Download as pdf or txt
Download as pdf or txt
You are on page 1of 26

For Construction

0 2/15/2018 Issued For Information SWL KSW


REV. DATE DESCRIPTION PRPD CHKD APPD
OWNER :

PROJECT :

KALSEL-1 COAL FIRED POWER PLANT PROJECT


CONTRACTOR :

SUB-CONTRACTOR :

PT. GRAHA USAHA TEKNIK

PREPARED BY DATE TITLE

2/15/2018
CHECKED BY DATE
20KV DISTRIBUTION LINE
SWL 2/15/2018
CCTV POLE FOUNDATION CALCULATION
APPROVED BY DATE

KSW 2/15/2018
DOCUMENT NUMBER REV. NO.

KSL1T-XX-XXX-XX-XXX 0
KALSEL-1 2x100MW Coal Fired Power Plant

1. GENERAL
2.1. Basic Design Parameters
Structure nam : CCTV Pole
Type of strcuture : Steel Pole
Type of Foundation : Shallow Foundation

2.2. Materials
Concrete for Foundation : Class B
fc' = 25 MPa

Reinforcement : SNI BJTS 40


Minimum yield strength (fy) 390 MPa
Minimum tensile strength (fs) 500 MPa
Modulus of elasticity (Es) 200000 MPa

2. LOADING
2.1. Dead Load (D)
2.1.1. Selfweight
Foundation selfweight to be automatically generated by software
2.2.2. Other Dead Load
Weight of pole 100 kg = 100 kg
CCTV + Accessories 5 kg = 5 kg
total = 105 kg
= 1.0 kN
2.2. Live Load (L)
Live load to be considered in this analysis is human load (including tools)
assigned as Point Load at certain points.
Live load, PL = 150 kg
= 1.5 kN

2.3. Wind Load (W)


ASCE 7-05, Clause 6.5.10
Design wind speed v = 120 km/hr
= 33.33 m/s
Terrain category, = C (Cl 6.5.6.3)
Importance factor, I = 1.0 (Cl 6.5.5)
Gust effect factor, G = 0.85 (Cl 6.5.8)
Wind directionality factor, Kd = 0.9 (Cl 6.5.4.4)
Velocity pressure exposure coefficient, Kz = 0.9 (Cl 6.5.6.6)
Topographic factor, Kzt = 1.0 (Cl 6.5.7.2)
Force coefficients, Cf = 0.7

PT. Graha Usaha Teknik


2
KALSEL-1 2x100MW Coal Fired Power Plant

Velocity pressure, qz = 0.613Kz*Kzt*Kd*V*I qz = 0.55 kN/m2


Design wind load, W = qz*G*Cf*Af = 0.33*Af kN

Wind Load at pole


Diameter of pole, d = 100 mm
Pole height, h = 6 m
Area tributary, Af = 0.6 m2
Wind Load at center height of pole, W = 0.20 kN
Momen at pole base, Mw = 0.6 kNm

2.4. Seismic Load (V)


Seismic load shall be conformed to the more stringent between Indonesian Seismic Code
and UBC 97.

2.4.1. Seismic Load Based On Indonesian Seismic Code


Parameters:
Spectral response acceleration parameter at period of 1s (S1) 0.1 g
Spectral response acceleration parameter at period of 0.2s (Ss) 0.25 g
Peak ground acceleration, (PGA) 0.15 g

Ss value S1 value

PT. Graha Usaha Teknik


3
KALSEL-1 2x100MW Coal Fired Power Plant

Calculation:
Site Class = D
Importance Factor, I = 1.25
SS = 0.232 g
S1 = 0.077 g
Fa = 1.6 (Table 11.4-1 ASCE 7)
Fv = 2.4 (Table 11.4-2 ASCE 7)
SMS = F a * SS = 0.3712 g
SM1 = F v * S1 = 0.1848 g
SDS = (2/3) * SMS = 0.25 g
SD1 = (2/3) * SM1 = 0.12 g
Sa = SDS = 0.25 g
R = 3 (Table 15.4-2 ASCE 7)

