FOOTING DESIGN (SQUARE FOOTING):

DEAD LOAD: 230 KN


LIVE LOAD: 30 KN
Qa: 60 Kpa
COL. DIM. A 0.400 m
COL. DIM. B 0.200 m
f'c: 20.700 MPa
fy: 278.000 MPa

EFFECTIVE DEPTH OF FOOTING:


BASED ON WIDE-BEAM SHEAR:
d test: 84.68 mm
BASED ON PUNCHING SHEAR:
EQN. TO BE INPUT: 78.027 X² 31610.814 X -4680000
USE HIGHER D: 200 mm INPUT ONLY THE POSITIVE SIGN
p min: 0.0050359712
p: 0.0027695875
p max: 0.0275728335
Note: p min < p < p max . If p min is larger than p, use p min.
USE p: 0.005035971
BAR DIA. 16 mm

SUMMARY:
LENGTH OF FOOTING: 2.200 m
WIDTH OF FOOTING: 2.200 m
DEPTH OF FOOTING: 299 mm PLS. ROUND UP
LONGITUDINAL BARS: 12 pcs.
TRANSVERSE BARS: 12 pcs.
BAR DIA. 16 mm
mm