[ERV Plus]
1
Trainer Profile
• Name :
• E-mail :
■ ERV + Basics
SAMSUNG
ERV ■ Key Technology
■ Case Study
■ ERV Line-up
■ Duct design
5
ERV + USP
Simple line up
6
ERV+ USP
Samsung D company
High Efficiency Medium-filter Pre-filter
7
ERV+ USP
Standard 52.2 Pre/Medium
Min. Efficiency (EN 779)
Class
Reporting Value HEPA/ULPA
(MERV) (EN1822)
1 D company Panel Type Compact Pocket Type
G1
2
3
G2
4 G 35
Pre filter MP 35
5 F 40 / F 45
G3
6
7
G4
8
Samsung Compact Pocket Type Compact ECO Pocket Type
9
F5
10
Medium 11 F6
F 50
Filter 12 F7 EP Series
MF Series
13 F8
14 F9
15 H 10
HEPA ULPA SF Series
16 H 11
HEPA 17 H 12
18 H 13
19 H 14
20 U 15
ULPA U 16
U 17
8
ERV + Basic
Supply Air
Access panel
Damper
9
ERV + Basic
Temperature range
10
ERV + Basic
The specification
11
11
ERV + Basic
62.82 kJ/Kg
35℃
RH 40% 27℃
-5 0 5 10 15 20 25 30 35
RH 47%
Dry bulb (℃)
71.7 62.82
Enthalpy efficiency ratio 100 = 49.5 %
71.7 53.77
12
ERV + Basic
2/1℃
OA SA
Heating
7℃ 20℃ -5 0 5 10 15 20 25 30 35 40
RH 87% RH 59%
Dry bulb (℃)
13
Operation mode
Operation mode
Energy recovery
(Heat exchange)
On/off button
Mode button
By-pass Fan button
Auto ventilation
Condition
Energy recovery
(Heat exchange)
|OA temp. – RA temp| >= 5℃
16
Operation mode
Clean up operation
Toilet
Living Room
Positive pressure
17
Operation mode
Outing operation
Quite operation
18
Operation mode
: Energy saving operation is run when all the following conditions are met.
1) One or more ERV units must be connected to MWR-WE10N (without or with indoor unit(s) )
2) Either the indoor unit or ERV must be ON (if the indoor unit is ON, it must not be FAN mode).
3) ERV must not be in Outing mode
4) ERV external control must not be enabled.
5) ERV must not be in “Centralized” control mode.
6) ERV must not be in “Kitchen Hood” control mode.
NOTE : The sub wired remote controller does not support energy saving mode
19
Operation mode
S 26°C S 22°C
Energy
Saving
Out temp < Set temp Out temp < Room temp Set temp < Out temp Room temp < Out temp
: Cool air intake ↑ : Cool air intake ↑ : Warm air intake ↑ : Warm air intake ↑
Out temp >= Set temp Out temp >= Room temp Set temp >= Out temp Room temp >= Out temp
: Heat exchange ↑ : Heat exchange ↑ : Heat exchange ↑ : Heat exchange ↑
20
ERV Plus
• Energy saving operation – EHP-ERV combined
: The operation of an ERV-combined indoor unit is not interfered by energy saving operation, but performs
temperature control as it usually does.
EHP
F3-F4
21
ERV Plus
• Energy saving operation – ERV only installation
ERV Plus MWR-WE10N LOW
MEDIUM
HIGH
F3-F4
TURBO
30 minutes 30 minutes
22
Operation mode
23
Operation mode
Heating operation
C area Suction air temp < auto cooling setting temp – Thermo off gap temp.
24
Operation mode
-After working of ventilation mode, cooling and heating mode of DX coli is possible.
25
Safety operation
26
Fan operation with CO2 sensor
☞ ERV airflow will be controlled automatically to supply fresh air by CO2 Level
CO2
Note
1. Option setting required
Fresh Air 2. In general, above 1000ppm is regarded
CO2
as pollution
27
Humidification
Humidifier element
Bracket
Water feed pipe
RHF050KHEA RHF100KHEA
Flow switch Connecting hose
Regular
0.2 L/min 0.4 L/min
flow rate
28
Humidification
29
Humidification
Intake air temperature : 0 ~ 40 ℃ Use at least the same as that of drinking or tap water
Supply water temperature : 2 ~ 40 ℃ Use neutral detergent for cleaning
Supply water pressure : 0.08 ~ 0.7 MPa
30
ERV Plus
- External control
- ERV ON/OFF control by external contact switch (enabled by option setting)
- 02 installation option
31
ERV Plus
- Kitchen hood control
: No need to set the option switch to enable kitchen hood control
Kitchen hood
External Kitchen hood Humidifier
control control control
32
ERV Plus
- Humidify control
: Humidity control by humidifier and locally purchased humidity sensor enabled by option setting
Heating + 05 option seg15 : 1-use 1
→ Solenoid valve on after3min.
33
ERV Plus
- External damper control
: External damper control or interlocking signal enabled by option setting (05 option seg16 : 0-disuse, 1-use)
Relay/Magnet
switch
Connection to external load via relay/magnet
(load current : over 0.5A)
34
ERV Plus
• CO2 sensor (MOS-C1)
- Pulse width variation depending on CO2 level (pulse period = 1004ms)
ppm 2ms
0ppm
2000 4ms
4ppm
1002ms
Pulse 2ms
2 1002 width 2000ppm
35
ERV Plus
• Option setting - 05 installation
Remote
controller
display
Exhaustion
Air RPM is
fixed as Quiet
0 0 Disuse 0 Disuse 0 Disuse
mode RPM
Positive
pressure
Indication &
details Supply
air RPM is
fixed as
1 Quiet mode 1 Use 1 Use 1 Use
RPM
Negative
pressure
36