SJ700 Drive Mapping on Profibus - PPO-5

Send request data to read


28 byte Drive RUN/STOP status in
SJ700 drive
I/P / O/p Send request data to read byte 14 & 15 continously -
Input Address
Address Oputput Current in byte 12 & Para read d003, Profibus
13. Continously Address 418 dec.
(Request send on write word (Request send on write Send request data to store
/Response receive on read word /Response receive on profibus configured data in
word) read word) drive NV memory
#0 #0 DRIVE HEALTHY AND status word bit 0 and 1 0

#1 DRIVE TRIP Status word bit 3 1 7394 hex / 4394 hex 7394 hex / 4394 hex 23CB hex
#2 DRIVE WARNING - 2
#3 OUTPUT BRIDGE ENABLED - 3 0100 hex / 0100 hex 0200 hex / 0200 hex 0000 hex
#4 OVER SPEED DETECTED - 4
Read para d003, byte 14 & 15, if value 0 then
#5 NO ZERO SPEED MEASURE STOP and if 1 Or 2 then RUN 5 0000 hex / 0000 hex 0000 hex / 0000 hex 0000 hex
#6 TORQUE LOOP SATURATION - 0001 hex / 0000 hex ( Set 1 for
#7 DRIVE RESET REOUIRED No need (fixed value 0) - 6,7 Fault code 0197 hex / 0197 hex 01A2 hex / 01A2 hex 10 second then set 0)
#8 NO EMERGENCY STOP REQ -
status word
#9 DRIVE IN TORQUE LIMIT Fixed value 0 - 8,9
#A ABSENCE OF NORMAL STOP REQUIRED -
Read para d003, byte 14 & 15, if value 0 then Actual Freq.
#B DRIVE RUN REQUESTED STOP and if 1 Or 2 then RUN 10,11
#C DRIVE READY AND status word bit 0 and 1
Output Current
#D PRECHARGE CONTACTOR IN - 12,13
#E MOTOR BRAKING -
#F ENCODER LOSS No need (fixed value 0) - 14,15 RUN/STOP status
#1 #0 EXTERNAL RESET No need (fixed value 0) -
#1 NO EXTERNAL E STOP - 16,17
#2 NO NORMAL STOP No need (fixed value 1) -
#3-#5 BLANK - 18,19
#6 CONVERTER UNLOCKING -
#7 BLANK - 20,21
#8 POWER SWITCH ON O/P contactor ON AND status word bit 0 and 1
#9 BLANK - 22,23
#A CONVERTER RADY EXTERNAL -
#B-#F BLANK - 24,25
Write 1163 in byte 0 &1 - for reading Fault code in 6
& 7 byte continous. Or triger if status word fault bit
#2 #0-#F FIRST TRIP CODE ON
#3 #0-#F FIRST ALARM CODE - 26,27
#4 #0-#F SPEED MEASURE 100%/26214digit Actual Freq. 0 to 4000 hex , byte 10 & 11,
Parameter d002 (add hex 197), byte 12 &13,
#5 #0-#F CURRENT MEASURE 150%/32767digit Devided by 10
#6 #0-#F TORQUE MEASURE 300%/32767digit -