Professional Documents
Culture Documents
Substation Automation Handbook
Substation Automation Handbook
Substation Automation Handbook
Volker Lohmann
Wolfgang Wimmer
Substation
Automation
Handbook
Comprehensive description of Substation
Automation and the coordination with
Network Operation to obtain both
performance and cost benefits by enabling
enhanced Power System Management
. ·.::
Copyright© 2003 by
Klaus-Peter Brand · klaus-peter.brand(!1 ieee.org
Volker Lohmann · volkerlohmann@ bluewin.ch
Wolfgang Wimmer · toptools (([ bluewin.ch
Publisher:
Utility Automation Consulting Lohmann,
lm Meyerhof 18, CH-5620 Bremgarten, Switzerland
http://www.uac.ch
Printed in Germany
ISm3-85758-951-5
1 Table of content
1 Table of content 5
2 About this Book 7
3 Introduction and Scope 15
4 Challenges with introducing Substation Automation 31
5 Primary Equipment in Substations 43
6 The Functions of Substation Automation 93
7 Substation Automation Structure 141
8 Substation Automation Architectures 151
9 Asset Management Support 183
10 New Roles of Substation Automation 197
11 Wide Area Protection 211
12 Standards and Quality Definition for Substation Automation 279
13 The System Standard IEC 61850 for Substation Automation 301
14 Phase Models of Substation Automation Systems 313
15 Benefits of Substation Automation 325
16 Guide to SA System Specification 339
17 Strategy to Cope ;,vith the fast Changing Technology 345
18 Trends and Outlook 349
19 References 353
20 Glossary 361
21 Annex 367
. '(
·
2 About this Book
The users were not happy about this situation as they When the design of IEDs to be applied fnr SCS
felt to be restricted to a specific vendor if they inten systems was based on common main stream hard
ded to extend their control systems. On the other ware components as well as on modular functional
hand, many SCS were implemented by small compa libraries for control that were quite similar to functio
nies and based on general purpose programmable nal libraries for protection, it was possible to integra
logical control (PLC) systems that could not provide te control and protection systems in comprehensive
the required functionality or meet the long term ori systems for substation automation (SA). The authors
ented system compatibility requirements, which are were personally involved with the development and
typical for the electric utility business. On the other implementation of a comprehensive platform for
hand, many of these small companies did not last for multipurpose control and protection IEDs. Therefore,
a long time because of commercial problems and the focus of this book is on SA rather on SCS with 7
2.2 separated protection. The objective of the authors is the power system integrity is maintained. SA enables
to make those readers with a background in substa automated corrective actions that reduce the respon
tion control or protection confident that the integra se time to problems significantly.
tion of both functionalities leads to cost effectivesys
tem solutions that have the same safety and availabi If sudden loss of generation or increase of load caus
lity as systems with separate IEDs for control and for es instabilities so fast that the operator has no chan
protection. ce to react fast enough, SA can be used by the wide
area protection scheme for rapid automatic load
The integration of the control and protection functio shedding to compensate for the loss of generation
nality to SA makes effective substation monitoring, and to reduce the load.
primary equipment condition and support of modern
systems for maintenance and asset management Because of this new role of SA, the scope of this
possible as an additional benefit that can be derived book as outlined in Chapter 3 has been extended
from SA. This book describes the realization of such beyond the traditional functions to describe wide
concepts, which lead to an enhancement of the over area protection schemes and their interaction with
all power system management. The objective is that SA. The objective is to make system planners and
the readers, who wish to evaluate the commercial operators aware of the new possibilities that are offer
benefits that can be derived from SA, become aware ed by SA in conjunction with wide area protection
that such an cost/benefii analysis has to take those systems and power system optimization concepts.
additional benefits into account.
. · . (
enthusiastic and receptive, and no utility wanted to requirement specification and engineering was made 2.2
take the risk to run a pilot project One of the main by Bernhard Sander, [2] and the function plan pro
obstacles for the acceptance were the utility's orga gramming for the bay controllers by Fritz Wittwer,
nization. The reason was that substation control. pro while Volker Lohmann was the project manager of
tection and communication were considered to be the total contract comprising the 800 kV GIS deve
separate disciplines and, consequently, each was lopment and delivery as well as the SCS part.
organized in separate departments. As the SA
approach integrated the whole lot in one system, the Five years after the order, ALPHA was successfully
idea of separate departments became obsolete, commissioned on 31st March 1987 within the sche
which was perceived by the corresponding depart duled delivery time.
ment managers as a threat.
After the merger of BBC and ASEA to become ABB
This situation changed drastically, when BBC was on 1Oth of August 1988, the progressive activities on
awarded by ESKOM South Africa with the world-first SCS in Switzerland were allocated to the protection
800 kV GIS 'ALPHA'. on 14th of December 1982. division of ABB Switzerland, which was headed by
This spectacular order has created a huge innovative Jean Gantner A new group for the SCS business
momentum not only in BBC for the development of development was established with Volker Lohmann
a complete new size of GIS but also on ESKOM's as manager and Klaus-Peter Brand, Wolfgang
side with regard to the readiness to accept new ideas Wimmer, Helmut Hager and Otto Preiss as members
and technologies [1] of the first core team. Two years later, this division
became the new company ABB Relays AG, which
The key issue for the ESKOM's acceptance of a
was managed by Otto Lanz.
microprocessor based substation control system
(SCS) was the complex and large 800 kV GIS substa In ABB Relays AG, the world-first commercial com
tion layout comprising 12 switchgear bays that would mon hardware and software platform dedicated for
have required a very extensive interlocking scheme, if the protection and control of HV substations was
it had been designed by relay logics. In view of the developed under Fred Engler, who was head of the
fad that more than 1 00 contacts of auxiliary switches development department. This innovative and revo
and relay contacts would have had to be connected lutionary approach enabled to merge protection and
in series for one single interlocking expression in control functions into one integrated system and to
Boolean algebra, ESCOM considered such a solution allow modern SA functions.
as impracticable und unreliable. The much better
solution was the BBC proposal to substitute hard The commercial break-through of this new platform
wired interlocking by a microprocessor based expert was enabled in conjunction with the first PC based
system, called "Topology based interlocking scheme", MicroSCADA from ABB Finland, which was used as
which was based on general rules rather than on station level HMI, and with the complementary new
Boolean Algebra expressions. This new idea was range of microprocessor based protection relays and
developed by Jurgen Kopainsky, Klaus-Peter Brand bay control units from ABB Finland for distribution
and Wolfgang Wimmer. [3] applications. The market acceptance was achieved in
the course of the first SA projects in Switzerland and
The development and implementation of this first in the UK. The key people for the successful comple
SCS in ALPHA was first headed by Jurgen Kopainsky tion of these demanding projects were Otto Preiss,
and later by Hermann Schachermayr, the customer Andre Kreuzer and Kurt Frei. 9
2.2.2 2.2.2 Curriculum Vitae Klaus-Peter Brand
From 1976 to 1982 he worked in the BBC Research the PM act1v1t1es in ABB Network Partner/Baden
Center, Baden, Switzerland in the area of SF6 plasma Switzerland He participated in the successful imple
physics (SF6 arc in high voltage breakers). He intro mentation of the ISO Certification process and was
duced the on-line literature search facilities in the responsible for the definition of the PM process He
Research Center. further provided sales support for complex projects,
and established the first ABB Internet based market
From 1982 to 1988 he acted as Senior Engineer in ing tool for Panorama.
the department for "Power System Analysis" of BBC.
Baden, Switzerland making load flow and EMTP cal In 2000 he moved to the ABB University Switzerland
culations. He participated in the team for the intro to manage, conduct and develop training courses
duction of "Substation Automation" jointly writing the mainly on the subjects of Power systems, Electro
Function and Engineering Specification, and design magnetic compatibility, Substation automation and
ing the System architecture. He joint the project team Communication. He has further set up a new curricu
for the pilot project in Substation Automation of an lum for Project managers.
800 kV GIS substation and was involved in the deve
lopment and application of the topology based Since 1990 he is working for CIGRE SC B5 (former
Interlocking method. He further acted as co-editor of SU4) as working group (WG) and task force (TF)
the company owned Handbook for Electrornagr1etic convener. Since 1995 he is member of the editor
Compatibility. team in WG10 of the IEC technical committee TC57
for the Standard IEC 61850 "Communication Net
After the merger of ASEA and BBC to ABB, from works and Systems in Substations'He is further
1988 to 1995 he was involved in the substation member of TK57, the Swiss National Mirror Commit
automation (SA) business development in ABB tee of TC57, and he is Senior Member of IEEE.
Relays/Baden, Switzerland to set up the engineering
activities, sales support and to contribute to the
design and realization of pilot projects. In the local
ABB organization he was product manager (PM) for Volker Lohmann was born 1940 ·In Mulheirn-Ruhr,
SA and he acted globally as chairman of the market Germany and studied Electrical Engineering at the
requirement group to define the next ABB genera Rheinisches Politechnikum DUsseldorf, Germany. He
tion of SA systems. gained his professional experience from more than
30 years of working with Brown Boveri Cie (BBC) and
From 1995 to 1999 he was PM of the ABB Panorama ABB Switzerland in various management positions
10 concept for Network Control and SA and coordinated and fields related to high voltage (HV) substations, HV
. '?
Volker Lohmann Wolfgang Wimmer · 2.2.2
circuit breakers (CB), gas insulated switchgear (GIS) Hamburg, where he also graduated in Computer
and substation automation (SA). He started his ca Science about Deadlocks in Communication net
reer 1965 with research in the application of HV works. After five years working for the Deutsches
power electronics for High Voltage Direct Current Elektronensynchroton in Hamburg, where he wrote
(HVDC) and variable speed drives. After several years compilers and implemented the base software for a
in research he moved into the sales and marketing packet switching network, he moved to Brown Boveri
organization for HV circuit breaker and gas insulated & Cie (BBC) in Baden/Switzerland.
switchgear (GIS) as sales and project manager. In
1982 the world's first 800 kV GIS project offered him There he started vvith the design and implementati
the opportunity to initiate the development and im on of a train control system and became member of
plementation of the first BBC microprocessor based the technical committee TC7 "Safety and Reliability"
substation control system (SCS) as the project mana of the European Workshop on Industrial Computer
ger. His coauthors were member of the project team. Systems (EWICS) He was further involved in the
design of engineering systems for remote terminal
In the course of the merger between BBC, units (RTU) and Network Control Systems. During this
Switzerland and ASEA, Sweden, in 1987 he was res time, he was also member of the IEC technical com
ponsible for the product management for SCS and mittee TC65 to develop the standard IEC 61508
protection and was involved in the development of a "Safety in Industrial Electronic Systems".
multi-functional and software library based platform
for intelligent electronic devices (lED) for control, pro His involvement in substation automation started in
tection and monitoring of HV substations. In 1995 he 1983 with participation in the development of a
became member of the ABB Business Area Mana topology based interlocking program, and continued
i gement Team for SA and protection and was world with the introduction of microprocessor based con
l wide responsible for the product management and trol systems for the substation automation business.
strategic marketing of SA systems. He retired in 2002 After the merger of BBC with Asea in 1987, he conti
and started his own company for Utility Automation nued with these activities in the new company- ABB
Consulting, where he is presently working. with focus on engineering processes and tools. He is
currently occupied with the development of substa
tion automation and monitoring systems at ABB/
Wolfgang Wimmer was born 1947 in Bad Switzerland, and he is member of the IEC TC57 work
Schwartau, Northern Germany. He studied Mathe ing group WG11 as editor of the upcoming standard
matics and Computer Science at the University of IEC 61850 for Communication in Substations, part 6. 11
; ·.
' I
2.3 Acknowledgements
2.5 There are quite a number of colleagues to be men Martin Ostertag (ABB Switzerland)
tioned, who have contributed directly or indirectly to Otto Preiss (ABB Switzerland)
this book by cooperating with us over more.than 20 Bernhard Sander (former BBC Switzerland)
years for a longer or shorter time. They have helped Hermann Schachermayr (ABB Switzerland)
to collect the basic information, to elaborate market Leif Williamsson (ABB Finland)
requirement specifications, to establish the SA busi
ness, to develop advanced ideas and to maintain the We further thank our company, ABB Switzerland, that
high level of the state-of-the-art. Most of them came gave us the great opportunity and support to build
from our internal business environment in BBC and up all this know-how in an inspiring international
ABB respectively, but there have been other impor environment, which has finally been converted into
tant contributors from customers and even from chal numerous SA products, systems, and projects.
lenging competitors. There have always lively discus
sions taken place, not only in our every day's working We further express our appreciation to Gbran Lind,
life but also in internal and external meetings, in Head of the Division Utility Automation System in
International Conferences, as well as in ABB Switzerland for his continuous, encouraging and
International Organizations like CIGRE and IEC and supporting interest in our book, as well as his Sub
the associated working groups. In order to avoid division Manager, Yves Baumgartner, for selecting our
that some contri butors are not mentioned below, book as official reference for ABB internal and exter
we first would like to express our cordial gratitude nal training in Substation Automation.
and appreciation very generally to all those
colleagues, we were privileged to work with on the
subjects of SA and communica tion within
substations.
2.4 We would like to hear from you
Some of these colleagues we like to mention are
listed below in alphabetic order as they have been This is the first edition of the Substation Automation
intensively involved in our activities in substation auto Handbook. In view of the fad that the technology is
mation and in our involvement in the IEC 6185 developing very fast and that it will enable further
stand ardization, each of them in a very particular enhancements in functionality and application it may
wdy: be desirable to produce further editions. This occa
sion would be an excellent opportunity to introduce
Lars Andersson (ABB Switzerland) comments and modifications, which may be raised
Carl Byman (ABB Sweden) and proposed by some of our readers. Therefore, we
Christoph Brunner (ABB Switzerland) encourage you to contact us via E-mail and to help
Rudolph Dinges (ABB Germany) that. the next edition can be improved accordingly.
Fred Engler (ABB Switzerland)
Kurt Frei (ABB Switzerland)
Soren Forsman (ABB Sweden)
Helmut Hager (former ABB Switzerland) 2.5 Readers Guide
Antti Hakala-Ranta (ABB Finland)
In the area of substation automation there are work
Jurgen Kopainsky (former BBC Switzerland)
ing people with different professional background.
Andre Kreuzer (former ABB Switzerland) Very often, this leads to a lack of mutual understand-
Lars-Gunnar Malmqvist (ABB Sweden)
12 Carl-Gustav Oesterbaka (ABB Finland)
ing between people with power system- back
ground, who e.g started their professional career
before PCs became a common working tool, and
computer scientists, who are familiar with the
modern way of thinking in the computer age_ They,
however, usually lack of the understanding of the pri
mary equipment and the particular requirements for The objectives of the authors are 2.5
making electronic equipment work in the harsh envi • To transfer their extensive know-how of all the
ronment of HV substations. Apart from this, they are aspects related to the technical, functional and
not aware of the sensitivity of the power system pro commercial issues around SA to all decision
cess and the impact of the control actions that are makers in utility management, system operation,
initiated by the IEDs on the power system behavior. system planning, engineering and maintenance
who wish to improve their personal knowledge
The authors are well aware of this conflict and the in this field (Chapters 4, 9, 10, 15 refer).
lack of mutual understanding from their personal
background in switchgear and substation automation • To make the power system oriented readers
as well as from their extensive experience in aware of the new possibilities and benefits that
can be exploited with the implementation of
• Gas insulated switchgear (GIS) research, design substation auwrnation systems (Chapters 4, 9,
and application, 10, 11, 1 5 refer).