Design Seismic Force, V V = (Sa / R) * I * W


V = 0.103W

2.4.2. Seismic Load Based On UBC 97 Code


Parameters:
Seismic zone factor = 2A
Sismic coefficient, Ca = 0.22
Cv = 0.32
Importance Factor, I = 1.25
Calculation:
R = 2.9
o = 2
Design base shear V = 0.110 W
Not exceeding, Vmax = 0.237 W
Not be less than Vmin = 0.030 W

Design Seismic Force, V V = 0.11W

2.4.3. Seismic Design Load


Seismic design load: the most critical between 2.4.1 & 2.4.2
V = 0.11W
W = 1.0 kN
V = 0.1 kN

Moment at pole base, Mv = 0.2 kN

PT. Graha Usaha Teknik


4
KALSEL-1 2x100MW Coal Fired Power Plant

2.6. Load Summary

Load Case FX (kN) FY (kN) FZ (kN) MX (kNm) MY (kNm)


Dead Load D 0.0 0.0 -1.0 0.0 0.0
Live Load L 0.0 0.0 -1.5 0.0 0.0
Wind Load X Wx 0.2 0.0 0.0 0.0 0.6
Wind Load Y Wy 0.0 0.2 0.0 -0.6 0.0
Seismic Load X Ex 0.1 0.0 0.0 0.0 0.2
Seismic Load Y Ey 0.0 0.1 0.0 -0.2 0.0

2.6. Load Combinations


2.6.1. Load Combinations (ASD)
Following load combinations are used for stability
Based on Civil & Structure Design Criteria

PT. Graha Usaha Teknik


5
KALSEL-1 2x100MW Coal Fired Power Plant

2.6.2. Load Combination (USD or LRFD)


Following load combinations are used for reinforcement design of foundation
Based on Civil & Structure Design Criteria

PT. Graha Usaha Teknik


6
KALSEL-1 2x100MW Coal Fired Power Plant

3. FOUNDATION DESIGN SUMMARY

PT. Graha Usaha Teknik


7
KALSEL-1 2x100MW Coal Fired Power Plant

PT. Graha Usaha Teknik


8
ATTACHMENT A
SOFTWARE INPUT & OUTPUT
FOUNDATION CALCULATION SHEET

One-Stop Solution for Foundation

TITLE DESCRIPTION
PROJECT/JOB NO. GUT
PROJECT/JOB NAME GUT
CLIENT NAME GUT
SITE NAME Kalsel
DOCUMENT NO.
REFERENCE NO.
STRUCTURE NAME CCTV Pole
LOAD COMBINATION GROUP NAME
REV DATE DESCRIPTION PREP'D CHK'D APPR'D APPR'D

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 1

FOUNDATION LISTS
Group Name No. Description No. Description
F1 1 F1

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 2

CONTENTS

1. GENERAL
1.1 MATERIALS & UNIT WEIGHT
1.2 SUBSOIL CONDITION & SAFETY FACTORS
1.3 LOAD COMBINATION

2. DRAWING
2.1 LOCATION PLAN & DETAIL SKETCH

3. FOUNDATION DATA
3.1 FOOTING AND SECTION DATA
3.2 PIER DATA
3.3 LOAD CASE
3.4 LOAD COMBINATION

4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
4.2 CHECK OF OVERTURNING MOMENT
4.3 CHECK OF CONTACT PRESSURE

5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
5.2 REQUIRED REINFORCEMENT
5.3 ONE WAY SHEAR FORCE
5.4 TWO WAY SHEAR FORCE

