33-11 KV Substation Equip Foundation

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

8ØT LINKS @ 200 C/C

8ØT @ 200 C/C


L
B

B
AS PER STRUCURE

A A L
SECTION B B
8ØT LINKS @ 200 C/C
B B

300
FGL FGL
METAL TOP METAL TOP
PLAN
NOTE:

1000 MIN.
FOR CENTRE TO CENTRE DISTANCE OF FOUNDATION BOLTS
REFER DRAWING OF SUPPORT STRUCTURE
8ØT @ 200 C/C
SCHEDULE OF FOUNDATIONS
PCC M7.5, 100THICK
150
EQUIPMENT/ SIZE OF REINFORCEMENT REMAKR TYP
STRUCTURE FOUNDATION
LxB VERTICAL LINKS
RUBBLE SOLING COMPACTED
33KV VCB 1200 x 600 8ØT @ 200 C/C 8ØT @ 200 C/C IN LAYERS NOT MORE THAN 300 THICK
33KV ISOLATOR IF BEARING STRATA IS MET AT DEPTH OF 1.0M
HARD STRATA THEN STONE SOLING NEED NOT BE PROVIDED.
11KV VCB+CT 1500 x 600 8ØT @ 200 C/C 8ØT @ 200 C/C SECTIONAL A A
NOTE:
IF SPECIFIED BEARING CAPACITY IS NOT AVAILBLE
11KV ISOLATOR 1000 x 600 8ØT @ 200 C/C 8ØT @ 200 C/C AT MINIMUM DEPTH THEN FOUNDATION TO BE PLACED
AT DEPTH WHERE SPECIFIED BEARING CAPACITY IS MET WITH.
11KV CT/ PT/LA/PI 400 x 400 -- --
33KV CT/ PT/LA/PI MAHARASHTRA STATE ELECTRICITY DISTRIBUTION COMPANY LTD.
BARAMATI ZONE.
11KV CR PANEL 650 x 450 8ØT @ 200 C/C 8ØT @ 200 C/C
CONSULTANT: A. P. JOG & ASSOCIATES, PUNE
11KV GANTRY 1200 x 600 -- -- DEPTH 1.50M
( H TYPE ) BELOW FGL
PROJECT:
Infra Plan/ Part II/Ph. A, T-014
11KV TAKEOFF 600 x 600 -- --
LOA. NO. CE(INFRA)/MUMBAI/EE-IV/INFRA PARTII/PH-A/J-14/LOC-C/25913 DT 17.9.13
NOTES:
1 USE CONCRETE OF GRADE M20 FOR RCC MEMBERS CONTRACTOR: BHARAT ELECTRICAL CONTRACTOR & MANUFACTURES (P) LTD.
2 USE STEEL OF GRADE FE250 FOR 6MM DIA AND J-78, M.I.D.C. KUPWAD, SANGLI-416436
GRADE FE415 DENOTED BY ØT FOR OTHER DIA.
3 CLEAR COVER TO MAIN REINFORCEMENT
FOOTING - 50MM COLUMN - 40MM TITLE:
DETAILS OF EQUIPMENT FOUNDATION FOR 33/11KV
BEAM - 25MM SLAB - 15MM SUBSTATION
4. LAP LENGTH FOR 60DIA.
5. BEARING CAPACITY 10T/SQM. OR MORE. SCALE SHEET DRG. NO. DATE: SHEET SIZE REVISION
1:100 1 OF 1 Becmpl/T-14/ Civil-10 20/05/2014 A3 0