• The development of substation automation
concepts, software functions and components. • To make the readers with a background in
conventional control and protection systems
• The marketing and introduction of SA business
(secondary systems) familiar with the specific
as well as negotiating SA contracts, managing
performance and safety aspects of SA systems
projects, trouble shooting and
that comprise integrated numerical protection
• last but not least from more than 20 years of and control T''"'nctionality (Chapters 6, 7, 8 refer).
teaching and conducting SA workshops in many
parts of the world. • To make the readers involved in the development,
design and application of IT in terms of intelligent
Many SA projects became a disappointment for electronic devices (lED) and for SA aware of the
users as well as for the suppliers as they failed to specific needs of the power system and the safety
meet the expectations with regard to cost effective- and availability related aspects of substation con
ness. The reasons were always very similar: the trol and protection (Chapters 6, 7, 8, 12, 13 refer).
users were not in the position to specify their • To provide the readers, who are involved with
requirements and the suppliers were not aware of engineering, testing and commissioning of SA
the genuine needs of their customers. The main systems with background knowledge with regard
motivation to write this book was the awareness to SA systems architectures, availability and safety
of the need for such a SA Handbook as a aspects as well as to the allocation of functions in
contribution to improve the mutual understanding a SA system (Chapters 6, 7, 8 refer).
between the two conflicting parties.
• To convey decision makers in utilities the message
that the implementation of SA throughout their
All readers are invited to read Chapter 3
substations offers new chances for the utilities to
"Introduction and Scope" to get familiar with the
improve their internal processes to the extent that
general way of thinking and the related vocabulary.
the overall costs in power system operation and
In addition to chapter 3 the readers may chose
maintenance are drastically reduced, the return on
those chapters that cover their missing knowledge.
investment is accelerated and the productivity as
well as the profitability of the enterprise is signifi
cantly improved (Chapters 4, 11,15 refer).
13
Table 2-1 provides a more detailed guidance for the
readers with various background and experience to
select the chapters that may be of particular interest
to tl1em to complement their specific knowledge
with information around SA.
..
2.6
R 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 21
Students X X X X X X X
Beginners in
Computer science,
Power systems,
Financal planning,
System operation X X X X X X X X X X X
Decison makers:
System planning,
System operation
Design/engineering,
Maintenance X X X X X X X X X
Developers X X X X X X X X X X X X
Engineering spec. X X X X X X X X X X X X
Protection spec. X X X X X X X X X X X X
SCADA spec. X X X X X X X X X X X X X
Testing/comissioning X X X X X X X X
Maintenance X x 1x X X X X
System planning X X X X X X X IX
Table 2-7 Readers Guide ·
2.6 References
[1] Volker Lohmann (BBC/Switzerland), Andrew C Bolton (ESGOM/South Africa)
Gas insulated switchgear developed for 765 kV, Modern Power Systems,
February 1985, published by United Trade Press Ltd. London/UK
[3] Klaus-Peter Brand, JUrgen Kopainsky, Wolfgang Wimmer · Topology based interlocking
14 of electrical substations, IEEE Trans. on Power Delivery PWRD-1, 3, 118-126 (1986)
' I
. ·
3 Introduction and Scope
3.1 Scope 16
3.2 Electric power as sensitive basics of our today's society 16
3.3 The electric power system 16 3
3.3.1 The long and complex path from power generation to power consumption 16 Table of
3.3.2 The power production 16 content
3.3.3 Three-phase system and current, voltage and frequency 17
3.3.4 The transportation of electric energy by the network and the related voltage levels 18
3.3.5 Some comments to voltage levels in electric power systems 19
3.3.6 The consumption of electric energy 19
3.3.6.1 The definition of root mean square values 20
3.4 Specific Aspects of the Electric Power System 20
3.4.1 The power flow 20
3.4.1.1 Production equals consumption 20
3.4.1.2 Base load demand and load peaks, variation of demand per day, week 21
3.4.1.3 Power flow controlled by physics of the power network 21
3.4.1.4 Many voltage levels for transmission and distribution 21
3.4.2 Power generation, network stability and energy quality 21
3.4.2.1 Dispersed power generation (DPG) 21
3.4.2.2 Complex network with stability problems 21
3.4.2.3 Power quality 22
3.4.3 Safety aspects 22
3.4.3.1 High currents, voltages and surges 22
3.4.3.2 Electromagnetic interference and high-frequency noise 22
3.4.3.3 Protection 23
3.5 The Role of the Substation for the grid 24
3.5.1 Node functionality 24
3.5.2 Access to the power and power network 24
3.6 The Role of Substation Automation for the Network Management 25
3.6.1 The Power Network Management System 25
3.6.1.1 The structure 25
3.6.1.2 The overall tasks 26
3.6.2 Local Functions in Substations 26
3.6.3 The local support functions for Network Level Systems 27
3.6.4 The cruci9l role of communication 27
3.7 Substation Automation Systems 28
3.7.1 Short definition of Substation Automation Systems 28
3.7.2 The History with Remote Terminal Units 28
3.7.3 From RTU to SA 28
3.8 Substation Automation Soiutions 29
3.8.1 Commercial questions behind substation automation solutions 29
3.8.2 Benefits of Substation Automation 29
3.8.3 The realization of SA automation 29
3.9 References 30 15
3 Introduction and Scope
1..
Figure 3-7 This schematic picture indicates the countrywide interconnection of power production
16 and consumption by the network
AQ
3.3.3
Photovoltaic cells like batteries produce electric ener Figure 3-3 Three-phase synchronous machine (generator)
gy with constant voltage and current called direct cur
rent (DC).
,.·.',
The production of electric power with the above
I
I mentioned rotating machines, where coils are mov
ing in changing magnetic fields, provides a sinuosoi
dal, alternating current (AC). Since these machines
(Figure 3-3) have usually three poles displaced by 1/3
of a complete turn we get a three-phase system, i.e.
Time
three-phase belts (windings) with induced sinuosoi
dal alternating voltages feeding three conductors - Phase1 Phase 2
Phase3
- •
'? '?
'?
This rotation frequency gives the frequency both of The conductors have some resistivity against this cur I
the voltage and the current Common values for the rent described by the above-mentioned impedance I I
(' j
power frequency are i.e. 50 Hz (e.g. in Europe) or consisting of indudivity, capacity, and resistivity.
60 Hz (e.g. in US). For some few railway systems, Overhead lines and cables form the network and, to
also some very small extent, gas isolated lines (GIL). In
16.7 Hz (formerly 16 2/3 Hz) is in use. Current refers plans of such networks, the conductors for all three \ !
to conducting particles (electrons) moving through a phases are shown as single lines.
3.3.4 conductor. Its driving force is the voltage with the
same frequency built up by the magnetic field in the The nodes in this network are substations
generators. Basically, power is calculated out of the providing facilities for switching on and off the
product of current and voltage. Considering the connections. In addition, the transformers are placed
phase shift (angle difference) described by sincp or here normally.
coscp between current and voltage or not. we get
three types of power, i.e. the apparent power (S), the Generators produce power at voltage levels of about
reactive power (Q) or the active power (R). The last 10 kV. This voltage has to be transformed up to the
value is what provides the electric energy to work for level of the connected transmission network. This is
us (see section 3.3.6.1). done by separate transformers (block transformers),
or more advanced, by transformer windings integrat
The three-phase system is advantageous as the three ed in the generator itself (power former). Depending
displaced phases fit well to rotating machines whit on the capacity and length of transmission lines need
out dead point. and no return conductor is needed ed, high and very high voltages are used for trans
under fault-free conditions. mission, typically from above 100 kV up to about
1000 kV. At the other side of the transmission lines,
The advantage of AC systems is that its voltage can these voltages are stepwise reduced by transformers
be transformed to higher and lower levels by trans to the subtransmission and distribution level of the
formers being based again on changing magnetic network (100 kV to 10 kV) and further down to
fields in the transformer coils. These magnetic fields match finally the voltage level of the consumer
result in inductance and the related electric fields in (below 1 kV in the most cases). Such a network is
capacitance of each wire. Both effects have to be shown schematically in Figure 3-5.
added to the Ohmic resistance of the conductor. The
result is the impedance meaning losses and phase
shifts of the sinusoidal currents and voltages. The
advantage of DC is that only the Ohrnic resistance Une
Transmission
has to be considered. These advantages of DC are
used also for power transmission by High Voltage
Direct Current (HVDC) lines. With these features, we
have started already to touch the transmission and
distribution of electric energy.
The different voltage levels found in electric power Direct current (DC) systems may be classified com 3.3.6
systems are not classified in any standard as low vol monly as follows:
tage (LV),·medium voltage (MV), high voltage (HV),
extra-high voltage (EHV), or ultra-high voltage (UHV). • Low voltage (24- 250 V): Auxiliary power in
In most countries, safety laws are connected with power plants and substations, control circuits and,
such a classification; national differences exist in this occasionally, utilization power in some industrial
classification. Only the limit between LV and MV is plants.
very commonly fixed at 1 kV. see e.g. IEC 60038. The • Medium voltage (300 - 600 V): Transportation
classification limits have been very often created industry
because of historical technical steps in switchgear
technology. • High voltage (greater than 600 V): Long
distance bulk transmission, submarine, and major
system interconnections
To avoid too many alternative solutions and too close
voltage levels, in IEC 60038 recommended sequen
It should be noted that such a classification is
ces of voltage levels are given, but without any refe
very often a characteristic for protection devices
rence to any voltage level terrn.
(distribu tion protection, transmission protection, etc)
and, there fore, may vary to some extent from
Another common classification of voltage levels refers supplier to sup plier. To follow the increasing demand
to the type or purpose of the network applied, e.g. if of electric ener gy, the functionalities are allocated to
it transmits power over long distances between gene higher voltage levels, e.g. in big cities energy is
ration and load centers, or if it distributes power from distributed at HV in a typical distribution network
some transmission end point to the users of the load structure.
center. A common example for AC (alternating cur
rent) is
• Distribution level (3.6 - 36 kV): Circuits transmitting 3.3.6 The consumption of electric energy
power to the final retail outlet, mostly with a radial
structure. Big consumers like machines and other industrial
• Sub-transmission level (17.5 - 145 kV): Circuits equipment are using three-phase energy supply at
transmitting power to distribution substations and medium voltage level (below 50 kV).
to bulk retail outlets, mostly with a linear or/and
ring structure. The private consumers may use three-phase supply
for heatig equipment like cooking and cleaning
• Transmission level (72.5 - 765 kV): Circuits trans
equipment. For a!! other purposes single-phase sup
mitting power between major substations of
ply is provided. In any case, the voltage level for pri
interconnecting systems, and to wholesale outlets.
vate consumers is at low voltage levels below 1 kV.
These transmission lines are further divided into:
• High voltage (HV): 115 - 245 kV For heating only the time average of the AC power is
effective. These time-averages for current. voltage
• Extra high voltage (EHV): 300 - 765 kV
and power are called rms (root mean square) values.
• Ultra high voltage (UHV): greater than The ever-present electronic devices rectify by their
power supplies the ACto DC as needed by their
elec
765 kV tronics. 19
.1 '
,;,.
,;,.
'? '?
'.[
3.4 3.3.6.1 The definition of root mean ting each other perfectly. The reactive power Q
square values shows the impact of such elements. Since Q degrad
es the transmission capacity for P and influences the
Instantaneous values of voltage and current voltage profile of the power system, producers or
consumers may have to pay a penalty.
U =Uosinwt
I =I osin( cut - rp)
U0 and lo are the amplitudes of voltage
and current respectively 3.4 Specific Aspects of the
f = 2nw is the power frequency Electric Power System
cp is the phase angle difference In addition to the features mentioned above, the
between voltage and current electric power system has many characteristics, which
are based on physical laws, equipment features and
Time averages means effective values or rms (root
user behavior. All these aspects have to be consider
mean squares)
ed for design and operation of the power system.
d lo The most important ones are listed below.
I I sm(mt - rp)
T .
le.ff = o t = r;;
0 v2 3.4.1 The power flow
T
3.4.1.1 Production equals consumption
le.ff = J I o sin(cut - rp )dt = ;
o v2 The production of power has to be more or less
T = 2n ;w is the period of the equal to the consumption since means for power
current or voltage storage are limited today (Figure 3-6). The most
powerful means are pump storage schemes, but also
Active Power pressure storage facilities, spinning wheels, batteries
and fuel cells are used to some small extent.
1T !I"
f
P =- U(t)I(t)dt
Power flow i
To
1 T . .
= ..:...U
T
of of s m mtsm(OJt- rp )dt = leffileffCOS rp
•
0
0.6
3.4.3. 7 High currents, voltages and
0.4 surges
0.2
Electrical power systems are operated at high voltage
0.0
0.0 0.2 0.4 0.6 0.8 1.0 P/Pm levels, which may endange.r human life or cause da
P/Pm= 1 mages for equipment. Therefore, adequate isolation,
Maximum power
transmission its supervision against damages, and proper ground
capability ing is essential. High currents may produce both ther
Figure 3-8 System stability: PV Operating Curve for mal effects and electromechanical forces, especially in
Transmission Lines (V5 fixed source voltage, case of short circuits. Lightning strokes and switching
V, variable load voltage, P power delivered operations may cause transient surges that proper
to load, Pm maximum power) protection means like surge arrestors have to be
applied.
3.4.2.3 Power
quality 3.4.3.2 Electromagnetic interference
and high-frequency noise
Power quality means mainly availability and stable fre
quency and is either assumed for given or negotiated Arcing strokes and re-strokes are caused by switching
in specific delivery contracts. These contracts may re of isolators and result in high-frequency transients
quire availability of electric energy without any inter (Figure 3-10). Therefore, effective grounding of switch
ruptions down to some milliseconds, constant power gear is not only requested at power frequency condi
frequency and stable supply voltage (Figure 3-9). tions but also for high frequencies. Proper grounding
and shielding avoids all effects, which may disturb or
destroy electronic equipment inside and outside the
substation.
kV .Us ul
nA , ,
+100
utL 0 ......:.......r1_u_ _ un'1..!..1{ If vL \I _
-100 ' 11 Reliable power supply is important, power 3.4.3.3
equipment
0 50 100 150 ms
I, -t is costly and the high voltages and currents may
cause damages both for people and devices. Short
circuits occuring in the transmission system on gene
rators (G), transmission and distribution lines or on
the loads (L) have to be detected in the shortest pos
sible time and the associated equipment must be
protected (Figure 3-11). Therefore, adequate protec
tion functions implemented in dedicated protection
devices are installed to safeguard the operation of
the electric power system.
f
f f
t ®t-€G .I*------¥<.1
fm --------!
- ;?Ill- MMC ·-
l 0
--
. I'
f
li
-(])-
1 ••
--llllf
I PROTECTIONICONTRO L-
UNIT/SYSTEM
23
3.5 The Role of the Substation
for the grid
3.5 3.5.1 Node functionality Some few compact HV substations are indoor and
housed in buildings but the majority of HV sub
The substation is the node in the electrical power net stations is outdoor and subject to severe climactic
work, which connects the lines and cables for trans conditions.
mission and distribution of electric power. The electri
cal node is the busbar in the substation. To cope with As mentioned above (Figure 3-7), the series impe
the dedicated needs for reliability and availability of dance and the shunt admittance of transformer, lines
the electrical power supply various busbar schemes and cables of the power system determine the
are in use like single busbar, double busbar, 1112 brea power flow. However, the switchgear in the sub
ker arrangement, ring bus, and H type. station may also limit this power flow. The maximum
allowed continuous rating is given mainly by the ther
Circuit breakers and isolators are installed to connect mal withstand capacity of the conducting material
or disconnect the incoming and outgoing lines with and the withstand capacity of contacts against
the busbar. The power flow is actively controlled and magnetic forces. In addition, the short circuit breaking
routed by these switching devices, i.e. by opening capacity of the circuit breakers limits the maximum
and closing the circuit breakers. For reliable insulation power allowed being connected via the network.
in case of open lines, disconnectors or insulators are
associated to the circuit breakers. Since these dis 3.5.2 Access to the power and power
connectors cannot break power, they must only be network
operated with the associated breaker in open posi
tion. To provide safety for maintenance earthing swit Instrument transformers measuring the actual volta
ches or temporarily earthing devices are used to ges and currents deliver the essential information
assure that the area under maintenance is without concerning the power system status. Both the power
voltage and dead. Introduction to switchgear see frequency and the local power flow is calculated out
chapter 5 and [3]. of these values or measured by dedicated power
meters directly.
in addition to the switchgear, there may be transfor The switchgear in the substations and the inter
mers in the substation to connect busbars at different connecting transmission and distribution lines are the
voltages if applicable. The tap changers of the trans high valued assets of the power system owner in
formers control the voltage in between. Voltage drops power business terms. As faults and failures do not
across the transmission lines between substations only degrade the devices but cause also losses in
occur because of the capacitance and reactance of power delivery, the status of these components is
the lines, the voltage may be adjusted also by adapt supervised or monitored in the substations for asset
able capacitor banks or reactors, which serve as sour management depending on the monitoring techno
ces or sinks of reactive power. logy applied and the owner's maintenance philoso
phy.