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 3

1. GENERAL

1.1 MATERIALS & UNIT WEIGHT


Items Value
2
Concrete (f'c : compressive strength) 25.000 N/mm
2
Lean Concrete (Lf'c : compressive strength) 15.000 N/mm
2
Reinforcement (D10 ~ D16 , yield strength) 240.000 N/mm
2
Reinforcement (D19 ~ , yield strength) 400.000 N/mm
3
Rs (Soil unit weight) 14.000 kN/m
3
Rc (Concrete unit weight) 24.000 kN/m
2
Es (Steel Modulus of Elasticity) 29000.000 kN/mm
2
Ec (Concrete Modulus of Elasticity) 3605.000 kN/mm

- Soil Capacity
Items Value
Soil Name q_all
Footing List F1
2
Qa (Soil Bearing Capacity) 68.7 kN/m
Buoyancy Not Consider
WL (Water Label from the EL = 0) 0 mm
FD (Frost Depth from the EL = 0) 0 mm
Internal Friction Angle 0
Passive Soil Pressure Consider
2
Cu (Undrained cohesion) Clay , 35 kN/m

1.2 SUBSOIL CONDITION & SAFETY FACTORS


Items Description
Allowable Increase of Soil (Wind) 33.33 %
Allowable Increase of Soil (Seismic) 33.33 %
Allowable Increase of Soil (Test) 20 %
Safety factor against overturning for OVM1(FO1) 1.5
Safety factor against overturning for OVM2(FO2) 1.5
Safety factor against overturning for OVM3(FO3) 1.5
Safety factor against overturning for OVM4(FO4) 1.9
Safety factor against sliding for the SL1(FS1) 1.5
Safety factor against sliding for the SL2(FS2) 1.8
Safety factor against sliding for the SL3(FS3) 1.5
Safety factor against sliding for the SL4(FS4) 1.5
Friction factor (m) 0.35

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 4

1.3 LOAD COMBINATION


Index Load Case Name Load Case Description
1 SW SELF WEIGHT
2 DL DEAD LOAD
3 LL LIVE LOAD
4 WX WIND LOAD X
5 WY WIND LOAD Y
6 EQX SEISMIC LOAD X
7 EQY SEISMIC LOAD Y

Comb . ID Load Combination for stability


101 1.0 SW + 1.0 DL + 1.0 LL
102 1.0 SW + 1.0 DL + 1.0 LL + .6 WX
103 1.0 SW + 1.0 DL + 1.0 LL + .6 WY
104 1.0 SW + 1.0 DL + 1.0 LL + .75 EQX
105 1.0 SW + 1.0 DL + 1.0 LL + .75 EQY
Comb . ID Load Combination for Reinforcement
201 1.4 SW + 1.4 DL
202 1.2 SW + 1.2 DL + 1.6 LL
203 1.2 SW + 1.2 DL + 1.0 LL + 1.0 WX
204 1.2 SW + 1.2 DL + 1.0 LL + 1.0 WY

Copyright (c) GS E&C. All Rights Reserved


3/15/2018 Page 5

2. DRAWING REFERENCE DWGS


NO. DWG NO. DWG TITLE

A01

NOTES
* OUTPUT UNIT : mm

01

GUT PROJECT

F1 FOUNDATION LOCATION PLAN


CCTV Pole

SQUAD CHECK
Y
PROCESS PIPING VESSELS STRUCT. ELEC. INST.

Z X SCALE JOB NO. MICROFILM NO.

AS SHOWN GUT

Copyright (c) GS E&C. All Rights Reserved


3/15/2018 Page 6

OUTPUT UNIT : mm

Copyright (c) GS E&C. All Rights Reserved


3/15/2018 Page 7

REFERENCE DWGS
NO. DWG NO. DWG TITLE
800 CL FOOTING
400 TOP BOTTOM

TYP.
3
400

6-D13

6-D13
800

NOTES
* ANCHOR BOLT
1X4-M12 ANC. BOLTS (TYPE TYPE L)

* OUTPUT UNIT : mm

6-D13
6-D13
FOUNDATION PLAN FOOTING REINF. PLAN
75 PROJ.

GUT PROJECT
400
TOC EL. + 100 100 100
2 3

200 1.5
TYP.

