Krohne Oil & Gas: Customer Review Code
Krohne Oil & Gas: Customer Review Code
Work may proceed subject to incorporation of indicated comments. Revise & resubmit.
MEUK13102016
Leak Detection System for ARL
LINE 16NL217
Customer:
Mountever UK Limited
16NL217-SYS-0011 A11
Customer Drawing / Document No.: Rev.Nr.
REV DATE DRAWN DESCRIPTON OF CHANGES
A11 04.01.2017 N. Nielsch Initial Version
Related Documents:
DOCUMENT NAME DOCUMENT NUMBER REV
PIG PIG
XX1 PT PT
XX2
101 102
SL-1 H
6" Diameter H Pig Receiver
H
H
TT
TT 102
101
Signal
Splitter
Signal
Splitter
Meter prover loop
FT DT FT
XX1 XX1 XX2
Inlet: Outlet:
Attock Oil Refinery (ARL) Shell Chaklala Terminal
Total Length ~8 km
Remote HP LaserJet
PipePatrol
Access Workstation
PipePatrol Server
USB Ethernet
USB
Keyboard/ Mouse
Ethernet Ethernet
PT TT
101 101 Ethernet by others Phoenix Contact
Phoenix Contact
I/O-Modul - AXL F Phoenix Contact PT TT
I/O-Modul - AXL F Phoenix Contact
Phoenix Contact TC MGUARD RS4000 AI4 I 1H AXC 1050 102
AI4 I 1H AXC 1050 Phoenix Contact 102
3G VPN
DT TC MGUARD RS4000 3G VPN
XX1
PLC + AI + DI/DO GSM Modem/Ethernet switch GSM Modem/Ethernet switch PLC + AI + DI/DO
CLIENT: MountEver UK Limited DOCUMENT NO.: 16NL217-SYS-0011
PROJECT NAME: Leak Detection System for ARL Line KROHNE Oil & Gas DRAWN: N. Nielsch SIZE: REV.
Minervum 7441
4817 ZG Breda The Netherlands DATE: 1/11/2017
SHEET NAME: Network Overview Tel: +31 (0)76 711 2000 KOG PROJECT NO.: 16NL217
A4 A11
Fax. +31 (0)76 711 2001
SHEET: 4 of 8
Remote Terminal Unit 1 (RTU 1)
- FT-XX1
For more details, refer to following documents:
General Arrangement Cabinet –
RTU 1 at Attock Oil Refinery (ARL): 1 x Ethernet
= 1 Pulse Signal
Doc no.: 16NL217-ENI-3530 TCP/IP communication
to Shell Chaklala Terminal
- DT-XX1
= 3 Analog Inputs (4-20 mA) Antenna cable for 3G Communication
- PIG-XX1 - Sounder
- Beacon
- Status PLC
- Cabinet UPS alarm
- Cabinet temp high alarm
- Cabinet PSU = 5 Digital Inputs (24 V DC)
= 2 Digital Outputs (24 V DC)
- TT-102
- PT-102 1 x Ethernet
TCP/IP communication
= 2 Analog Inputs (4-20 mA) for Remote Access
- PIG-XX2 - Sounder
- Beacon
- Status PLC
- Cabinet UPS alarm
- Cabinet temp high alarm = 2 Digital Outputs
- Cabinet PSU = 5 Digital Inputs (24 V DC) (24 V DC)
TCP-IP
PipePatrol Visualization PipePatrol
for Attock Refinery to Chaklala terminal SynEnergy 3 Data
pipeline
OPC Client OPC Client Field Data
COM COM
OPC Server
Kepware KepServerEX V5
+ Modbus Suite PipePatrol Server
PipePatrol Server
TCP/IP
Modbus Slave TCP/IP via Ethernet Modbus Slave
TT-XX TW-XX
COM Ethernet
XX-XX XX-XX
HTML 5
4-20 mA Analog Signal
Modbus
Motor Operated Valve Shut Down Valve Hand Valve Pulse Signal
PipePatrol
MOV-
XX
MOV-XX M SDV-
XX
SDV-XX M
HV-XX HV-XX H Data 24 V DC Digital
M M
H
24 V DC
Field Data
Pig Launcher Pig Receiver 230 V AC
XXX XXX
3G Communication
USB
XX
xx1 unknown transmitter
XX
xx1 unknown tagname
FT Flow Meter
PT Pressure Transmitter
TT Temperature Transmitter