Depending on the voltage level and other boundary
conditions, there is a lot of different switchgear All these means in the substation provide the inter
(some times called primary equipment) installed in face accessing the power system, i.e. for changing the
substa tions. They are described in chapter 5. The actual topology, for measuring voltage and current,
isolation medium may be air (air isolated substation and for providing data about the assets. This access
- AIS) or SF6 gas (gas isolated substation -GIS) or a may be used either by human operators or by auto
combina nomous automatics like protection functions.
24 tion of both.
The switchgear will be described in chapter 5. The
system and functions for controlling, monitoring and
protecting the power network in the nodes and their
relation to the overall network management will be
explained in paragraph 3.6.
3.6 The Role of Substation At the various levels, different tasks or functions are 3.6
performed referring to the allocated parts of the
Automation for the Network power system. From the view of the substation, all
Management functions performed in the substation are called local
functions and all functions at the higher control levels
3.6.1 The Power Network Management are called remote functions. Therefore, the complete
System network control system may be reduced to a two
level system model at least in the context of this
3.6. 7. 7 The structure book.
The power network management system is a multi
level hierarchical control system. The highest level, e.g. Since a lot of local functions provide subsidiary sup
the National Control Center (NCC) manages the com port to remote functions, the interaction of these func
plete network; subordinated control levels e.g. repre tions with the network management functions has to
sented by Regional Control Centers (RCC) manage be discussed as a whole.
some regions. The lowest control level is in the sub
stations where the Substation Automation System
controls the node and provides direct access to the
power system (Figure 3-12).
Figure 3-7 2 Hierarchy of the netvvork power
management system
NETWORK
LEVEL R
-E-G-IO-N-I a- m)--!=o9
N
-A-TI-ON
Network control
r£at" 'dI
AREA 1
2
Network control
SUB . r\1_.e_t_:_:_r - -on-_tr_o_l....,.
STATION
LEVEL
F"--· &
Switchgear Switchgear Switchgear Switchgear·-
Figure 3-73 The Kirchhoff's Laws In addition to the powr system, its most costly com
ponents, i.e. the switchgear is monitored as well pro
viding all data important for maintenance. Apart from
Inherent differences in the acquisition equipment and the power system, also the substation automation
the common time base cause some inconsistencies system itself including protection is monitored, super-
26 in the data retrieved from the substations. Therefore,
. '?
vised and self-supervised. In case of any failure, either Very often, condition related data from all 3.6.4
corrective actions can be locally initiated or alarms substations in the network are collected in
can be issued. Monitoring Centers to calculate trends and to
elaborate maintenance and planning strategies and
All substation related information can be accessed via to elaborated a prognosis for the future behavior of
the local station HMI, which can also be used for power system. Therefore, the substations are the
local operations. Since in normal situations nearly all backbone of a global asset mana gement system.
sub stations are running unmanned and remotely
con trolled, data and commands are exchanged via Summarizing all the mentioned features, a
com munication links with the remote network substation automation system can be seen as
control center. both the most decentralized part and most
important part of the overall power system
management.
3.6.3 The local support functions for
Network Level Systems
3.6.4 The crucial role of communication
In case of remote operation of a substation, the
basic role of the substation automation system as The overall power management system is a distribu
source of power system information and sink of ted system. Its lowest but most important level is sub
power con trol commands is still valid. All passive station automation. Therefore, reliable communica
and active ele ments of the switchgear are tion plays a crucial role for reliable power system ope
supervised and protect ed. The most protection ration. The fast advances in communication techno
functions will stay autono mous in the substation. logy provide many new opportunities. However, the
very specific functional and performance require
Process data are provided pre-processed to ments and the long lifetime of power equipment
informa tion for the remote network control impose some hard technical and commercial con
system. Auto matic functions in the substation straints, which have to taken into consideration.
can reduce the heavy load of the functions residing
on NCC level in the network control system and
accelerate the res ponse time to contingencies to
maintain power sys tem integrity.
These functions may be performed more or less The communication function of the RTU is also need
combined in a lot of dedicated intelligent _Electro ed in the SA, but is changed to a communication
nic Qevices (lED) for control, monitoring, protection, interface. In most cases, this function is implemented
automatics, communication, etc The functions of sub in a gateway lED. Depending on the communication
station automation are described in chapter 6, the protocols used this gateway has to convert the pro
substation automation structure in chapter 7. tocols in both directions also (protocol converter). The
information collected and stored in distributed devic
es (IEDs) of the SA will be communicated to the
3.72 The History of Remote Terminal Units SCADA master via this gateway. Note that also pro
tection devices are seen as part of the Substation
Historically, the only interface between the switch
Automation integrated by the common communica
gear and the network management system was a
tion system. Protection functions may be also imple
Remote Terminal Unit (RTU) in each substation. The
mented together with control functions in one single
RTU was a central unit containing a lot of inputs and
lED.
outputs, nearly no local functions but the communi
cation interface to the remote network control center.
Depending on the functionality and availability request
RTUs and NCC both together formed the Supervisory
ed in the substation, its geographic extension and
Control And Data Acquisition system (SCADA). A
commercial boundaries, RTUs will remain a conve
SCADA system is primarily used to monitor, control
nient solution for a lot of substations. Reverse, RTUs
and manage the power system remotely by human
may be defined as most simple substation automa
intervention to deliver electrical energy as per delivery
tion systems also. Some comparison is given chapter
contracts. It provides real time status information
8.
(both analogue and digital) as well as historical infor
mation to the operator and supports his decision
The trends and outlooks for the future
making for effective supervisory control. In addition,
developments are addressed in chapter 18.
the action of protection like start and trip is included
28 as simple yes/no information.
3.8 Substation Automation Solutions
3.8.1 Commercial questions behind costs, increase productivity and to improve power 3.8
substation automation solutions system performance. How this is fulfilled will be
shown in the book
Generally, one can think of many dedicated solutions,
however, one has always to take really a hard look at One of the original means is to automate actions,
the cost efficiency of those solutions and find a justi which have been previously executed by operators.
fication for the selected implementation of SA. For This could be realized at least partly by hardwired
this purpose, some key questions have to be answer logic instead of microprocessors. The full benefits
ed like provided by the microprocessor-based lEOs only are
derived from
• What is the impact on capital expenditure
budget? • easier design of complex logic by
software including designable levels of
• What is the impact on the operating
functional integration,
expenditure budget?
• all the additional opportunities and services,
• Will all the proposed services/benefits be
which can be provided if all the information
utilized and is the approach cost efficient?
is available in digital format and shared
between IEDs.
These questions have to be discussed in the context
of the benefits of Substation l'•.utomation.
To improve the overall technical and economical
management of the power system, one would want
3.8.2 Benefits of Substation Automation to access all data stored in any lED from
anywhere. Depending on the communication link
In order to decide whether it is a benefit to use in the sub station, Substation Automation Systems
SA, any utility must firstly know, and secondly provide this
decide, what kind SA services shall be implemented. opportunity either via a dedicated link via the corpo
For the elaboration of an implementation strategy, rate network (Intranet) or via Internet selected by
the utility is faced with the following questions: security requirements. Utilities may even give dedi
cated service access to suppliers or limited user
• What are the technical objectives of SA. and
access to major customers for data that may be rele
how does each service c:::ontribute to meet the
vant to them.
objectives?
• What are the main business objectives of SA The benefits of Substation Automation are further
and how does each service contribute to meet discussed in chapter 15.
the objectives?
• When the boundary between utilities and custo
mers is inside the substation, is it expected that the
customer should have similar systems/IEDs and 3.8.3 The realization of SA automation -
whether they should be integrated with the uti!it;7
Bearing in mind the fast changing information tech
Both the most basic requirements and the highest nology, the development of systems and products
benefits of SA systems are to minimize the number for Substation Automation should be done in a well
of outages and outage times, to decrease operating defined sequence of. phases. Some of them are of
interest for customers also. 29
. '? . (
3.9 The project execution shows also well-defined phases Important for the customer is to safeguard his invest
from specification to maintenance requiring a close ments in spite of the fast changing technologies.
cooperation between customer and supplier. The Recommendations how to reach this goal are given
project has to meet all standards mentioned in chap in chapter 1 7.
ter 12 if applicable. All what has to be considered for
a successful and harmonic project execution is dis
cussed in chapter 14.
309 References
[1.1] Olle I. Elgerd 0 Electric Energy Systems Theory, 2nd ed., Mac Graw Hill,
1982 [1.2] Olle I. Elgerd, Patrick. D. van der Puije 0 Electric Power Engineering,
2nd ed., Kluwer Academic Publishers, 1997
[2.2] Helmut Ungrad, Wilibald Winkler, Andrej Wiszniewski 0 Protection Techniques in Electrical
Energy Systems, Marcel Dekker, New York (1995)
[3] Switchgear Manual, © ABB Calor Emag Schaltanlagen Mannheim, iOth revised edition,
Cornelsen Verlag, Berlin, 2001
30
4 Challenges with introducing Substation Automation
31
. !
'?
4 Challenges with introducing Substation Automation
4.1 4.l Substation Automation, book to provide answers to these questions and
explain various options how to do it depending on
the ineluctable way? customer benefits, operating philosophies, business
environment etc
Twenty years ago, the first local automatism appear [
ed in electrical substations.·Some of those automa i
tisms were used to eliminate earth faults by opening 4.1.1 Necessary conditions to install
and closing cyclically the feeders in rlV/MV substa new technology in substations
tions, others were in charge to permute automatical
ly the transformers in EHV/HV substations. These We think that four different aspects have to be con
automatism were so slow that both the operating sidered in connection with the implementation of
staff and the customers could follow these protection new technologies in substations. These involve the
and optimization procedures. electrical network the utilities social aspect, the end
customer aspect and the utilities policy aspect. All
Today, the information technology (IT) has have to be analyzed in detail.
progressed in such a way that wide area protection
schemes can be realized that are in the position to
protect the en tire power system relying on co-
4. 7. 7. 7 Electrical network
ordinated defense plans. They are the ultimate consideration
barriers intended to pre vent the spreading of losses Digital substation automation systems improve the
of synchronism through out the utility network control of the network All basic functions like tele
Distributed computers, satelli te based time control, local control, event recorder, disturbance re
synchronization and communication, broadband corder, numerical protection, automation of substa
communication networks and intelligent substation tion automation (SA) systems are interacting with the
automation systems and phasor measure ment entire power system control:
units (PMU) are involved in such protection
schemes. As the response of operating staff is too • The tele-control functionality allows the SCADA
slow with the legacy technology in emergency situa operating people to have a good oveivievv control
tions, the emergency control goes through all the on the network They receive supervision informa
automated control systems to operate globally in less tion and can operate the switchgear with the
than 0.5 second. highest reliability.
In the meantime, electromechanical, static, electronic • The control functions allow the operating people
and fully digital technology have been successively to run the substation as if they were inside it.
installed in substations. The average outage time for User-friendly human machine interfaces (HMI)
a end customer went down from 2 days to 10 minu provide the right information at the right time.
tes per year. Utilities are now selling quality of the Easy to operate and to understand are the
electricity rather than power of the electricity. qualities of the control interface. We.cannot find
any operating people who are used to SA still
There are world-wide utilities who ask themselves prefer conventional hardwired substations and
the question: Must we do it? Can we do it? What will restricted HMI.
the advantages and the inconveniences be to install
fully digital substation control systems together with
32 the advanced functionality? The authors try in this
• The sequence of event recorders with time 4.1.1.2 Utility social aspect 4.1.1.3
tagging at one millisecond, which are incorporated
in the IEDs for protection and control provide Substation automation leads to unmanned substa
comprehensive and precise information and can tions and thus fewer operating people. This is a fact
help protection people to improve the global and may mean a taboo aspect and an obstacle to
protection scheme (of all SA have the same time introduce substation automation systems. On the
reference). other hand, it can be a very important advantage in
cases when the substations are located far from the
• The disturbance recorder that are included
operation point. Considering the flexibility of opera
in SA allow the network maintenance
ting people, we assume that with a good training
engineers to analyze a faulty part of the
and good documentation, average operating people
network.
have no problem to operate correctly a digital sub
• Numerical protection relays improve the quality station automation system, locally or from remote.
of the protection. This equipment can be set with
very good precision and their behavior can even With the integrated self-diagnostic facility in connec
be dynamically adapted to changing condition tion with a centralized maintenance center, just a few
and topology. maintenance people are necessary. SA makes pre-
. ventive maintenance obsolete and allows changing
• Automation is a very important point. This to "just in time maintenance" practices with the aid of
allows the SA to have self-response to problems condition monitoring facilities.
and
to arrange in a predetermined configuration In addition, SA means reduced time to design, erect
procedure the topology of the network in few and test substations. Project teams can be reduced in
seconds. This cannot be equaled by the best number because ofthe fact that substation automa
SCADA operating people. tion systems are simpler to design, install and test.
Commencing the installation of digital substation This means, however, that that the introduction of SA
control systems requires very few conditions on the must be carefully prepared by the utility. Although the
electrical network. Existing SCADA can be used social consequences are important, the benefits for
because SA can be adapted to their communication the utility have to be given priority. There are less
protocol. Static or electromechanical relays can still be people involved but those need higher qualification
used even if the SA implies digital relays for new and their jobs are more challenging.
installations. Existing substations cail be enhanced
stepwise. SA systems can easily be connected and
coordinated with switchgear placed on the lines and 4.1.1.3 End customer aspect
cables.
Substation automation systems improve the quality
of service and thus have a positive impact on the
reliability the power supply to the end customer. SA
decreases the number of human errors as SCADA
people are enabled by means of digital interlocking
schemes to control the complex topology of the
power network with higher reliability. Such guided 33
control decreases the number of operating faults,
especially in emergency situations. Precise analyses of
fault cohditions are processed by the SA
Cost/Benefit Analysis
of New HV/MV Substations
., 100.00
1::
-
80.00
VI
VI
0 60.00
0
Q) 40.00
>
i
20.00
a;
a:: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
0.00
Years of Operation
The financial policy has to be changed as the intro 4. 7 .2.3 Network and
duction of new technologies requires consideration
energy management
.' of the costs for the total life cycle of the equipment
(Figure 4-1). aspect
4.1.3 4. 7.3. 7 Basics rules to preserve As an utility primary task to maintain the quality of
independence and to succeed service rather than to maintain suppliers equipment,
utilities may prefer to sign a maintenance
One of the most basic rules for all utilities that contract with the supplier to keep the SA
intend to introduce the SA technology is to stay equipment up to date.
indepen dent from vendors and to stay in a position
that they have the choice of the equipment But this Such an approach will ensure successful implementa
indepen dence has a cost aspect, as an utility cannot tion of the new technology and the required inde
afford to have 10 different suppliers for SA systems pendence at the same time.
because of the implications involved with regard to
spares, main tenance and training. Utilities need to It may be cost efficient to sign delivery contracts with
carefully choose the optimal solution and to buy the suppliers for several substations over a time pe
the best solution to their problem of their riod of 3-5 years. Prices will be reduced and the
problems. utili ties teams will not have to spend time on new
sub station control system designs.
