Professional Documents
Culture Documents
Calculation - Foundation CCTV Pole
Calculation - Foundation CCTV Pole
PROJECT :
SUB-CONTRACTOR :
PT. GRAHA USAHA TEKNIK
2/15/2018
CHECKED BY DATE
20KV DISTRIBUTION LINE
SWL 2/15/2018
CCTV POLE FOUNDATION CALCULATION
APPROVED BY DATE
KSW 2/15/2018
DOCUMENT NUMBER REV. NO.
KSL1T-XX-XXX-XX-XXX 0
KALSEL-1 2x100MW Coal Fired Power Plant
1. GENERAL
2.1. Basic Design Parameters
Structure nam : CCTV Pole
Type of strcuture : Steel Pole
Type of Foundation : Shallow Foundation
2.2. Materials
Concrete for Foundation : Class B
fc' = 25 MPa
2. LOADING
2.1. Dead Load (D)
2.1.1. Selfweight
Foundation selfweight to be automatically generated by software
2.2.2. Other Dead Load
Weight of pole 100 kg = 100 kg
CCTV + Accessories 5 kg = 5 kg
total = 105 kg
= 1.0 kN
2.2. Live Load (L)
Live load to be considered in this analysis is human load (including tools)
assigned as Point Load at certain points.
Live load, PL = 150 kg
= 1.5 kN
Ss value S1 value
Calculation:
Site Class = D
Importance Factor, I = 1.25
SS = 0.232 g
S1 = 0.077 g
Fa = 1.6 (Table 11.4-1 ASCE 7)
Fv = 2.4 (Table 11.4-2 ASCE 7)
SMS = F a * SS = 0.3712 g
SM1 = F v * S1 = 0.1848 g
SDS = (2/3) * SMS = 0.25 g
SD1 = (2/3) * SM1 = 0.12 g
Sa = SDS = 0.25 g
R = 3 (Table 15.4-2 ASCE 7)
TITLE DESCRIPTION
PROJECT/JOB NO. GUT
PROJECT/JOB NAME GUT
CLIENT NAME GUT
SITE NAME Kalsel
DOCUMENT NO.
REFERENCE NO.
STRUCTURE NAME CCTV Pole
LOAD COMBINATION GROUP NAME
REV DATE DESCRIPTION PREP'D CHK'D APPR'D APPR'D
FOUNDATION LISTS
Group Name No. Description No. Description
F1 1 F1
CONTENTS
1. GENERAL
1.1 MATERIALS & UNIT WEIGHT
1.2 SUBSOIL CONDITION & SAFETY FACTORS
1.3 LOAD COMBINATION
2. DRAWING
2.1 LOCATION PLAN & DETAIL SKETCH
3. FOUNDATION DATA
3.1 FOOTING AND SECTION DATA
3.2 PIER DATA
3.3 LOAD CASE
3.4 LOAD COMBINATION
4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
4.2 CHECK OF OVERTURNING MOMENT
4.3 CHECK OF CONTACT PRESSURE
5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
5.2 REQUIRED REINFORCEMENT
5.3 ONE WAY SHEAR FORCE
5.4 TWO WAY SHEAR FORCE
1. GENERAL
- Soil Capacity
Items Value
Soil Name q_all
Footing List F1
2
Qa (Soil Bearing Capacity) 68.7 kN/m
Buoyancy Not Consider
WL (Water Label from the EL = 0) 0 mm
FD (Frost Depth from the EL = 0) 0 mm
Internal Friction Angle 0
Passive Soil Pressure Consider
2
Cu (Undrained cohesion) Clay , 35 kN/m
A01
NOTES
* OUTPUT UNIT : mm
01
GUT PROJECT
SQUAD CHECK
Y
PROCESS PIPING VESSELS STRUCT. ELEC. INST.
AS SHOWN GUT
OUTPUT UNIT : mm
REFERENCE DWGS
NO. DWG NO. DWG TITLE
800 CL FOOTING
400 TOP BOTTOM
TYP.
3
400
6-D13
6-D13
800
NOTES
* ANCHOR BOLT
1X4-M12 ANC. BOLTS (TYPE TYPE L)
* OUTPUT UNIT : mm
6-D13
6-D13
FOUNDATION PLAN FOOTING REINF. PLAN
75 PROJ.
GUT PROJECT
400
TOC EL. + 100 100 100
2 3
200 1.5
TYP.
