Professional Documents
Culture Documents
Minimization of Reactive Power Losses in Power Systems Through Facts Controller
Minimization of Reactive Power Losses in Power Systems Through Facts Controller
Minimization of Reactive Power Losses in Power Systems Through Facts Controller
Abstract--In this paper, a sensitivity-based method has been efficient control of active and reactive power flows in the
proposed for optimal placement of various types of FACTS transmission networks. High cost of these FACTS controllers
controllers. An Optimal Reactive Power Dispatch problem has requires their optimal placement in the system. The optimal
been formulated and solved using computer programming to placement of these controllers minimizes the reactive power
determine the optimal placement of FACTS controller on IEEE-
losses.
30 bus system. FACTS – Flexible AC transmission systems, SVC
– static VAR compensator, TCPAR – thyristor controlled phase
angle regulator, TCSC – thyristor controlled series capacitor. . 2. OPTIMAL PLACEMENT OF FACTS CONTROLLERS
Index Terms – FACTS, SVC, TCPAR & TCSC In this study, the placement of FACTS controllers
have been considered from the static point of view to reduce
the total system reactive power loss . A method based on the
1. INTRODUCTION
sensitivity approach, as described below, has been suggested
for the placement of FACTS controllers.
With ever - increasing interconnections and stressed
operating conditions, the secure and stable operation of
2.1 Loss sensitivity indices
power systems has become a challenging task. Due to
economical and environmental reasons, the expansion of
The proposed method utilizes the sensitivity of total
generation and transmission facilities has not been in
reactive power loss with respect to the control parameters of
proportion with the growth in the load. This has resulted in to
FACTS controllers for their optimal placement. The control
increased real and reactive power losses in the transmission
parameters for the three FACTS controllers include line net
network and voltage variation problem at the load bus occurs
series reactance (Xk ) for the TCSC placed in line-k, phase
in most of the power systems.
shift(φk ) for the TCPAR placed in line -k and reactive power
injection (Qi) for the SVC placed at bus -i. The loss sensitivity
Voltage at the load bus should be constant for
smooth operation of loads. Voltage variation is associated factors with respect to the parameters of these controllers can
with reactive power limitations of the power system. Hence it be defined as
is very necessary to control the reactive power of the system. ∂Q L
Achievable generator reactive capability (GRC) is generally ak =
much less than indicated by the manufacturer’s reactive ∂X k = Loss sensitivity with respect to control
capability curves, due to constraints imposed by plant
auxiliaries and the power system itself. Over-heating of rotor parameter Xk of TCSC placed in line -k (K=1, …… N l )
takes place due to over-excitation and armature heating takes ∂Q L
place due to large reactive power generation [1-3]. Hence the bk = = Loss sensitivity with respect to control
need is to minimize the reactive power losses in the power ∂φk
system. Reactive power losses in power systems can be parameter φk of TCPAR placed in line -k (K=1, ……
minimized with the help of optimal scheduling of reactive Nl )
power outputs of sources, transformer tap settings and other
compensating devices. ∂Q L
The Flexible AC Transmission Systems (FACTS) ck = = Loss sensitivity with respect
controllers are being popularly utilized in power system ∂Q i to control parameter Qi of SVC placed at
networks [4-5]. Mainly FACTS controllers include Thyristor bus -i (i = l, …….N)
Controlled Series Capacitor (TCSC), Thyristor Controlled These factors have been computed at a base case
Phase Angle Regulator (TCPAR) and Static VAR load flow solution, as given below. Consider a line-k
Compensator (SVC). These controllers enable fast and connected between bus-i and bus-j and having series
impedance Rk + jXk . where, Xk is the net reactance after
considering the reactance of a series compensator, if present
in the line. Let the complex voltages at the buses-i and j be
(S.K. Saini is with Deptt. of Electrical Engg. in Jaipur Engineering College,