A very important issue that assures independence is
the strict rule to accept only systems that are design
ed in accordance with International Standards, prefe 4. 7 .3.2 Find a global
rably with IEC 61850. This is of particular importance commitment inside your
for the communication within the substations. IEC
utility
61850 is the only standard that provides an open
architecture and assures interoperability with IEDs
A lot of different people and disciplines are involved
from various vendors, who offer compliancy with IEC
during the introduction of substation automation
61850 implemented.
systems. A good way to success is to involve all the
In the process of introducing the new technologies, it categories of people who will be involved with the
is highly recommend that utilities start with feasibility new technology.
studies to elaborate requirement specifications that
correspond to their specific needs. For the sake of
independence, it is recommended to select two 4. 7 .3.3 Find a financial indicator to
com petent suppliers only and to ask each of them chose what must be made first
to pro duce pilot installations including the
complete func tional and technical specifications. The The crucial question for an utility is whether it is eco
operating peo ple should have their specific man- nomically justified to invest in new technology for
machine interface and the maintenance engineers their substations and when the investment has to be
should obtain the documentation in accordance made and to what extent it should be done. A good
with their specific documentation style guide. approach to make this judgment is to evaluate the
shortcomings in quality of services. Such shortcomings
Aft h ·1 · 11 · · .
r..er t••e p:.ot :nsta..at:on !S ava11 able compreh.ensJve_
. could include:
factory acceptance tests should be conducted using • Lack or failure of power
generation a primary equipment simulator for product approval. • Lack or failure of
transmission
Such a product approval procedure should be
applied only once to assure that the right and feasi- • Lack or failure of distribution
36 ble product, is received on site. • Lack or failure of accounting
I.
F
I ;
To evaluate all these parameters is a very complex
task and it is suggested to define a single non-per-
formance factor called "! on Qistributed _Energy"
The F-Time parameter has to be- cut in short time
<200 ms and long time >= 200 ms (F.S-Time and F.L-
Time) because these two kinds of failure do not have
(NDE) to analyze the shortcomings in service. the same impact for the final customer. Generally, F.S-
Time are not very sensitive for the end customer
This NDE is a new unit, in the local currency by kWh, except if this one uses programmable logic compu-
which. represents the difference of money between ters without using UPS. 4.1.4
the two states of power system: F.S-Time is coming from fault on the lines (trees,
1. The utility is able to deliver the energy storms, lightning,...) and F.L-Time is commonly coming
to the end customer and from stations or equipment
2. The utility is not able to deliver
Repeatability of non-quality is a w;ry important aspect
too. The situation involved by twenty energy prob-
The valuation of the NDE is a very sensitive action lems a year is more than twice as worst than the
because the NDE is not only the benefit by kWh but
situation involved by ten energy problems a year. It
includes all the activities of the utility. For national or
seams that the customer disappointment is propor-
state utilities, the NDE will include the lack of quality
tional to the square of the default number. To eva-
I
of energy, that this factory cannot produce and then
'I,
luate this fact, we propose to use a formula like:
i cannot grow and cannot pay its people and they can-
2
c I
I
not use electricity because they cannot pay or buy Cost = A * E * N + B * E * NDE
electric equipment. where A is a utility coefficient in currency
''· E: is the power cut in kWh
The NDE does not indicate where to invest but indi- N: is the number of faults
I' cates when and how much to invest. This is the first
B: is an utility coefficient
step. The NDE is also used to sort the projects and
I NDE: is in currency/kWh
give priority between two projects. (The NDE is also
a very good parameter to control the level invest- with this approach, every utility is able to determine
I
II ment in a utility. It can be used with great benefit by what to invest and when to invest and if we consider
the management board for financial regulation.) the substations, the utility will realize rapidly that the
costs that are caused by conventional hardwired sub-
But non-quality of service translated in NDE alone is a station control systems and old protection relays are
poor approach, if we do not consider other parame- very significant.
ters as well. Level of voltage, frequency, reactive
power transfer, number of long and short time inter-
rupts are important parameters. One part of 4.1.4 Conclusion
these
parameters is involved in network stability. Moving to substation automation system is an ine-
luctable way but is not done without
consequences.
Therefore utilities use as a more complete approach Generally, we can find advantages for the end custo-
quality parameters, which are often the time of inter- mer, but the way to provide these can be difficult
for rupts coming from the electrical network and stations utilities. Examples from European or North
failures (F-Time) and time of interrupts coming from utilities can not easily be transferred
American
directly to the works on the network and the substation (W-Time). rest of the world.
Historical and detailed information of these two
para-
meters is very important so as to be able to deter- World-wide knowledge is a good guarantee for sue-
mine where to invest to increase the quality of ser- cess in such an approach. This know-how may be
VICe. learned assisted by world-wide active companies but
the major part of the thoughts must be done
inter-
nally. This approach is necessary to avoid great
deception and disillusion in the years to come. 37
. ' . ·
4.2 Management and Utilization
of Substation Data
4.3 Dedicated hardware devices for process data record • Intelligent power system voltage control:
ing that were previously proviued for data retrieval The active and reactive power flow in the network
from the control center now become functional can be tracked system wide by means of a
modules that are integrated into the IEDs. The RTU dedicated voltage control function. As it knows ·
merely acts as a gateway to provide access to these the position of all transformer tap-changers it can
data, which are transmitted to the relevant historical automatically adjust them from remote, and it also
data base for storage and processing. These data can switch capacitor banks, or initiate of load
comprise: shedding etc
• Sequence of event recordings
There may still be some obstacles like processing
• Disturbance recordings power and speed of a typical WAN/LAN, to apply
• Quality of supply measurands such new functions but they may become reality in a
• Statistical metering for power system not too distant future.
planning purposes
• Accounting information 4.3 System Performance Aspects
With these new features an SA system can be In order to assure that the SA system performs ade
provid quately to conventional systems, the following per
ed by the most cost effective functions like: formance related aspects have to be addressed:
• System-wide under-frequency load shed • Security, reliability, dependability and speed in
ding: Dedicated IEDs monitor the system volta order to ensure that the protection functionality
ges, currents, frequency and power and are com is not degraded and has highest priority at all
municating peer-to-peer on a real time basis over times
the corporate wide area network (WAN). In case
of power generation deficit detected they deter • Flexibility, expandability and forward
mine the most suitable location for performing compatibility with newer systems to ensure that
load shedding on the basis of real time voltage future expan sion can be accommodated at
instability studies, power swing predictions and minimum costs
actually measured loads.
Strategic - Automation project must improve power Until recently, automation in the substation has meant
quality, reliability of service and information available the presence of a SCADA remote terminal unit (RTU)
to many utility engineers. A recent Newton-Evans sur-
-
4.4.4 vey indicated that RTU would be primary information Communication links, other than voice grade tele
processing task handler for the majority of those phone connections, are typically between transmis
polled (54%). 35% percent indicated the require sion subs and master stations via microwave, fiber
ment for a separate processor - other than an RTU, optic, or dedicated telephone lines using relatively
15% preferred a PLC-based approach and another slow data transfer rates from 1200 to 9600 baud.
1 5 % indicated a combined approach using
both technologies. Approximately 30 % of th::>se Most distribution substations today have a limited
surveyed indicated that they had not yet formed an number of IEDs. Many have RTUs, but few have
opinion on the type of substation platform that been provided with automated SER, fault
would be imple mented. All of these answers are, of recording and microprocessor based relay systems.
course, right. For the purposes of this book, Connectivity is similar to that mentioned above for
substation automation is defined as a transmission sub stations.
microprocessor based system that inte grates and
processes substation status, analog and control Maintenance practices at legacy substations involve
information and communicates with local and/or labor intensive routine on-site manual inspection.
remote devices. Field devices such as circuit breakers, switchgear,
transformers and load tap changers are maintained
Actual, the capabilities of equipment that qualify routinely without detailed information on operation
under this definition are quite varied. SA systems of these devices.
range from simple RTUs to fully networked PC/PLC
systems that manage WAN/LAN input/outputs (1/0)
and provide advanced services for the substation
environment and mainstream distribution automation
4.4.4 Opportunities and justifications
functions.
Many opportunities exist today to design, operate
and maintain substations using better, faster and
4.4.3 Substation legacy systems and cheaper devices and service methodologies. These
practices efficiencies are accomplished by eliminating unneces
sary redundant systems and using microprocessor.
Transmission substations have received the lion's based controllers to manage information supplied by
share of automation devices in the past because of IEDs.
the importance of their reliability to system opera
tions. Automation devices at these sites include RTUs, Typically, substation automation passes justification
fault recorders, sequence of events recorders (SERs), tests under the following conditions.
annunciater panels, and a few microprocessor based
relays. Input/output (1/0) to these devices is typically New construction - the substitution of RTUs, mimic
via hardwired connections to instrument transformers style control panels, annunciaters, sequence of
(via transducers), field and local status contacts, inter events recorders (SERs), fault recorders,
posing relays, and mimic style control panels. The cable/conduit systems, and significant control room
dominant protective devices are electromechanical space with SA reduces the cost of new
relays. The local operator interface is generally a con construction while vastly improving functionality. SA
trol panel, analog meters, annunciater window is a "no brainier" for new substations.
boxes,
40 and recording devices of various types.
4.4.5. 7 Design Benefits
• Standardization of the user interface and
improved user access.
• System architecture standardization for uniformity
of operation and building SAIDA upgrade paths. 4.4.5
Significant retrofit or expansion of existing • Elimination of unnecessary redundant equipment.
substation - capital projects that add new' bays,
transformers or switchgear can easily incorporate SA • Reduced substation infrastructure including wiring,
retrofit projects cost effectively. Legacy systems can conduit wire channels, control/relay panel space
be replaced or integrated into the new SA infrastruc and control house size.
ture. • Easy upgraciability using mainstream hardware
and software.
Upgrading the WAN to high speed capabilities • Protocol independence.
such as Ethernet speeds - RTU architectures nor • Distributed computing and communication
mally communicating with SCADA master stations at hub for simplified integration of distribution
1200 baud will not be compatible with the high automation (DA).
speed data transfer and synchronizing required by
modern WANs.
4.4.5.2 Operation Benefits
New or replacement RTU, annunciaters,
• Uniform HMI for data access.
sequence of events recorder, fault recorder, or
electromechanical relays -the integrated SA plat • lnteroperability of IEDs.
form will include the functions of all these dedicated • Integrated alarm log and sequence of
devices plus an order of magnitude of additional events reporting.
func tions and all at a significantly reduced price. • Custom display and reporting capability
from integrated database.
• Automatic logging of HMI accesses
4.4.5 Benefits of substation automation
and operating activities.
integration
• Programmed logic for automatic reconfiguration
Integrated substation automation systems provide of busses and/or feeders.
improved benefits in the functionality, design, opera • Network (peer to peer) messaging between
tion, maintenance and reliability of the substation substation server nodes and other WAN nodes.
operating environment. The architectures of most
substation automation solutions vary significantly and 4.4.5.3 Maintenance Benefits
include smart systems, black box proprietary solu
tions, and open WAN/LAN solutions using off-the • Data for relaying, metering and
shelf commodities from the PC and PLC marketplace. communication service is available locally or
The following lists categorize and summarize the remotely.
potential benefits available from a well integrated • Each lED can be directly accessed (locally
substation automation architecture using PC HMI, from the PC HMI or remotely via modem)
subLAN, lED relays, and remote modem access. from
easy to use HMI for configuration, setting and
diagnostic reporting.
• Predictive maintenance is possible frorn automatic
analysis of equipment operating history.
• Supervision and management of transformer,
load tap changer, and circuit breaker internal
operations
• Uniformity and consistency in HMI operation • Reduced costs for new construction.
procedures reduces the chances for operating
• Reduction of unnecessary trips to read alarms,
errors.
relay targets, and station logs.
• Integrated and sequenced databases
• Readily accessible relay operation information,
provide accurate information for problem
fault location data and alarm log for
analysis and maintenance.
operators will help reduce line patrolling and
• Monitoring of all station equipment ensures that problem investigation time, and thus outage i :,
failed equipment is detected and repaired before time.
called upon for service during system disturbances. • Reduced training costs because of uniform
• Reduced customer outage minutes resulting in database, HMI. customized screen format tailored
improved reliability indices. for ease of use.
• Reduced chances for operator switching errors. • Integrated database information, comprehensive
• Quick isolation of faults and restoration of service problem reporting and a future expert system
to unfaulted feeder sections. can greatly facilitate of maintenance and repair
activities, thus reducing costs.
• Maintenance scheduling can be streamlined
and optimized for a cost effective and efficient
program, by using the ad documentation.
• Distributed computing hub to manage the
substation and connected feeder environment.
• Shared access to the enterprise WAN by SA
and DA devices.
4.5 Reference
Ryan Bird · Justifying Substation Automation, Black & Veatch, http//tasnet.com/justa.shtml
42
5 Primary Equipment in Substations
5.1 Introduction 45
5.1.1 Condition Monitoring 45
5.2 Switchgear installations 46
5.2.1 Classification of switchgear installations 47 5
5.3 Single line diagram and busbar configuration 47 Table of
5.3.1 Definition of Switchgear 48 content
5.3.2 Common circuit configurations 49
5.3.3 Special configurations, mainly outside Europe 51
5.3.4 Configurations for load-center substations 52
5.4 Substation Structure 53
5.4.1 Circuit Breaker Bays/Feeders 53
5.4.2 Bus coupler bays 54
5.4.3 Connections of Instrument Transformers 54
5.5 Switching Equipment 55
5.5.1 Circuit Breakers 55
5.5.1.1 Circuit Breaker tripping operation 55
5.5.1.2 Requirements for control of circuit breakers 57
5.5.1.2.1 Phase-discrepancy monitoring 57
5.5.1.2.2 Anti-pumping control 57
5.5.1.2.3 Non-stop motor operation 57
5.5.1.2.4 SF6 gas monitoring 57
5.5.1.2.5 Local/remote control 57
5.5.1.2.6 Energy monitoring 57
5.5.1.2.7 Autoreclosure 57
5.5.1.2.8 Synchronized switching 58
5.5.1.3 Definitions 59
5.5.1.3.1 Auxiliary switches 59
5.5.1.3.2 Opening time 59
5.5.1.3.3 Total break time 59
5.5.1.3.4 Arcing time 59
5.5.1.3.5 Closing time 59
5.5.1.3.6 Operating cycle of circuit breakers 59
5.5.1.3.7 Monitoring of circuit breakers 59
5.5.1.3.8 Rapid or auto-reclosure 60
5.5.1.4 Critical CB parts to monitor 60
5.5.2 Disconnectors and Earthing Switches 61
5.5.3 Switch disconnectors -61
5.5.4 Instrument transformers 61
5.5.4.1 Definitions and electrical quantities 62
5.5.4.2 Current transformers 62
5.5.4.2.1 Definitions for current transformers 62
5.5.4.2.2 Selection of current transformers 64
5.5.4.3 Voltage transformers 65
5.5.4.3.1 Definitions for voltage transformers 65 43
. '?