100
@150
600

D10
500

D13 FOUNDATION DETAIL FOR


400

200
F1
D10
75

100
3

SQUAD CHECK
300

8-D13
PEDESTAL
3

PROCESS PIPING VESSELS STRUCT. ELEC. INST.

LEAN CONC. 50 THK


CRUSHED STONE 100 THK
SCALE JOB NO. MICROFILM NO.
SECTION
REV. DATE DESCRIPTION DRWNCHKD APPD APPD APPD
AS SHOWN GUT

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 8

3. FOUNDATION DATA
3.1 FOOTING AND SECTION DATA
( mm ) Ft. Name F1
Ft. Type ISO
2
800 Area 0.640 m
Ft. Thickness 300.00 mm
3
Ft. Volume 0.192 m
Ft. Weight 4.608 kN
Soil Height 500.00 mm
400 400
3
Soil Volume 0.240 m
Soil Weight 3.360 kN
800

Buoyancy Not Consider


Self Weight (except Pr.SW) 7.968 kN

600
500

300

The Origin coordinate


The Center of gravity (0,0) mm

Section Data
( mm )
Ft.Name Direction Ft. Volume Soil Volume Pier Wt
3 3
F1 All Direct 0.192 m 0.240 m 2.304 kN

Sec.Name Section Area Ft. Weight Soil Weight Total Weight


2
S1 0.640 m 4.608 kN 3.360 kN 10.272 kN

3.2 PIER DATA


Off X , Off Y is offset position from the Center of the footing
If Pier Shape is Circle or Circle wall, Pl is a Diameter. and Pw is a Inner Diameter
Area is pier concrete area
Weight is pier and inner soil weight in case circle wall except Tank1 Type(Circle Ring Footing Shape)
2
Unit( Length : mm , Weight : kN , Area : m )
Ft.Name Pr.Name Shape Pl Pw Ph Area Weight Off X Off Y
F1 1 Rectangle 400.000 400.000 600.000 0.160 2.304 0.000 0.000

3.3 LOAD CASE


Fz
Fy
Mz
Input the point loads in the global coordinate system direction. Positive directions of moments (shown in the sketch)
My are based on the right hand rule.
Fx
Mx

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 9

Index Load Case Name Load Case Description


1 SW SELF WEIGHT
2 DL DEAD LOAD
3 LL LIVE LOAD
4 WX WIND LOAD X
5 WY WIND LOAD Y
6 EQX SEISMIC LOAD X
7 EQY SEISMIC LOAD Y

Unit( kN , kN-m )
Ft.Name Pr.Name Load Case Fx Fy Fz Mx My
1 0 0 -2.3 0 0
2 0 0 -34.8 0 0
3 0 0 -1.5 0 0
1 4 0.2 0 0 0 0.6
F1
5 0 0.2 0 -0.6 0
6 0.1 0 0 0 0.2
7 0 0.1 0 -0.2 0
Footing SW 0.000 0.000 -7.968 0.000 0.000

3.4 LOAD COMBINATION


In Pier Top In Footing Bottom In Footing Bottom Center
without Self Weight with Pier Self Weight, with Pier & Footing Self Weight & Soil Weight,
But without Footing Self Weight, Case PileType
in centroid of Pile Group
Case NonPileType
in centroid of Footing

3.4.1 Load Combination in Pier Top (Without SW)


Unit( kN , kN-m )
Ft.Name Pr.Name L.Comb. SFx SFy SFz SMx SMy
101 0.000 0.000 -36.300 0.000 0.000
102 0.120 0.000 -36.300 0.000 0.360
103 0.000 0.120 -36.300 -0.360 0.000
104 0.075 0.000 -36.300 0.000 0.150
F1 1 105 0.000 0.075 -36.300 -0.150 0.000
201 0.000 0.000 -48.720 0.000 0.000
202 0.000 0.000 -44.160 0.000 0.000
203 0.200 0.000 -43.260 0.000 0.600
204 0.000 0.200 -43.260 -0.600 0.000

