly for PD diagnostics
might be followed by a diagnostic off-line test. This test for in-service insulation is not currently available.
should apply the same procedure of withstand testing
and PD measurement as described above. The PD Furthermore, it is important to coordinate the
values of that test shall be compared with the reference quality assurance tests (routine tests in factory,
values (“fingerprints”) of the initial on-site test. commissioning tests on-site, and tests after repair) and
the diagnostic tests (off-line or on-line). The results of
There are many different types of HV apparatus and measurements of partial discharges, dissipation factor
systems. To be able to test them all requires a wide variety and other quantities of quality tests are used as the
of well adapted mobile HV test facilities including references (“fingerprints”) for later diagnostic tests
PD measuring equipment. Fig. 4 shows examples of and measurements. Records of repeated measurements
a selection of the HV test facilities outlining the type may be used to show trends (e.g. PD magnitudes,
of test object, the purpose of the on-site test, methods pulse rate/s, etc.) which present the most important
of handling and the cost requirements. A main aspect information for condition assessment. All this enables
should be that the test voltage should represent stresses the establishment of the “life cycle record” (Fig. 1) for
in service. Related aspects are given in chapters 4 and 5. important HV equipment as the reference for condition
based maintenance (CBM).
Clear guidelines for the requirements of the test
voltages to be applied are given in IEC 60060-1 and The brochure is organized in six chapters. In chapter
60060-2 for routine testing and in IEC 60060-3 for 2, titled “High Voltage Sources and Accessories for
on-site testing. For installations which have been in On-Site Applications” the general requirements for
service, lower voltages and/or shorter durations may on-site test voltages as published by CIGRE WG 33.03/
be used. These test values should be fixed, taking into TF 04 and published in ELECTRA No. 195 (2000) are
account the age, environment, history of breakdowns, up-dated with the state of the art of test voltages, used
and the purpose of carrying out this test, as there is not a for PD measurements (continuous alternating voltage
general principle for the value of the on-site test voltage (AC); damped alternating voltage (DAC), very-low
levels for all type of HV apparatus. The test voltage frequency voltage (VLF)). A survey on the application
levels required for insulation coordination are only of these test voltages for various HV apparatus is given
related to new insulation, and any similar coordination in Table 2.
a b
c d
(a) 400 kV GIS by ACRF (frequency tuned resonant circuit) test system of modular reactors via bushing
(b) 400 kV GIS by ACRF test system with directly flanged reactor
(c) 150 kV HV cable system by DAC test system
(d) 400 kV/433 MVA power transformer by static frequency converter
BROCHURE N° 502
Copie papier / Hardcopy
(en anglais seulement)
(in English only)
Contact
Fax +33 (1) 53 89 12 99
e-mail : publication@cigre.org
ou téléchargerà http://www.e.cigre.org
or download at http://www.e.cigre.org
(Membres uniquement /Members only)