5.5.4.3.2 Inductive voltage transformers 66
5.5.4.3.3 Capacitive voltage transformers 67
5.5.4.4 Non-conventional transformers 68
5.5.4.4.1 Active non-conventional transformers 68
5.5.4.4.2 Passive non-conventional transformers 69
5.5.4.43 Cable connection to protection devices 69
5 5.5.4.4.4 Serial connection to protection devices 70
Table of 5.5.5 Innovative HV switchgear technology 70
content 5.5.5.1 Modern design concepts 70
5.5.5.1.1 Process electronics (sensor technology, PISA) 71
5.5.5.2 Innovative solutions 71
5.5.5.2.1 Compact outdoor switchgear installations 71
5.5.5.2.2 Hybrid switchgear installations 73
5.5.6 SF6 gas-insulated switchgear (GIS) 73
5.5.6.1 General 73
5.5.6.2 SF6 gas as insulating and arc-quenching medium 74
5.5.6.3 Gas Density Monitoring 75
5.5.6.4 Components 76
5.5.6.5 SMART-GIS 77
5.5.7 Surge arrestors 78
5.5.71 Design, operating principle 78
5.5.72 Application and selection of MO surge arresters 79
5.5.8 Transformers 81
5.5.8.1 Transformer connections 82
5.6 Voltage and Power Factor Control 82
5.6.1 Transformer control and voltage regulation 82
5.6.1.1 Change over switches 82
5.6.1.2 On-load tap changer (OLTC) 82
5.6.1.3 OLTC control 83
5.6.1.3.1 Local control 83
5.6.1.3.2 Station and remote control 83
5.6.1.3.3 Automatic control 84
5.6.2 Power capacitors 84
5.6.2.1 Compensation of reactive power 84
5.6.3 High voltage reactors 85
5.6.3.1 Current limiting reactors 85
5.6.3.1.1 Voltage drop and voltage variation 85
5.6.3.1.2 Reactor circuits 86
5.6.3.2 Shunt reactors 87
5.6.4 FACTS 88
5.7 Static Var (reactive power) compensation (SVC) ·- 90
5.71 Applications 90
5.72 Types of compensation 90
5.72.1 Thyristor controlled reactor (TCR) 90
5.72.2 Thyristor switched capacitors (TSG) 90
5.72.3 Thyristor switched capacitors/thyristor controlled reactor (TSC/TCR) 91
44 5.8 References 92
5 Primary Equipment in Substations
The idea to include this chapter in this book is to pro Utilities can save themselves time and money by
vide background knowledge about the primary pro employing a step-by-step condition-based, rather a
cess in terms of switchgear installations, various purely time-based, maintenance strategy for the pri
single line diagrams, switching equipment, and mary and secondary equipment.
modern fle xible AC transmission systems (FAGS)
to readers who have their professional expertise Generally, time-based or usage-based maintenance is
mainly in IT applications or in secondary equipment a suitable strategy if degradation is gradual and pre
for control, protection and monitoring. The dictable. However, curative maintenance is also requir
descriptions of the main primary equipment that is ed as numerous defects cannot otherwise be pre
located in distribution and transmission substation, i.e. vented or detected. In the case of sorne parts, the
possibility of failure is constant, even if there are very
• Circuit
few signs of aging. However, in the longer term,
breakers
there will always be some kind of degradation
• Disconnectors and earthing switches process involved. For example, in the case of static
• Switch disconnectors parts, such a process rnay take 50 years or more.
• Instrument transformers However, if maintenance is only performed when
necessary, based on the condition of the component
• Innovative switchgear technologies
(condition based maintenance, or CBM), overall
• SF6 gas insulated switchgear (GIS) savings on maintenance tasks can be achieved.
• Surge arrestors Indeed, field experience has shown that savings of
• Transformers 20-30% are possible.
are detailed enough that the interaction between The condition of a component is estimated through
substation control, protection and monitoring can be inspections, diagnostic tests, monitoring systems and
explained. In addition to this, the attention is drawn to (partly) dismantling one or more samples. When app
those critical parts of the primary equipment, which lying CBM, there rnust be at least one condition indi
are subject to aging and wear. cator and proven expertise in the assessment of de
gradation. The key issue is to detect degradation
The descriptions of FAGS applications is included before failure occurs and apply an 'expert-rule' to
because they are mentioned in Chapter 11 'Wide area define what will happen next and when.
protection" as counter measures to maintain power
system integrity in case of the occurrence of multi
Condition monitoring includes acquisition, recording,
contingencies.
processing and visualizing measured quantities to
allow early detection of faults in important equipment
such as circuit-breakers, power transformers or instru
ment transformers. According to international surveys
conducted by CIGRE,the operating mechanisms and
the electrical control circuits in circuit-breakers are the
primary source of serious faults, i.e. failures causing
operational disruptions. The most common sources 45
.' .ll
of failure are the mechanically actuated parts such as 5.2 Switchgear ·--;--.
installations
electro-mechanical relays and signaling contacts in
the electrical control circuits and in , ..
'
operating mecha- nisms for the primary '
equipment
low-voltage switchgear and a variety of auxiliary ser- • Extra high voltage (EHV): 300 - 765 kV
vices. These must additionally be accounted for in the • Ultra high voltage (UHV): greater than 765 kV
station layout.
• Direct current systems can be classified as
' '
I Depending on the intended plant site, the construe- follows:
tion of a switchgear installation must conform to IEC • Low voltage (24 - 250 V): Auxiliary power
requirements, ANSI Standards or particular national in power plants and substations, control
codes. circuits and, occasionally, utilization power
in some industrial plants.
The starting point for planning a switchgear installa- • Medium voltage (300 - 600V):
tion is its single-line diagram. This indicates the
extent
Transportation industry
of the installation, such as the number of busbars and
branches, as well as their associated apparatus. The • High voltage (greater than 600V):
most common circuit configurations of high and Long distance bulk transmission, submarine,
medium-voltage switchgear installations are shown and major system interconnections.
in the form of single-line diagrams in chapter 5.3.
r
Symbol Designation Features !
,..,- Disconnector Mechanical switching device, providing an isolating distance in the open position.
It is capable to open or close a circuit if either a negligible current is switched or
if there is no significant change in voltage between the terminals of the poles.
,..,_ Circuit Breaker Mechanical switching devices are able to make, carry and interrupt currents under
normal conditions in the network and carry and close onto currents under speci-
fied abnormal conditions in the network, e.g. in the case of short circuits.
Draw-out Mechanical switching devices as above but withdrawable to provide in the open
Circuit Breaker position an isolating distance with the affect that separate disconnectors
are not necessary.
Link Mechanical link to outgoing or incoming overhead lines or cables (line feeder)
and transformers, reactors respectively (transformer, reactor feeder).
Earthing Mechanical switching devices for earthing and short circuiting circuits. They are
,..,--11• switch capable of carrying currents for a specified time under abnormal conditions,
e.g. short circuits.
-e- Current
transformers
The primary winding is incorporated in the HV line and carries the current flowing
in the network It has various secondary cores for protec,.on and metering with
a rated output of 5 to 60 VA depending on the rated burden at 1 or 5 A.
Inductive Inductive voltage transformers are transformers of low output with which the
voltage voltage is proportional to and in phase with the primary voltage. They are used to
transformer transform the HV to be measured to a secondary voltage to be fed to measuring
and protection devices, e.g. primary rated voltage 110 000 h/3 V, secondary
voltage 110h/3 V.
@
Power The purpose of power transformers is to transfer electrical energX from systems
transformers with one voltage U1 to systems of another voltage U2. I
L .•
48
•II• 1111 Surge arrester Surge arresters are used for protection of important equipment against over-
voltage particularly transformers, from atmospheric overvoltages due to lightning
and switching over-voltages.
5.3.2 Common circuit configurations I II I
5.3.2
--.----.----" ---r-----r--
1 I I I
I
_......_ _......_ _......_
0
1
5.3.2
BPB
Double busbars with draw-out circuit-breaker Double busbars with bypass busbar (US)
In medium-voltage stations, draw-out circuit-breakers The bypass busbar is an additional busbar connected
reduce downtime when servicing the switchgear; also via the bypass branch. Advantage: each branch of the
a feeder disconnector is not necessary. installation can be isolated for maintenance without
interrupting supply, with the bus coupler acting as line
circuit breaker.
1:
)
Two-breaker method with draw-out circuit
I,
Triple (multiple) busbars
breakers
For vital installations feeding electrically separate net
Draw-out circuit-breakers allow to built very econo works or if rapid sectionalizing is required in the event
mical medium-voltage stations. There is no need for
busbar or feeder isolators and a bus coupler. For
of a fault to limit the short-circuit power. This layout is
frequently provided with a bypass bus.
I:
sta tion operation, the draw-out breaker can be
50
inserted
in a cubicle for either bus I or bus II. I,
'i
. -
"-":r "--L "--
c
5.3.3
11/2-breaker method
YYY)
I Fewer circuit-breakers are needed for the same flexi bility
as above. Isolation without interruption. All brea kers are
normally closed. Uninterrupted supply thus maintained
even if one busbar fails. The branches can be through-
connected by means of linking breaker C.
Cross-tie method
With cross-tie disconnector "DT'; the power of line A can be
switched to branch A,, bypassing the busbar. The busbars
are then accessible for maintenance.
Ring busbars
Two-breaker method with fixed switchgear
Each branch requires only one circuit-breaker, and yet each
Circuit-breaker, branch disconnector and instrument breaker can be isolated without interrupting the power
transformers are duplicated in each branch. Busbar supply in the outgoing feeders. The ring bus bar layout is
interchange and isolation of one bus is possible, one often used as the first stage of 1 lf2-brea
branch breaker can be taken out for at any time ker configurations. 51
without interrupting operation.
A
B
Double-feed station
A B
i
c
,....-------, -----------d ,r ,
!
'i
i
Single-feed station i
Switch-disconnectois are frequently used in load-center substations for the feeders to cables or
transformers. Their use is determined by the operating conditions and economic considerations.
......., r+
_[ j j
1 ' l_
I
r
with circuit-breakers with switch-disconnectors three transformers
.,
u
5.4
BB I BB I BB I Q 15
:::::=c:=
BBI
BBliJ==r= BB II BB II
Q1li Q2
BBIIrr
Q25 I I
Q1 v ....._,,.
.· .
Q5
QOI Q 0 Q 5
r....._," II
Q 9\_ Q 8 Q9
SA
T
\ Q8
00: Circuit breaker, 07, 02: Busbar disconnectors, Stationary unit earthing switches are used in SF6 gas
05, 08, 075, 025: Earthing switch, SA: Surge Arrester, T: insulated switchgear (GIS) to provide temporary earth ing to
Transformer, G: Generator, GB: Generator breaker (desig_n avoid danger in case of maintenance.
tio_n, numbers according to DIN).
Transformer bay: Feeder disconnectors are usually not provided
because the transformer is disconnected at both high
Line and cable bay: The earthing switch 08 eliminates voltage and low voltage sides. The earth ing switch 08 is
capacitive charges and provides protection against recommended for maintenance
atmospheric charges on overhead lines. work 53
. ·.:
5.4.3 , 5.4.2 Bus coupler bays requirements concerning security of supply and the
necessary flexibility when switching over or dis
connecting.
In the configurations in chapter 5.4.1, the tie-breaker
branches are shown in a simple form. Experience Division into two bays is generally required in order to
shows, however, that more complex coupling arrange accommodate the equipment for the breaker bran r
\
ments are usually needed in order to meet practical ches.
B BIIrr ::,r=::::cJ
BI
TTQ21J
Q1 Q2Q1\,)Q2
BB I
BB II =r:=:::::c::
TG I
Q 11
_I
Q 1\ Q2
I
Q1 lQ 2Q Q2
aoJ QO
Q
=n=
Q1 Q2
881
88 II
The instrument transfor
mers are usually placed
beyond the circuit-breaker
QO, with voltage transfor
mer TS after current trans
If the instrument transformers cease to function
when the bypass is in operation line protection of the
branch must be provided by the instrument transfor
mers and protection relays of the bypass. This is pos
sible only if the ratios of all instrument transformers in
;·
former T1. This is the cor all bays are approximately equal. The protection
red arrangement for syn relays of the bypass must also be set for the appro
00 chronizing purposes. Some priate values. Maintenance d the bay instrument
T1
T5 kinds of operation require transformers is easier and can be done during bypass
09\08 the voltage transformer operation. If capacitive voltage transformers are used
beyond the bay dis which also ad as coupling capacitors for a high
•'-I•• connectors, direct on the frequency telephone link, this link is similarly inopera
54 cable or overhead line. tive in the bypass mode.
5.5 Switching Equipment
5.5.1 Circuit Breakers Specially designed breakers are used for specific 5.5
duties such as railways, where they have to ex
High-voltage circuit-breakers are mechanical switch tinguish longer-burning arcs (longer half-wave) in
ing devices capable of making, carrying continuously 16 2/3-Hz networks. Breakers used with smelting fur
and breaking electrical currents, both under normal naces frequently operate with reduced actuating
circuit conditions and, for a limited period, abnormal force and lower breaking capacity. This leads to less
circuit conditions, such as in the event of a short wear in spite of the high switching frequency and to
cir cuit. Circuit-breakers are used for switching long seNice inteNals.
overhead lines, cable feeders, transformers, reactor
coils and capacitors. They are also used in bus ties
and in instal lations with multiple busbars to allow 5.5. 7. 7 Circuit Breaker tripping
power to be transmitted from one busbar to operation
another.
Circuit breakers (CB) use the energy of an electric arc
for short circuit current interruption as explained in
Figure 5-4:
Figure 5-3 420 kV Circuit breaker with current trans The decision whether the current can be interrupted
formers (ABB) in air insulated substation (AIS) or not is made at the critical contact position (3). If the 55
·
distance between the contact opening is not big
enough at current zero then the current is interrupted t,
at the next current zero point after another 20 ms.
This means that the arcing time can vary between
approx. 15 and 35 ms depending on the contact
separation in relation the proximity to the next current
5.5.1.1 zero point
==============
Figure 5-5 Short circuit current interruption
5.5.1.2.8 Synchronized
switching
interruption
Target for contact
Circuit breakers operation in high voltage networks separation
can be sometimes the source of undesirable transient
overvoltage and overcurrents. This is particularly true separation
for reactive load switching, e.g. shunt reactors, shunt
capacitors, unloaded power transformers and un
loaded transmission lines. High switching transients
can either exceed the maximum permissible values Figure 5-6 Synchronized switching with shunt reactors
causing the protection devices to respond or
endan ger the long term endurance of the HV The interruption of shunt reactor current, which is
switching equipment in the network. very small compared to rated interrupting current of
the CB, normally leads to current chopping before
The traditional measures to limit the switching over current zero. This develops high overvoltages in the
voltages and overcurrents has been the application of shunt reactor. These may exceed the voltage with
surge arresters to protect transformers against over stand characteristic and cause re-ignitions of the cir
voltages as well as closing and opening resistors, cuit breaker and produce steep transient recovery
which were associated with the circuit breakers to voltages. Such transients cause aging of the reactor
switch no-load lines, no-load transformers and capa winding insulation. If the tripping impulse is synchro
citor banks.
nized such that the CB contacts separate within the
arcing time window and the current is interrupted
Synchronized switching of circuit-breakers, in which
exactly at current zero (+/-some ms tolerance) such
every breaker pole is synchronously actuated by a
voltage transients are avoided.
suitable control unit at the instantaneous value of the
58 current or the phase-to-earth voltage, are becoming
. ·
5.5.1.3.6 Operating cycle of circuit breakers
u
!!
c: 5.5.3 Switch disconnedors
3
.:;;c: ..
High-voltage switch disconnectors are switching
T1! T2 Time(ms) devices that make, carry and break operating
currents
-f---- f-----i-....Au:£ili<OQU: ctA and also carry and in part also make short-circuit cur
Auxiliary contact B rents. In their isolating open position, they also form
an isolating distance.