Kukas, Jaipur) and C.P. Gupta is with Deptt. of Electrical Engg. in Malaviya Vi∠δ i and Vj∠δ j, and respectively φk = δ i-δ j be the phase
National Institute of Technology, Jaipur (formerly known as M.R.E.C., shift in the line-k including the effect of the phase shifter. The
Jaipur) loss sensitivity with respect to Xk and φk can be computed as
INDIAN INSTITUTE OF TECHNOLOGY, KHARAGPUR 721302, DECEMBER 27-29, 2002 731
For computing the loss sensitivity with respect to the 2.3 ORPD considering FACTS controllers
SVC control parameter Qi , a general loss formula has been
used, according to which After optimal placement of the FACTS controllers,
the conventional optimal reactive power dispatch (ORPD)
Q L = ∑ ∑ γ jk (PjPk + Q j Q k ) + ς(Q j Pk − Pj Q k )
N N
formulation has been modified to include TCSC, TCPAR and
j=1 k=1 SVC. In the present work, static models of these FACTS
Equation (3) controllers have been considered in which a TCSC is
represented as a static capacitor/reactor offering impedance
Where, γ,ς are the loss coefficients defined as: jXc, a TCPAR as a transformer having complex tap ratio
1:a∠α and a series admittance Yk and a SVC is represented
cos(δ j − δ k )
X jk as a reactive power source Qsvc with its limits as Qmin svc and
γ jk =
VjVk Qmax svc. Considering a general case when all the three types of
FACTS controllers are present in the system, the modified
sin (δ j − δ k )
X jk ORPD formulation is as follows:
ς jk =
Vj Vk Minimize,
Equation (4) N1 N1 + N 2 N1
L = 2∑ (Q LM + QML ) + ∑ QTCSCi + ∑Q
Q
TCPARi
Pj+ jQj = Complex power injected at bus-j j −1 i = N1 +1 i = N 1 + N 2 +1
Xjk = Imaginary part of the jkth element of [Zbus]
Equation (6)
If SVC is placed at bus-i, the sensitivity index with
respect to SVG control parameter using above loss formula Where, QL = Total reactive power loss.
can be expressed as: QTCSCi = Reactive power loss in line-i having TCSC
QTCPARi = Reactive power loss in line -i having TCPAR
∂Q L
= 2∑ (γ ij Q j + ςij Pj ); i = 1,....., N
N
2.2 Criteria for optimal placement Hence, the remaining ( N l - N1 - N2 ) lines are
consisting of TCPARS. The above minimization is subject to
Generally, FACTS controllers should be placed on reactive power balance (equality constraint)
the most sensitive bus or line. For instance SVC is employed
at the most sensitive bus from the voltage control viewpoint Nq N q + N SVC
whereas TCSC or TCPAR is placed in the most sensitive line
for the effective power flow control. With the loss ∑ QGi − QL − QD +
i =1
∑Q
i = N q +1
SVCi =0
sensitivities computed as discussed earlier, following criteria
Equation (7)
732 NATIONAL POWER SYSTEMS CONFERENCE, NPSC 2002
And a set of inequality constraints In the present work, each type of FACTS controllers
Q min
Gi ≤ Q Gi ≤ Q max
Gi ; i = 1,........N q has been considered only one at a time, in order to establish
their relative impact on voltage control An actual power
Vimin ≤ Vi ≤ Vimax ; i = 1,........N system may, however, have several such controllers in
operation which can be modeled using the above general
X cjmin ≤ X cj ≤ X cjmax ; j = N1 + 1,.......N1 + N 2 formulation.
Table 1
Priority list of Sensitivity Indices for IEEE 30-Bus System
Table 2
Comparison of Total Q-losses for IEEE 30-Bus System
Top five priority lines/buses based on the values of value of 0.50845 p.u. to -1.99885 p.u. and 0.34651 p.u.
these indices, computed at the base case operating point, are respectively.
as shown in Table 1. It is observed that top five priority lines
for the placement of TCSC and TCPAR are the same. 4. CONCLUSIONS
However, using the criteria for optimal placement of these This study reveals that rescheduling of reactive
controllers, the line having 4 th priority i.e. the line connecting power outputs of sources and transformers OLTC control
buses 27 and 11 (having a series reactance of 0.0379 p.u.) is drastically reduces the total reactive power losses of the
considered for the placement of TCSC and TCPAR. Whereas, system. Among three FACTS controllers considered, SVC is
the optimal placement of SVC was considered at bus 30, found to be the most effective in reducing the reactive power
having the first priority based on the value of index c i. loss in the IEEE 30-bus system,