3.4.2 Load Combination in Footing Bottom (With Pier SW)


Unit( kN , kN-m )
Ft.Name Pr.Name L.Comb. SFx SFy SFz SMx SMy
F1 101 0.000 0.000 -38.604 0.000 0.000
1 102 0.120 0.000 -38.604 0.000 0.468
103 0.000 0.120 -38.604 -0.468 0.000

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 10

104 0.075 0.000 -38.604 0.000 0.218


105 0.000 0.075 -38.604 -0.218 0.000
201 0.000 0.000 -51.946 0.000 0.000
202 0.000 0.000 -46.925 0.000 0.000
203 0.200 0.000 -46.025 0.000 0.780
204 0.000 0.200 -46.025 -0.780 0.000

3.4.3 Load Combination in Footing Bottom Center (With Pier & Footing SW)
Load Combination of Elastic Condition
- C.G. of Load is coordinate from left bottom. Unit : mm Unit( kN , kN-m )
Ft.Name L.Comb. SFx SFy SFz SMx SMy C.G. of Loads
101 0.000 0.000 -46.572 0.000 0.000 400.0 , 400.0
102 0.120 0.000 -46.572 0.000 0.468 400.0 , 400.0
F1 103 0.000 0.120 -46.572 -0.468 0.000 400.0 , 400.0
104 0.075 0.000 -46.572 0.000 0.218 400.0 , 400.0
105 0.000 0.075 -46.572 -0.218 0.000 400.0 , 400.0

Load Combination of Ultimate Condition


- C.G. of Load is coordinate from left bottom. Unit : mm Unit( kN , kN-m )
Ft.Name Sec.Na L.Comb. SFx SFy SFz SMx SMy C.G. of Loads
201 0.000 0.000 -51.946 0.000 0.000 400.0 , 400.0
202 0.000 0.000 -46.925 0.000 0.000 400.0 , 400.0
F1 S1
203 0.200 0.000 -46.025 0.000 0.780 400.0 , 400.0
204 0.000 0.200 -46.025 -0.780 0.000 400.0 , 400.0

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 11

4. CHECK OF STABILITY
4.1 CHECK OF SLIDING
mSFz + P.F mSFz + P.F
Formula : ( or ) > Fs -> OK (Uni-Axial)
SFx SFy
P.F = Passive Force (apply only in case checked passive force, mark by P ) Unit ( kN )
Ft.Name Dir. L.Comb. ( mSFz + P.F) / SFx or ( mSFz + H.P.F) / SFy Fs(i) Result
X 103 SFx = 0 , Then N/A P 1.8 OK
F1
Y 103 ( 0.35 46.57 + 0.5 ) / 0.12 = 140.03 P 1.8 OK

4.2 CHECK OF OVERTURNING MOMENT


Formula : (SMry / SMoy or SMrx / SMox) > OVM(i) -> OK Unit ( kN-m )
Ft.Name Dir. L.Comb. SMry / SMoy = OVM or SMrx / SMox = OVM OVM(i) Result
X 102 18.63 / 0.47 = 39.81 1.5 OK
F1
Y 102 SMo = 0 , Then N/A 1.5 OK

4.3 CHECK OF CONTACT PRESSURE


4.3.1 Contact Pressure Formula
'Handbook CONCRETE ENGINEERING' Second Edition edited by Mark Fintel

SFz SMy X(i) SMx Y(i)


q1,q2 = or
Af Iy Ix
if q1 or q2 < 0 , than q1 and q2 will be recalculated
by following formula
L
0
q(x) width(x) X dx
Px = L
0
q(x) width(x) dx
L
P = 0 q(x) width(x) dx

4.3.2 Input Data


2 4 4
Ft.Name Af (m ) Fl (m ) Fw (m ) Ix (m ) Iy (m )
F1 0.640 0.800 0.800 0.0341 0.0341