Closing coil current
These devices are used as follows:
• Transformer switches for smaller power supplies in
the distribution network for switching magnetizing
Auxiliary contact B, early close
currents and commutation currents (e.g. 100 A at
CB closing time ! up to 2.5 kV voltage difference) when changing
transformers or the power supply,
Figure 5-7 Circuit breaker mechanical
performance monitoring
• Line switches at one end of an overhead
line
• Busbar section switches
5.5.2 Disconnedors and Earthing Switches
• Switches for short cable length Oc <
Disconnectors are used for galvanic isolation of net 3A).
works or sections of switchgear installations. As an
independent air-insulated device, they form a visible
isolating distance in their open position. They are sui 5.5.4 Instrument transformers
table for switching small currents (<0.5 A) distance or
Instrument transformers are used to transform high
also larger currents, if the voltage does not change
voltages and currents to values that can be unified or
significantly between the contacts of a disconnector
measured safely with low internal losses. With induc
pole during switching (commutation currents).
tive current transformer (CT) the primary winding car
During opening, disconnectors generate a lot of low ries the load current while with voltage
energy discharges between the contacts that open transformers (VT), the primary winding is connected
to the service voltage. The voltage or the current of
the secondary
winding is identical to the value on the primary 61
5.5.4.2 Current transformers
5.5.4.1 Definitions and electrical quantities • Primary rated current: the value of the
A distinction is made between CT cores for primary current that identifies the current
transformer and for which it is rated.
measure ment purposes that are used to conned
instruments, meters and similar devices and
transformers for pro tection needs for connection of • Secondary rated current: the value of the
protection devices. secondary current that identifies the current trans
. former and for which it is rated.
Instrument transformers are classified according to
their measurement precision and identified accor
dingly. They are used as shown in the tabJe below:
• Rated burden: the value of the burden on The positive signs of the primary and secondary cur 5.5.4.2.1
which the accuracy requirements of this standard rent must be specified in accordance with the
are based. · agree ment on connection labels.
• Rated output: the value of the apparent power The composite error in general is expressed as a per
(in volt amperes at a specified power factor), centage of the rms values of the primary current as
which the current transformer yields at secor>dary given by the following equation:
rated current and rated burden.
&c=-
100 HT-f( 2
Knls-Ip) dt
• Current error (transformation ratio error): the Here: lp T 0
ring ·a current intensity and derived from the Kn: Rated transformation ratio of the current
devia tion of the actual transformation from the transformer ·
rated transformation. The current error is given by IP : Rms value of the primary current
the equation below and expressed as a IP : Instantaneous value of the primary current
percentage. I, : Instantaneous value of the secondary current
T : Duration of fundamental period
• Phase displacement: the angular difference Note: the composite error should exceed 1 0 %
between the primary and secondary current to protect the device fed from the current trans
vectors. The direction of the meter is specified so former against the high current values occurring
that on an ideal current transformer the phase if there is a fault in the network.
displacement is equal to zero. The phase displace
ment is considered positive when the secondary • Overcurrent limit factor (FS): the ratio of the
current meter is ahead of the primary current rated limiting current to the primary rated current.
meter. It is usually expressed in minutes or in
Note: if a short-circuit current flows through the
centiradians.
primary winding of the current transformer, the
Note: the definition is strictly speaking only load on the instruments connected to the current
applicable to sinusoidal currents. transformer is smaller in proportion to smallness
of the overcurrent limit factor.
• Composite error: in its stationary state, the
composite error Ec based on the rms value of • Rated accuracy limit current: the value of the
the primary current is the difference between the primary current up to which the current trans
instantaneous values of the primary current the former for protection needs meets the require
instantaneous values of the secondary current ments for the composite error.
multiplied by the rated transformation. 63
I,
• Accuracy limit factor: the ratio of the The transformer output at 16.7 Hz must be multiplied
primary rated accuracy limit current to the with the factor 0.33 and at 60 Hz with 1.2.
primary rated current.
When selecting the current transformers, not only the
output but also the overcurrent limit factor of the
• Thermal rated continuous current: unless
transformer must be considered. The overcurrent limit
otherwise specified, the thermal rated continuous
5.5.42.2 factor is given on the nameplate.
current is equal to the primary rated current.
In the case of measuring and metering cores, the
• Current transformer with extended current overcurrent limit factor should be as small as possible,
measuring range: the thermal rated continuous e.g. 5 or 10 to protect the connected instrumentation
current must be equal to the extended primary against excessive overcurrents or short-circuit currents.
rated current. Standard values: 120 %, 150 % and Because the overcurrent limit factor only applies for
200%. the rated burden but actually rises with a smaller bur I.
den or smaller transformer load in approximately an I
• Rated short-time thermal current: the rated inverse ratio, the operating burden of the connected !
short-time thermal current (1s) must be given for instrumentation including the required connection
every current transformer. lines must be equal to the rated burden of the
trans former so far as possible to protect the
Note: if a current transformer is a component of
measuring mechanisms from destruction. Otherwise,
another device (e.g. switchgear installation), a time
the second ary circuit should include an additional
difference from one second may be given.
burden.
• Rated peak short-circuit current: the value of Protective cores for connection of protection relays, in
the rated peak short-circuit current (ldyn) must in contrast to the measuring cores, must be selected so
general be 2.5 lth· Only in the event of deviation that their total error is not too large even if short-
from this value must ldyn be given on the name cir cuit currents remain in the range in which the
plate. protec tion relays should function accurately
according to their settings, e.g. 6 to 8 times rated
current. There fore, the protective core must be
5.5.4.2.2 Selection of current transformers
designed so the product of the rated output and
the overcurrent limit factor is at least equal to the
The choice of a current transformer is based on the product of the power requirement of the secondary
values of the primary and secondary rated current, transformer circuit at rated current and with the
the rated output of the transformer cores at a given required overcurrent iimit factor. This is particularly
accuracy class rating and the overcurrent limit factor. important if a large primary conductor cross-section
The overcurrent limit factor must be adjusted to the is required to meet the ther mal short-circuit
load current of the consumer. stresses. In such a case, a current transformer for
higher rated current should be select ed, where the
Rated output and rated burden of current transfor primary winding number and also the output will be
mers (at 50 Hz). lower because the load current is less than the rated
current. or a special transformer can be used.
Rated output in VA 5 10 15 30 60
Rated burden at 5 A in Q 0.2 0.4 0.6 1.2 2.4
Rated burden at 1 A in Q 5 10 15 30 80
64
5.5.4.3 Voltage transformers
. '?
Example:
• Rated voltage factor: the multiple of the Inductive voltage transformers are supplied in the fol
,. primary rated voltage at which a voltage
transfor
lowing designs: \'
mer must respond to the thermal requirements
for a specified load duration accuracy class.
• Two-phase isolated voltage transformers
• Voltage error (transformation ratio error): for connection between two phases, ratio
the deviation of a voltage transformer when mea 60001100 V, for example. Two voltage trans
suring a voltage resulting from the deviation of formers in V connection are normally used for I
the actual transformation from the transformation. measuring power in three-phase networks.
The voltage error is given by the equation below
and expressed as a percentage. • Single-phase isolated voltage transformers for I
connection between one phase and ground, ratio
11 0000 I v3 II 100 I v3 V. Three transformers
connected in star are required for measuring
I
power in three-phase networks. If single-phase
Here: isolated voltage transformers have an auxiliary
Kn : rated trar.sfo mation ratio winding for ground-fault monitoring, in three
UP :actual primary voltage phase networks, this must be measured for the I
Us : actual secondary voltage when UP is subject ratio of 1OOV3 V. The "open delta" in the three
to measuring conditions. phase set can also have a fixed resistance for
damping relaxation oscillations (resulting from
ferro-resonances in insulated networks with small
• Phase displacement: the angular difference
capacitances).
between the primary and secondary voltage
vectors. The direction of the vector is specified
so that on an ideal voltage the phase displace • Three-phase voltage transformers with the
ment is equal to zero. The phase displacement is measuring windings connected in star"and an
positive when the secondary vector is ahead of auxiliary winding on the 4th and 5th limb for
the primary vector. It is expressed in minutes or ground-fault detection. The auxiliary winding has
in centiradians. a voltage 100 V in the event of a ground fault.
:
3 Transformer
4 Secondary terminals
_L Cn 5 Terminal box trimming winding
-r
6 Carrier HF terminal
6 '- r- 7 Carrier HF coupling
8 Damping device
YYYtYYYYt Y
2
3
100%
( 811 4
810 .
89 0 0
88 5
%
J
4
1 %
3 1
5
87 0
5 -< 86
85 0
o.45% 1
B4
1 o
II
.
1
5
%
83 0 o.o5% 8
0
1 _d
82
, L
.,. 7 ' 81 t
0
Filter:
When selecting capacitive voltage transformers, pri Non-conventional transformers consist of a measure
mary and secondary rated voltage, rated frequency, ment recorder, a measured value transmission line
rated output and class are the essential features. In bridging the potential difference between high volt
addition, the rated thermal limiting output of a age and ground potential and an electronic
ground fault detector winding, rated voltage factor interface at ground potential for measured-value
and the specified load duration at increased voltage processing and connections to protection devices in
must be considered. the station con trol system.
Capacitive voltage transformers are selected similarly Measurement recorders can be divided into active
to the inductive transformers, but the capacitances of
and passive systems depending on the method
the high-voltage capacitors (C 1), of the intermediate
used.
voltage capacitor (C2 ) and the rated capacity (Cn) must
also be given. A dimensioning example for a capaci
tive voltage transformer is shown below:
5.5.4.4.1 Active non-conventional
Primary rated voltage 110 OOON3 V transformers
Secondary rated voltage
Hall-effect elements, Rogowski coils without an iron
• for measurements 110N3V
core or specially designed bar-type current transfor
• of winding for mers with linear characteristics are used for current
ground detection. Voltage acquisition is generally done using
fault detection 100/3 v resistive or capacitive voltage dividers. In substation
Rated output 75 VA, Cl 0.5 technologies for rated voltages below 52 kV and also
Rated voltage factor 1.9 U0, 4 h for GIS installations for higher voltages,active non-con
ventional transformers offer very attractive solutions.
Thermal rated burden rating 120 VA. 8 h
Rated capacity 4.400 pF ± 1 0 However, in outdoor substation technology for trans
% Rated frequency 50 Hz mission networks, the electrical measured quantities
must still be converted to a digital or analogue opti
The properties with transient processes are also cal signal at high-voltage potential. This requires devic
important with capacitive transformers (interaction es for providing the required auxiliary energy at high
with network protection). SF 6-insulated switchgear voltage potential. This energy requirement-may either
installations also include inductive and capacitive vol be taken from the high-voltage that is being monitor
tage transformers. ed or by optical means, either by solar cells or by
energy transmission via fibre-optic lines.
68
5.5.4.4.2 Passive non-conventional
transformers
From technical considerations, the best solution is a 5.5.5. 7 Modern design concepts
direct digital/digital fiber optic process bus connection
rather than low-level and non-electric signals that The application of processors and modern informa
might have to be amplified to conventional values tion processing technology in substation and net
like 1 A or 100 V thus requiring expensive amplifiers work control systems and also in secondary systems
and loosing information like bandwith by principle of switchgear installations, fast data bus systems that
(Figure 5-9). The main obstacle for the acceptance of transmit over fiber-optic cables instead of copper
such a solution has been that this link could only be wires and newly developed sensors for current and
a vendor specific proprietary solution because of the voltage enable revolutionary designs that lead to
lack of International Standards that assure the inter smaller and more compact installations with a simul I! .
operatibility between IEDs from various vendors as taneous increase in availability and ease of mainte
well as sensors/actuators from various vendors. This nance in the area of high- and very high-voltage
problem has been addressed by the new IEC 61850 equipment and switchgear installations.
standard.
Electro
mechanical
protection
IEC60044-1, IEC60186 Electro
static
·: ........ protection
lA I
I
'
' IEC60044-7
Voltage Numerical
-
IEC60044-8
amplifier , protection
& control
Numerical
control
Decentralized distributed microprocessor based Another possibility for reducing the space required
modules (PISA = J:rocess lnterface for 2ensors and for outdoor installations significantly is to use hybrid
duators) can be used for direct control of the pri installation designs. In this case, gas-insulated switch
mary components of switchgear installations. At the gear is used in which many primary components (cir 5.5.5.2
same time, these modules enable all parameters, cuit-breakers, transformers, discor'1nectors etc) are
such as switch position, gas density, storage pro installed in a common gas insulated housing. Only the
perties of operating mechanisms, to be recorded busbars and, depending on the basic design, the
where they signify current status of the equipment associated busbar disconnedors are installed out
and therefore provide the necessary prerequisites for doors.
monitoring modern switchgear installations.
All new switchgear components are distinguished by
Examples of equipment used for this purpose are consistent integration of non-conventional sensors (in
inductive robust proximity sensors for detecting this case primarily current and voltage sensors), pro
contact position of circuit breakers and disconnectors, cessor controlled mechanisms and connection to the
gas density sensors for SF6 gas-insulated switchgear bay control with fiber optics. This yields the
(GIS) installations and circuit-breakers. Powerful micro following:
computers are used for the preparation and • increased
prepro cessing of the sensor signals. Complex availability
auxiliary switch packets in operating mechanisms are • less space
no longer need ed because the software can multiply required
signals without problems. The main advantages of
• shorter project runtimes and
this technology are therefore the ability to reduce
the quantity of moving components, the smaller • extended maintenance intervals with a significant
dimensioning and standardization of mass-produced increase in ease of maintenance.
components as is already done other industries.
Figure 5-7 0 Slide-in switching module with LTB Circuit
For the transmission of sensor data fiber optical breaker (CB) and integrated SF6 current
cables are used and for the communication the transformer (CT), disconnector (Of), earthing
trahs msslon protocol according to the Standard earthing switch (ES) and surge arrestor
(SA) for145kV
IEC
61850.
Figure 5-7 7
Compact switching module for 170 kV with draw-out
circuit breakers (CB), disconnector (Of) and current
transformer (CT)
I
I
·..·
.,
Figure 5-72 .......1
72 Plug And Switch System PASS
I I
I I l:.
I I
·•
5.5.5.2.2 Hybrid switchgear installations The saving of space amounts to as much as 60 % in 5.5.6
new installations. For retrofit projects, the space
Two insulation media, i.e. air and SF 6 , can be
requir ed by the switchgear installations is generally
combin ed in high-voltage installation with the
dictated by the existing busbars and the gantries. In
modular prin ciple of SF6 -isolated installations. This
this case, the advantages of the PASS solutions are
type of installa tion is referred to a "hybrid
primarily in the drastically reduced cabling
installation':
requirements and fast installation and
commissioning.
Figure 5-12 shows a hybrid switching device for vol
tage levels of up to 550 kV. The name "Plug And
Switch System" - PASS - indicates the philosophy of The 11/2 circuit-breaker method can also be success
this concept. The highly integrated components form fully implemented in hybrid design ( Figure 5-13). In
a complete bay comprising SF6 gas-insulated circuit addition to saving up to 60% in surface area requir
ed, PASS is also characterized by easy replacability. It
breaker, busbar disconnectors (2 disconnectors in ca
can be connected to the overhead lines as easy as
se of a double busbar arrangement), maintenance
conventional installations.
earthing switch, current and voltage transformers.
This modular pre-tested switching units allow that in
new installations and in retrofit projects compact bay
units can be erected and commissioned very quickly.
They are connected to secondary equipment of the 5.5.6 SF6 gas-insulated switchgear (GIS)
substation by prefabricated cable links, which include
both the auxiliary voltage supply cables and the fiber
optic cables to the station automation system. 5.5. 6. 7 General
'· - - .
Transformer
Disconnector I
j
, ..