100
@150
600
D10
500
200
F1
D10
75
100
3
SQUAD CHECK
300
8-D13
PEDESTAL
3
3. FOUNDATION DATA
3.1 FOOTING AND SECTION DATA
( mm ) Ft. Name F1
Ft. Type ISO
2
800 Area 0.640 m
Ft. Thickness 300.00 mm
3
Ft. Volume 0.192 m
Ft. Weight 4.608 kN
Soil Height 500.00 mm
400 400
3
Soil Volume 0.240 m
Soil Weight 3.360 kN
800
600
500
300
Section Data
( mm )
Ft.Name Direction Ft. Volume Soil Volume Pier Wt
3 3
F1 All Direct 0.192 m 0.240 m 2.304 kN
Unit( kN , kN-m )
Ft.Name Pr.Name Load Case Fx Fy Fz Mx My
1 0 0 -2.3 0 0
2 0 0 -34.8 0 0
3 0 0 -1.5 0 0
1 4 0.2 0 0 0 0.6
F1
5 0 0.2 0 -0.6 0
6 0.1 0 0 0 0.2
7 0 0.1 0 -0.2 0
Footing SW 0.000 0.000 -7.968 0.000 0.000
3.4.3 Load Combination in Footing Bottom Center (With Pier & Footing SW)
Load Combination of Elastic Condition
- C.G. of Load is coordinate from left bottom. Unit : mm Unit( kN , kN-m )
Ft.Name L.Comb. SFx SFy SFz SMx SMy C.G. of Loads
101 0.000 0.000 -46.572 0.000 0.000 400.0 , 400.0
102 0.120 0.000 -46.572 0.000 0.468 400.0 , 400.0
F1 103 0.000 0.120 -46.572 -0.468 0.000 400.0 , 400.0
104 0.075 0.000 -46.572 0.000 0.218 400.0 , 400.0
105 0.000 0.075 -46.572 -0.218 0.000 400.0 , 400.0
4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
mSFz + P.F mSFz + P.F
Formula : ( or ) > Fs -> OK (Uni-Axial)
SFx SFy
P.F = Passive Force (apply only in case checked passive force, mark by P ) Unit ( kN )
Ft.Name Dir. L.Comb. ( mSFz + P.F) / SFx or ( mSFz + H.P.F) / SFy Fs(i) Result
X 103 SFx = 0 , Then N/A P 1.8 OK
F1
Y 103 ( 0.35 46.57 + 0.5 ) / 0.12 = 140.03 P 1.8 OK
- Y-Direction (Uni-Axial) 2
Unit( kN , kN-m , kN/m )
Ft.Name L.Comb. q1 q2 ci cj Qmax Qa Cont.A.R Result
F1 103 67.284 78.253 0.000 0.800 78.3 91.6(gross) 100 % OK
5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
Footing design is in accordance with unltimate strength method at footing bottom.
Calculated total pier load as
SQ = SFz - Self Weight Factor (Soil Weight + Footing Weight)
Ft.Name : Footing Name , Sec.Name : Strip Name for Footing Reinforcement Design
Dir. : Direction , L.Comb. : Load Combination Index , Sl or Sw : Strip X or Y width
2
Unit(N/mm ,mm)
f(Flexure) f(Shear) f'c fy1 fy2 f_cl f_clt f_clb
0.85 0.8 25.00 240.00 400.00 3.0 3.0 3.0
Note : The reinforcement is calculated bases on the maximum moment under the foundation in each direction.
But, the 'ISO' , 'OCT' , 'HEX' , 'COMB' , 'TANK1' foundations are calaulated as face pier
Where,
Mu 0.85 fck 2Rn
Rn =
fbd
2 , f = 0.85 , r.req =
fy ( 1- 1-
0.85fck )
5.2.2 Check of Footing Reinforcement
Footing Name : F1 GroupType : Isolated
- X direction (All Width)
Sec.Nam L.Comb. Using Bar (mm) Loc. (m) Width b (m) d (mm) As (mm )
2
Sec.Nam L.Comb. Using Bar (mm) Loc. (m) Width b (m) d (mm) As (mm )
2
Unit : mm
800
800
1 Pw 400 mm f Vc 1070.600 kN
bc / as 1 / 40 Result OK