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 12

4.3.3 Pressure Check


- Qa = Soil bearing capacity
- Uc = Uplift Allowable capacity
- X-Direction (Uni-Axial) 2
Unit( kN , kN-m , kN/m )
Ft.Name L.Comb. q1 q2 ci cj Qmax Qa Cont.A.R Result
F1 103 72.769 72.769 0.000 0.800 72.8 91.6(gross) 100 % OK

- Y-Direction (Uni-Axial) 2
Unit( kN , kN-m , kN/m )
Ft.Name L.Comb. q1 q2 ci cj Qmax Qa Cont.A.R Result
F1 103 67.284 78.253 0.000 0.800 78.3 91.6(gross) 100 % OK

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 13

5. DESIGN OF FOOTING
5.1 DESIGN MOMENT AND SHEAR FORCE
Footing design is in accordance with unltimate strength method at footing bottom.
Calculated total pier load as
SQ = SFz - Self Weight Factor (Soil Weight + Footing Weight)
Ft.Name : Footing Name , Sec.Name : Strip Name for Footing Reinforcement Design
Dir. : Direction , L.Comb. : Load Combination Index , Sl or Sw : Strip X or Y width

5.1.1 Data Unit( mm , kN , kN-m )


Ft.Name Sec.Na Dir. L.Comb. Fl or Fw Sl or Sw SFz SM SQ
201 800.00 800.00 51.946 0.00 51.946
202 800.00 800.00 46.925 0.00 46.925
S1 X
203 800.00 800.00 46.025 0.78 46.025
204 800.00 800.00 46.025 0.00 46.025
F1
201 800.00 800.00 51.946 0.000 51.946
202 800.00 800.00 46.925 0.000 46.925
S1 Y
203 800.00 800.00 46.025 0.000 46.025
204 800.00 800.00 46.025 -0.780 46.025

5.1.2 Design Parameters


Yield Strength - D10 ~ D16 : fy1 , D19 ~ : fy2
f_cl : Clear Cover for edge of footing reinforcement
f_clt : Clear Cover for top of footing reinforcement
f_clb : Clear Cover for bottom of footing reinforcement
Loc. : Location of Critical Point from left side of footing

2
Unit(N/mm ,mm)
f(Flexure) f(Shear) f'c fy1 fy2 f_cl f_clt f_clb
0.85 0.8 25.00 240.00 400.00 3.0 3.0 3.0

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 14

5.2 REQUIRED REINFORCEMENT


5.2.1 Reinforcement Formula
- Shrinkage and temperature reinforcement
As = fac b h , fac = 0.002 ---- USD99 CODE 5.7.2(1)
- Required Reinforcement by Analysis
As As2
- At every section of flexural members where tensile reinforcement is required
As As5
As As4
- The requirements of Eq (6.3.2) need not be applied, if every section As provided is
at least one -third greater than that required by analysis
As2 = r.req b d
As3 = 1.333 r.req b d
1.4
As4 = bd
fy
0.25 fck
As5 = bd
fy
Asmax = 0.75 rb b d
fck 0.003 Es
rb = 0.85 b1
fy 0.003 Es + fy
Selected As = Max ( As1 , As2 , Min ( As3 , Max ( As4 , As5 ) ) )
If Selected As < Using As < Asmax , then OK!!

Note : The reinforcement is calculated bases on the maximum moment under the foundation in each direction.
But, the 'ISO' , 'OCT' , 'HEX' , 'COMB' , 'TANK1' foundations are calaulated as face pier
Where,
Mu 0.85 fck 2Rn
Rn =
fbd
2 , f = 0.85 , r.req =
fy ( 1- 1-
0.85fck )
5.2.2 Check of Footing Reinforcement
Footing Name : F1 GroupType : Isolated
- X direction (All Width)

Sec.Nam L.Comb. Using Bar (mm) Loc. (m) Width b (m) d (mm) As (mm )
2

204 top 6 - D13 @ 158.8 0.400 0.800 290.650 760.061


S1
201 botom 6 - D13 @ 158.8 0.600 0.800 290.650 760.061

Sec.Nam L.Comb. Mu (kN-m) Rn r.Req


204 top - - -
S1
201 bottom 1.299 0.023 0.0001

Sec.Nam L.Comb. As1(mm )