1
Earthing Switch : \
10
Figure 5-75
Pressure/Temperature
diagram of pure SF6 Gas
- 60 - 40 - 20 0 20 Temperature
40 60 75
[ T I 0C]
Figure 5-76 SF6 Gas Schematic Diagram
l ··,
Reference is made to the typical layout of a GIS sta The current transformers for measuring and protec
tion in Figure 5-14 and gas schematic diagram Figure tion purposes are of the toroidal core type and can
5-16. be arranged before or after the circuit-breaker. depen
ding on the protection concept. Primary insulation is
The busbars are separated by barrier insulators at provided by SF,: gas, so it is resistant to aging: Iron
each bay and form a unit with the busbar disconnec free current transformers using the Rogowski coil
tors and the maintenance earthing switches. principle are used with SMART-GIS. They allow quan
titative evaluation of short-circuit currents and so
The circuit-breaker operates on the self-blast princi make it possible to create a contact erosion image of
ple. Conventional puffer-type breakers use the the circuit-breaker. Also fibre optic CTs could be used
mechanical energy of the actuator to generate the as an alternative, if available.
breaker gas stream while the self-blast breaker uses
Voltage transformers for measurement and protec The surge arresters are generally of the gap-less type 5.5.6.5
tion can be equipped on the measuring windings and contain metal oxide resistors. If the installation is
and an open delta winding for detecting earth faults.. bigger than the protected zone of the line-side arre
ster, arresters can also be arranged inside the installa
Inductive voltage transformers are contained in a tion. It is generally advisable to study and optimize the
housing filled with SF6 gas. Foil-insulated voltage trans overvoltage protection system, particularly with dis
formers are used, with SF6 as the main insulation. tances of more than 50 m.
Capacitive voltage transformers can also be employ Each bay has a control cubicle containing all the
ed, usually for voltages above 300 kV. The high vol equip
tage capacitor is oil-insulated and contained in a hous ment needed for control, auxiliary power supply.
ing filled with SF6 gas. The low-voltage capacitors and
the inductive matching devices are placed in a sepa The gastight enclosure of high-grade aluminum is of
rate container on earth potential. Capacitive tapings in low weight so that only light foundations are requi
conjunction with electronic measuring ampli- fiers are red. The enclosure surrounds all the live parts, which
also available. are insulated from the enclosure by SF 6 gas at a
pres sure of 350 to 450 kPa.
Electro-optical voltage transformers using the Pockels Barrier insulators divide the bay into separate gas
principle are also used with SMART GIS. compartments sealed off from each other. This mini
mizes the effects on other components during plant
The cable sealing end (pothead) can extensions, for inspection and maintenance. The flang
accommodate any kind of high voltage cable with ed joints contain non-aging gaskets. Any slight leak
conductor and connection facilities for testing the age of gas can pass only to the outside but not into
insulation of the cables with DC voltage. If there adjacent compartments.
is a branch dis" connector, it is sufficient to open
this during testing.
Each switching device is provided with an easily
accessible operating mechanism (arranged outside
Maintenance earthing switches, which may be requir the enclosure) for manual emergency operation. The
ed during servicing, are usually placed before and contact position can be seen from reliable mechani
after the circuit-breaker. Normally mounted on or cal position indicators.
integrated in the disconnector housing, they are ope
rated by hand or motor only if the high-voltage part
is not under voltage. The maintenance earthing 5.5.6.5 SMART-GIS
switch after the circuit-breaker may be omitted if there
a high-speed earthing switch on the line side. A characteristic of SMART-GIS is replacement of con
ventional secondary technology, such as transformers,
SF6 outdoor bushings allow the enclosed switchgear contactors and auxiliary switches with modern
to be connected to overhead lines or the bar termi sensor technology and actuators. Inductive
nals of transformers. In order to obtain the necessary proximity swit ches and rotary transducers detect the
air clearance at the outdoor terminals, the bushings position of the switching devices; the SF 6 gas
are properly separated using suitably shaped enclo density is calculated
sure sections. from the gas pressure and temperature or measured
directly. 77
.
'
5.5.7 Surge arrestors
5.5.7 Actuators control the trip solenoids and the electric 5.5.71 pesign, operating principle
motors of the mechanisms. Specially designed sen
sors detect current and voltage. Rogowski coils and The operation and design of the surge arrester has
electro-optical voltage transformerswithout ferromag radically changed over the last twenty years.
netic components are generally used for this purpo
se. To ensure secure transmission of signals, fiber Arresters with spark gap and with series-connected
optic cables instead of the conventional hard-wired silicon carbide (SiC) resistors have been replaced by
connections are used within the bay and station con surge arrester technology without spark gap and with
trol system. metal-oxide resistors. The former porcelain housing is
also being replaced more and more by polymer
The process is controlled and monitored by decen insu lation.
tralized distributed microprocessor based modules
(PISA= _Erocess Interface for $ensors and 6ctuators),
which communicate with one another and with
u
higher-order control components via a process bus.
states can be avoided before they affect operation a lower linear part
and maintenance. This results in reduced reserve and b knee point·
redundancy requirements in the system and improv- c strongly linear part
ed economy of operation. · d upper linear part ("turn-up area")
The protective level of the MO arrester .is set by its 5.5.72 Application and 5.5.7.2
re sidual voltage UP. The residual pea'k value of the
vol tage appears at the terminals of the arrester
selection of MO surge
when a surge current flows. A surge current with a arresters
front time of about 1 [.IS, and a time to half value
up to 10 tS and a current up to 10 kA represents Surge arresters are used for protection of important
very steep over voltage waves, and the associated equipment particularly transformers, from atmosphe
residual voltage is comparable to the front spark ric oveNoltages and switching oveNoltages (Fig. 5-18).
over voltage of a spark-gapped arresters. MO arresters primarily selected on the basis of two
basic requirements:
Surge arresters are protective devices that may be
overloaded under extreme fault conditions. In such • The arrester must be designed for
cases, e.g. when voltage leaks from one network stable continuous operation,
level to the other, a single-phase earth fault occurs in • Must provide sufficient protection for the
the resistor assembly of the arrester. The pressure re protected equipment.
lief ensures that the housings do not explode. The
earth-fault current of the at the arrester site must be
less than the guaranteed current for the pressure re
lief of the relevant arrester.
Figure 5-7 8 Typical 7 45 kV transformer (T), bay
with circuit breaker (CB) surge arresters
(SA) and current transformer (U)
79
characteristic and it is decisive for the selection of the
arrester with reference to temporary overvoltages.
During the operating duty test of an MO arrester
type, a test voltage is applied immediately following
the surge current for a period of 1 0 s to the test
object . t
and mechanical requirements are known as precisely mana gement center. .1.
as possible. The magnitude of the maximum power
frequency voltage, magnitude and duration of the u I
I
temporary overvo/tages and the anticipated stresses p.u. .!
caused by switching and lightning overvoltages must 4
all be known. In addition, the stress caused by
short circuit current forces and special environmental
con ditions, e.g. temperatures over 45 °(, 3
installation in earthquake regions etc, are very
important.
2
When selecting the arrester by its electrical data, there
must be an appropriate margin between the
protec tion level of the arrester and the insulation
levels stand ardized for he applicable operating
voltage to meet the requirements of the insulation
coordination (Figure 5 -19).
I
Parallel connecting of MO resistor columns allows
every technically necessary dimension of the energy
absorption capability to be implemented at equivalent
protection levels. Doubling the number of columns a maximum phase to ground voltage at power
can reduce the protection level and almost double frequency in normal operating conditions
the energy-absorption capability. (1 p.u. = peak value)
b peak value of maximum phase to ground voltage
For MO arresters, the continuous operating voltage U, of an adjacent phase in case of a ground fault
is defined as the maximum power frequency voltage cE earth fault factor (=14)
that the arrester can withstand continuously. The peak d Switching impulse voltage (limited by surge
value of the continuous operating voltage of the arrester to UPS)
arre ster must be higher than the peak value of the UPS Switching impulse protection level of surge arrester
ope rating voltage. On one hand, it is determined
UwL Rated lightning impulse voltage (BIL) for equipment
by the power-frequency voltage that corresponds
standard values
to the maximum voltage in the network; but on
the other hand, permissible harmonics of the UwS Rated switching impulse voltage (SIL) for equipment
standard values ·
voltage must be considered In normal networks, a
safety margin of 5% over the system voltage at
power frequency is suffi cient. Figure 5-7 9 Arrester selection for /ow-resistance
earthed transmission network for
The rated voltage U, of an MO arrester is the refe ± 245 kV with earthing factor CE= 1.4
80 rence value to the power frequency versus the time
5.5.8 Transformers
5.5.8
.. 1
S
----.-- Cooling system
A
Figure 5-20 Large power transformer comprising primary/secondary cooling systems and tap changer
with surge arrester (SA) on the primary voltage side U 7
The purpose of transformers is to transfer electrical • Power transformers, the winding of which
energy from systems of one voltage U, to systems of are in parallel with the associated systems. The
another voltage U2 . systems are electrically independent. The transfer
of power solely by induction.
The transfmmers can be differentiated according-to
their manner of operation (Figure 5-21). • Autotransformers, the windings of which are
connected in line (series winding RW and parallel
winding PW). The throughput of power is partly
by conduction and partly by induction. 81
:
5.6 Voltage and Power Factor II
I
i
Control I '
5.6
• Booster transformers, the w!nding of which are
5.6.1 Transformer control and voltage
electrically independent. one winding being regulation
connected in series (RW) with one system in order One of the most important operational requirement
to alter its voltage. The other winding is connected is that the ratios of the power transformers can be
in parallel with its associated system (Excitation adapted according to load variation by means of a
winding 8/11). The additional power is transferred on-load tap changer control (OTPC) (Figure 5-20)
purely inductively.
devices. This transformer control enables
• to maintain the system voltage
within a narrow range
PW • to adjust the real power and reactive
power flow in interconnected networks
RW
EW
and rectifier plants for DC supply
Star A y y
The on load tap changer is used in grids with fre
quent short term load variations. The range of volta
Interconnected star ""( ge adjustment is ± 16 % of the voltage level that
z z
has to be guaranteed. The range is divided in 2
A
times 16
Open steps with 1 % voltage range each. As the adjust
Ill Ill ment of the taps has to be conducted under load,
the tap changer is equipped with a spring drive
82 Table 5-7 Transformer connections
and motor for rewinding the spring after operation.
This type of operation is called step-by-step
switching.
uv
.------------.,
1 I
rate command has to be given. This feature assures Figure 5-22 Transformer tap changer diagram for local,
station and remote control
that not several steps can be changed with one
com mand and that the voltage regulation is made
step by-step.
11 Higher/Lower mechanical
5.6.1.3
rn
drop proportional to the tap changer position can be
measured by an position indication instrument
Tap position indicator, electrical
In addition to the position indication, the voltage
level that has to be guaranteed can be displayed
at sta tion control level.
0 Start indicator
Figure 5-23 Active and reactive currents in an electrical 5.6.3.1.1 Voltage drop and voltage variation
installation, a) uncompensated,
b) compensated with capacitor, The rated impedance is the impedance per phase at
c) power vector diagram rated frequency. The resistance of a current-limiting
reactor is negligible and in general. amounts to not
more than some 3% of the reactance XL· 85
AU, AU,
u"'
9
)
) )
0
1) r'l
9
)
) ) )
)
I
) )
j j j j
1- r i
I
t t lI 11
1I '
l_
I
a) b) c)
86 Figure 5-25 The most common reactor circuits, a) branch circuit b) group reactor circuit c) busbar reactor circuit
. '?
The scheme shown in Figure 5-25 under a), with The higher the voltage level and the longer the line 5.6.3.2
the reactors in the branches, is the most commonly distances are the higher are the closing overvoltage.
used. The circuit shown in b), with one common In certain cases the value for OM can be more than 3
group reactor in the supply feeder for several times 05 without any measures for limiting the peak
branches, is often chosen for reasons of saving value to less than 2 times 05.
space. The costs of purchase and operation for the
same degree of protection are higher than with Such a measure can be the lateral compensation by
reactors in the bran ches. shunt reactors at both end to prevent pre-charges of
the open line and/or closing resistors on circuit brea
In power stations with a high short-circuit power, it is kers (CB+CR). The closing resistors contact is closed
usual to fit busbar sectionalizing reactors together shortly before the main contact closes to limit the line
with bypass circuit-breakers, as shown in c). In normal energizing current inrush and is opened immedia
operation, the closed circuit breaker and isolators pro tely after the main contact has closed. Its insertion
vide a permanent connection between the busbar time is not more than 3 ms. The closing resistor
sections. In the event of a fault, the circuit-breaker value is between 0.4 to 1 kQ.
opens, and the reactor prevents that both generators
feed into the fault and limits the short-circuit Shunt reactors of suitable size must be permanently
current magnitude approximately to that of the connected to the line to limit the temporary funda
individual systems. mental frequency over voltages. Such line reactors
also serve to limit switching over voltages to some
extent However, reactive shunt compensation increas
es the surge impedance of the line and thereby
reduces the surge impedance loading (SIL) level that
is, the load at which a flat voltage profile along the
5.6.3.2 Shunt
line can be achieved. These permanently connected
reactors shunt reactors also consume active power, which is a
continuous loss to the system.
Shunt reactors in long EHV lines, mainly 400 kV
and above are applied to compensate the effects
Such disadvantages can be overcome with the aid of
of line capacitances and to limit the various types
thyristorized controlled shunt reactors (CSR), which
of over voltages. The example in Figure 5-26 shows
offers all the advantages of the permanently connect
the occur rence of closing overvoltages, which are
ed shunt reactor but only when it is required thus
caused as soon as the line is energized with the
reducing the continuous reactive power drawn as in
circuit breaker
the case of a fixed shunt reactor. CSR automatically
closing at t 0. Before closing the line voltage UL = 0.
goes of the circuit during increased line loading to
The closing overvoltage is rising fast to its maximum
limit the power frequency dynamic over voltag s.
value OM and after approximately 10 ms the overvol
tage OM = OLand line voltage OL becomes
equal with the source voltage 05.
CJ ,. l 1
tronic based components for rapid power flow and
voltage control Figure 5-27 and hence the functiona
Transformer•
lity of existing devices can be optimally extended.
reactor CR reactors i
Generation Plant 400 kV Transmission line Substation i.
vsc
5.6.4 The shunt reactors are switched off sometimes to
increase the power transfer capacity of the transmis
sion line during heavy load conditions. This, however,
vsc
involves the risk of oveNoltage during sudden load
star point connections Series connections
throw off.
5.6.4 FACTS
The VSC modules can also be placed on high volta
Taking into account the actual structure and opera ge potential (Figure 5-28) as well as on low voltage
tion of the interconnected power systems the potential, which will reduce the insulation level and
demand grows to utilize the network capacity in a hence the equipment costs (Figure 5-29).
more effective and flexible way. That means to
increase the utilization of existing transmission facili Against this background the definition of Flexible AC
ties in sense of enhancement of technical and eco Transmission System devices is expanded to encom
nomic performance and more flexible adaptation to pass intelligent network nodes. These are optimized
changing environments. power electronic assisted substation systems aimed
at power flow control as well as voltage control and
Much research has been directed to point out the active filtering for more effective network utilization in
operational benefits of flexible AC Iransmission a deregulated environment and large system exten
System (FAGS) controllers for steady state operation sions projects.
as well as the power system dynamic improvement.