2
As2(mm )
2
As3(mm )
2 2
As4(mm )
2
As5(mm ) Asmax(mm )
2

204 top 240.000 - - 1356.367 1211.042 13088.560


S1
201 bottom 240.000 21.920 29.220 1356.367 1211.042 13088.560

Sec.Nam L.Comb. Using As(mm )


2
Select As(mm )
2
Result
204 top 760.061 240.000 OK
S1
201 bottom 760.061 240.000 OK

- Y direction (All Width)

Sec.Nam L.Comb. Using Bar (mm) Loc. (m) Width b (m) d (mm) As (mm )
2

204 top 6 - D13 @ 158.8 0.400 0.800 277.950 760.061


S1
201 botom 6 - D13 @ 158.8 0.600 0.800 277.950 760.061

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 15

Sec.Nam L.Comb. Mu (kN-m) Rn r.Req


204 top - - -
S1
201 bottom 1.299 0.025 0.0001

Sec.Nam L.Comb. As1(mm )


2
As2(mm )
2
As3(mm )
2 2
As4(mm )
2
As5(mm ) Asmax(mm )
2

204 top 240.000 - - 1297.100 1158.125 12516.650


S1
201 bottom 240.000 22.922 30.556 1297.100 1158.125 12516.650

Sec.Nam L.Comb. Using As(mm )


2
Select As(mm )
2
Result
204 top 760.061 240.000 OK
S1
201 bottom 760.061 240.000 OK

5.3 ONE WAY SHEAR FORCE


5.3.1 One-Way Shear Formula
- f Vc = 0.8 1/6 fck B'w d
- Vu <= f Vc , then OK!!

5.3.2 Check of One-Way Shear


Footing Name : F1 GroupType : Isolated PileType : False

Unit : mm
800
800

- X direction One-Way Shear (All Width)


Sec.Nam L.Comb. Loc. (mm) d (mm) Bw (mm) fVc (kN) Vu (kN) Result
S1 201 0 290.6 800 155.013 0 OK
- Y direction One-Way Shear (All Width)
Sec.Nam L.Comb. Loc. (mm) d (mm) Bw (mm) fVc (kN) Vu (kN) Result
S1 201 0 277.9 800 148.24 0 OK

Copyright (c) GS E&C. All Rights Reserved


3/15/2018

Project Na. : GUT


Calculation Sheet
of Project No. : GUT

Foundation Client : GUT Page 16

5.4 TWO WAY SHEAR FORCE


5.4.1 Two-Way Shear Formula
Vu = SFz Shade Ratio
f Vc1 = 0.8 1/6 (1 + 2/ bc) fck bo d
f Vc2 = 0.8 1/6 (1 + as d / 2 bo) fck bo d
f Vc3 = 0.8 1/3 fck bo d
f Vc = Min(f Vc1 , f Vc2 , f Vc3)
Vu f Vc , then OK
where
bc = ratio of long side to short side of the column, concentrated load or reaction area
as = 40 for interior colimns
= 30 for edge columns
= 20 for corner columns
bo = perimeter of critical section
Footing Area - Punching Area
Shade Ratio =
Footing Area

5.4.2 Check of Two-WayShear


2
Ft.Name F1 Punching Area 476997.500 mm

800 Pr.Name 1 Ratio Shade 0.255

Shape Rectangle f Vc1 1605.900 kN

L.Comb. 201 f Vc2 1661.666 kN


800

Pl 400 mm f Vc3 1070.600 kN

1 Pw 400 mm f Vc 1070.600 kN

bo / d 2762.6 / 290.65 mm Vu 13.230 kN

bc / as 1 / 40 Result OK

Copyright (c) GS E&C. All Rights Reserved

You might also like