Using existing networks more effectively is the main In modem power systems the trend to transmit
objective in the framework of FAGS device applica power through given corridors is rapidly evolving. The
88 tions. Most of these applications are focused on the reason for this is the lack in the right of way for new
4
Figure 5-29
Facts at low voltage potential
89
5.7 Static Var (reactive power)
compensation (SVC)
,--::·
90
THV
DC
1--
THV 5.7.2.3
RC RC
$([) 1--
I--
THC
a) b) THC
RC THV RC
c) THC
5.8 Switchgear
[1] Switchgear Manual· © ABB Calor Emag Schaltanlagen Mannheim, 1Oth revised
edition, Cornelsen Verlag, Berlin, 2001
[2] KP. Koppel. B. Stepinski, H. Ungrad, K-P. Brand · New Sustation Concepts,
5th Conf. on Electric Power Supply Industry (CEPSI), Manila (1984)
SF6
[3] K-P. Brand, H. Jungblut · The Interaction Potentials of SF6 Ions in SF6 parent Gas
Determined from Mobility Data, Journal of Chemical Physics 78, 4, 1999-2007 (1983)
[4] K-P. Brand ·Dielectric Strength, boiling Point and Toxicity of Gases- Different
Aspects of the same Basic Molecular Properties
IEEE Trans_ on Electrical Insulation El-17, 5, 451-456 (1982)
[5] K-P. Brand, W. Egli, L. Niemeyer, K Ragaller, E. Schade· Dielectric Recovery of an Axially blown
SF6 -Arc after current Zero: Pt./11 - Comparison of Experiment and Theory
IEEE Trans. on Plasma Science PS-10, 3, 162-172 (1982)
[6] K. Ragaller, W. Egli, K-P. Brand ·Dielectric Recovery of an Axially blown SF 6 -Arc
after current Zero: Pt./1- Theoretical Investigations, IEEE Trans. on Plasrna Science PS-
10, 3,
154-162 (1982)
[7] E. Schade, K Ragaller ·Dielectric Recovery of an Axially blown SF 6 -Arc after current
Zero: Ptl- Experimental Investigations, IEEE Trans. on Plasma Science PS-1 0, 3, 141-153
(1982)
[8] K-P Brand · A Model Description of the !on Mobility in SF6 at elevated Pressures,
Proc 15th lnt.Conf.on Phenomena in Ionized Gases (ICPIG) Minsk (1981), Part I, 301-302
[9] K-P Brand, J Kopainsky ·Model Description of Breakdown Properties for Unitary
electronegative Gases and Gas mixture, Proc 3rd Int. Symp. on High Voltage Engineering (ISH),
Milan (1979), Paper 31.05 (4 pages)
[10] K-P. Brand, J Kopainsky ·Breakdown Field strength of Unitary attaching Gases
and Gas mixtures, Applied Physics 18, 321-333 (1979)
[11] K-P. Brand, J. Kopainsky ·Particle Densities in a decaying SF 6 Plasma
Applied Physics 16, 425-432 (1978)
Sensors _
[12] F. Engler et al. ·Test and Service Experiences on Gas insulated switching Systems
and Substations with intelligent Control, Cigre 2000, Paper 34-101 (7 pages), Paris, September 200
l ----
92 ',-
6 The Functions of Substation Automation
6.1 Introduction 95 6
6.2 Process Connection 95' Table of
6.2.1 Sensors and Actuators 96 content
6.2.1.1 Instantaneous analog process inputs (current, voltage) 97
6.2.1.2 Other analog inputs 98
6.2.1.3 Binary process inputs 98
6.2.1.4 Binary process outputs 98
6.2.1.5 Other binary outputs 98
6.2.1.6 Analog outputs 99
6.2.1.7 Analog data from unconventional sensors 99
6.2.1.8 Binary data from unconventional sensors 99
6.2.1.9 Binary process outputs to unconventional actuators 99
6.2.2 Pre-processing of data 99
6.2.2.1 Pre-processing binary data 99
6.2.2.2 Pre-processing of analogue data 101
6.3 Operative Functions 104
6.3.1 Monitoring and supervision functions 104
6.3.1.1 Process state display 105
6.3.1.2 Process overview display 106
6.3.1.3 System configuration display 106
6.3.1.4 Event list and handling 107
6.3.1.5 Alarm annunciation and handling 108
6.3.1.6 Measuring and metering 109
6.3.1.7 Blocking list 109
6.3.1.8 Disturbance recording 111
6.3.1.9 Archiving 111
6.3.2 Control Functions 111
6.3.2.1 Control management functions 112
6.3.3 Protection and safety related functions 118
6.3.3.1 Main protection functions 119
6.3.3.2 Protection related functions 126
6.3.3.3 Interlocking 127
6.3.4 Distributed automation support functions 128
6.3.4.1 Distributed Synchrocheck 128
6.3.4.2 Busbar image 128
6.3.4.3 Station wide interlocking 129
6.3.5 Distributed Automation Functions 132
6.3.5.1 Switching Sequences 132
6.3.5.2 Breaker failure 132
6.3.5.3 Automatic protection adaptation 132
6.3.5.4 Reverse blocking 133 93
. ?
'
,·· '
1·.·
'\_
94 1-i
6 The Functions of Substation Automation
·-
-Q1
' HVLine
bav.
'":!ay =
...... . . , : : :--
IL
··-
. ?
Intelligent Primary Equipment Substation Automation System
0
I
I
·Q51
·QO
1 Proce
- - -;..-- - -·
ss bu s !
\ Proces
_. :_
- - - - - - ·- · m - - - =
t a<
,
cou pl er
d\-A'-
1 l1 Bus lnterbay '
·T1 Star coupler '=====d bus .... :::··
Sampling Network
'i
AD-Conversion Centre i
Signal Processing I
I,
at least the AID conversion and serial communica former tap changers. The most important outputs are
tion, they act at least similar to conventional I/O cards. the control of switches and tap changers. Additionally
Preprocessing of data for maintenance purposes and other physical quantities like temperature, gas pres
more functionality can be added. Therefore, the pro sure etc have to be monitored, and binary as well as
cess interface is moved directly into the process, i.e. to analog control outputs to different other equipment
the switchgear. may be necessary. This leads conventionally to the I
1.
following kinds of sensors and actuators respective
Another change regarding the process interfaces is interfaces to them:
the introduction of non-conventional sensors and
• Currents and voltages from the switchyard:
actuators, e.g. based on fiber optics to generate opti .I
cal signals that are related to the magnitude of the Current transformers (CT) and voltage transformers
primary current rather than a magnetically transfor (VT) directly located in the switchyard deliver cur
med current. To make signal processing not compli rents in ranges from 0 to 1 A or to 5 A, respective
cated, all these non-electrical sensors should produce voltages in the order of 100 or 200 V AC Voltage
signals that are directly proportional to the primary transformers are sometimes also called Potential
source signals. Non-conventional actuators allow to Transformers (PT).
operate the drives of the switching devices directly • Switch positions: Auxiliary switches are mecha
via a serial link also(optical process bus). nically connected with the main contacts. With the
help of the station battery (auxiliary voltage) of
6.2.1 Conventional Sensors and Actuators 1001110/220 V DC they deliver binary information
to the SA system. A switch position is normally
The most important inputs from the process are the indicated by two contacts: one is closed if the
currents and voltages from different places in the switch is closed, and a second one is closed if the
96 switchyard, and the positions of switches and trans- switch is open.
6.2.1.1 Instantaneous analog process
inputs (current voltage)
The analog process inputs are transferred to a sui
table signal range by appropriate signal transformers,
which additionally provide the galvanic isolation from 6.2.1.2
This double indication shows a moving switch in the process. The analog signals are filtered by an anti
the so-called intermediate position if both alias filter, which suppresses multiples of the sampling
contacts are open. For disconnectors and earthing frequency, and finally converted to binary samples by
. switches it is physically impossible that both means of an AID converter (Figure 6-3). Also high
contacts are closed at the same time in normal frequency damping filters are sometimes used to
operation, so this must be regarded as an error. suppress disturbing spikes, depending on the func
The same is true for the intermediate position, if tion to be performed. After this conversion further fil
it lasts longer than the switch movement tirr,e tering with digital filters is made if necessary.
(often called running time). For circuit breakers in Important criteria here are the .accuracy of the AID
high voltage switchyards often each of the three conversion related to the measuring range, and the
phases has its own drive. It may then happen that sampling frequency, which may possibly influence the
one phase is in a different state than the others functionality that is based on the signal data. Both,
(phase discrepancy). If the contaQ:s of the phases amplitude and phase relations are needed. If different
are connected in parallel (logic OR) to get one phases must be compared, then they need a time
double indication again, then the 1-1 state may synchronization accuracy in the order of some
happen, and may be cleared e.g. by an open micro seconds, providing the accuracy needed by
command. If however this state lasts too long or the func tions considered. A timing jitter of 25 [!S
can not be cleared, then again this is a serious leads to an accuracy of about 2 %. The information
error (permanent pole discrepancy). content of samples may be also represented as
phasors, i.e. as a value with an amplitude and a
• Other indications or alarms: Similar
phase angle with the same accuracy.
auxiliary switches like for switch positions are
used, but each indication has one contact only: In pure control systems, where only RMS values of
single indication. currents, voltages and power values are needed,
• Commands: Tripping or closing coils have to dedicated measurand transducers are sometimes used
be supplied with power. Again normally a to preprocess and calculate the needed values from
process auxiliary voltage in the range of 1 VT and CT inputs. They deliver the needed analog
00/110/200 V DC is used, and up to 1 A qu9ntities to the control system either via some serial
currents have to be switched by the auxiliary link, or as mA or V signals similar to e.g. pressure
contacts. sen sors.
For other physical quantities special sensors are used,
which normally deliver proportionai outputs in the
6.2.1.2 Other analog
range of 0...20 mA or +-10 V DC Other ranges (e.g. inputs
0...10 mA, 0... 20 V) are also sometimes used. For
Because of electromagnetic disturbances the mA or
sen
Volt inputs have to be galvanically isolated, e.g. by
sor failure supervision 4...20 mA is also often used,
iso lation amplifiers (Figure 6-3), before they can be
where 4 mA corresponds to a physical value of 0,
fed directly to an AID converter. The needed
while 0 mA indicates that the sensor has failed, e.g.
sampling rate is normally much slower than for the
because of a broken wire. These electrical quantities
voltage and current inputs. Very often sampling is
have to be fed into the SA system, and there
done directly in the application function.
encod ed into binary information, which is suitable
for fur Examples are the so-called PT sensors for tempera-
· J ther processing.
ture with different characteristics (PT20, PT100, etc.). 97
6.2.1.6 Most of the sensors have a linear characteristic, but may happen. An often-used solution is reading back
for some of them a non-linear characteristic has to be the state of a second contact which is mechanically
applied to get the correct physical value (non linear coupled to the operating contact. With this contact
scaling). arrangement, the proper functioning of the control
circuit can be supervised by conducting operation
simulations e.g. once a day without activating the
6.2.7.3 Binary process inputs operating coils.
The process voltage, which indicates either an open
Usually, a contact has to separate each side of the
or a closed contact, is normally connected to optical
operating coil,-so that in normal state the coil is com
couplers for galvanic isolation (Figure 6-3). Thereafter
pletely isolated. This assures that even a short circuit
a discriminator determines the 0 or 1 state. Note that
cannot lead to unintended switching (Figure 6-14).
the 1 state may denote a closed contact (normally
open, NO-contact) as well as an open contact (nor Several contacts in series lead to additional time
mally closed, NC-contact). The contact inputs may be
delays. For protection trips, which must be fast, there
grouped to double indications or, e.g. in case of
fore often only one heavy-duty relay (contact) is used.
trans former tap changer position, to multiple
These single command relays are then over-dimen
indications representing digital numbers. These
sioned to get a very high reliability. This applies only
digital numbers may be binary coded, BCD coded,
for circuit breaker opening, which is not considered as
or even have some other code like Grey code. The
unsafe as other switching operations.
appropriate decoding has to be made in the
substation automation system e.g. by the tap
changer controller.
6.2. 7.5 Other binary
outputs
6.2. 7.4 Binary process
Other binary outputs may be provided for local or
outputs
remote state and alarrn indications. For these outputs
Binary command outputs to the process are perfor signaling relays are used, which are normally not
med via relays whose contacts can directly switch the safety critical and must switch only low currents in the
trip/close coil currents, so called heavy-duty contacts mA range. They may however also be used to ope
(Figure 6-3). The problem here is that these contacts rate the heavy duty relays mentioned above to provi
may burn or melt together, if they switch relatively de an additional barrier against electromagnetic inter
high currents. These command outputs are safety cri ference.
tical. because an unintended operation of a switch may
cause physical damage or endanger human beings,
which happen to be nearby the switch during
opera tion. To minimize the risk two separate output 6.2. 7.6 Analog
chan nels that are connected in series must be outputs
used to supply the operating coil current. In line
For analog outputs normally + -10 V or +- 20 mA
with the for mer RTU based solutions one is called
outputs are used. If an EMI barrier is Jlecessary, addi
the Select channel, which selects the switch, and
tional separating amplifiers are provided. In a modern
the other Execute channel, which switches the
sutslstation, there is normally no need for analog out
load current. Both contacts have to be supervised,
puts, as mostly serial interfaces and LCD or Led
so that a relay
based displays are used.
98 (contact) failure is detected before any second failure
.. • •
6.2.2.1.1
...
f1 . .
Bl
1-r-1 •
Local MMI
B O
Bl •SA
.. ..
..
•SMS
•
81 I ,-,-:I
Intelligent electronic device (lED)
Bl Binary Input for protection and control
BO Binary Output
AI Analog Input
Fl Filter
AD Analog/Digital Converter Figure 5-3 Process connection to a typical/EO
f ; lv
6
- -----
•
- -----
\jC Time
Auxiliary contact
v
VA\
100 Time stamp Time stamp
this buffer depending on the kind of function, which
has to rely on them (mostly protection). These fil ed
values may then be used by the various functions. A
common application for measuring purpose is to cal
culate voltage and current RMS values, frequency,
active and reactive power, as well as the power fac
the change are suppressed. Figure 6-4 illustrates this tor COS!p. 6.2.2.2
method. It has to be noted that it causes an
additio nal delay for the communication of the The measuring process at a certain point in the pro
change of state. If a fast reaction is needed, contact cess possibly leads to a calculated value like the RMS
debouncing should be avoided. It must however be values mentioned above. This value at a certain point
kept in mind that even for an optical input of the process, or sometimes this point itself is called
debouncing cannot be avoided if the source in the measurand. The following general measurand hand
process is a mechanical contact. ling functions refer to electrical measurements as well
as to non electrical measurements from sensors or
6.2.2.1.2 Oscillating transducers, but normally not to the raw sampled
values, which are handled specially e.g. by protection
Some process phenomena like waves of lake water functions.
actuating special contacts for water level indication
may lead to oscillating, i.e. repeated opening and 6.2.2.2.1 Scaling
clos ing of the contact within a time span of 100
ms or even longer. The oscillating may also be The measurands coming from the AID converter are
caused by a broken wire of an input signal, which some integers, depending on AID converter accuracy
flatters due to air circulation. These changes may between 8, today mostly 12 up to 16 bits wide.
lead to unneces sary load of the communication Application functions need an application value in
system as well as unnecessary triggering of some engineering unit. The conversion of the inte
processing functions. Oscillation should therefore gers to engineering units (e.g. Volts or Megawatts) is
be suppressed, but an nounced to the operator. called scaling. The resulting value then normally has
This feature is called anti oscillating or oscillation a floating-point data type. Sometimes also calculated
suppression. It is often imple mented by counting values have to be scaled. A power value calculated as
the changes within a fixed time interval. If this U * I* cos IP might already have a floating-point for
counter reaches a pre-set limit, the oscillating state mat, but has to be normally scaled to the MW
is set, and the communication as well as the range.
processing of any further state changes are
suppressed. If the counter value declines below this The scaling process has to consider the converter
limit (plus sometimes an additional hysteresis value), characteristics across the converter measuring range.
the oscillating flag is reset and new values are Most converters have a linear characteristic, but not
sent and processed again. all. Therefore, in special cases also other than linear
conversions might be necessary.
6.2.2.2 Pre-processing of analogue data
Linear conversion is mostly performed by providing
The preprocessing of analog values after the conver an offset b and a factor a, so that the scaled value s
sion from analog to digital data depends on the (floating point) can be calculated from the measured
kind of value, and the purpose. As already stated in value m (integer) as ·-
6.1.1.1, the prerequisite in each case is that the
analog inputs pass through an anti-alias filter in s =a* m +b.
ordei to prevent any negative impact of the
sampling frequency. If the communication capacity is small and the
value must be transmitted as compact as possible,
The current and voltage samples are stored into a the sen
buffer. Different filtering algorithms may be applied to der scales the value down to a minimum number of
101
row range around nominal value of the line voltage.
If the line is taken out of operation, the voltage
value becomes zero. As this is below any low
voltage limit it would lead to an alarm, although it is
a normal ope rating state. Therefore the alarm
digits for communication, and the receiver scales handling is mostly combined with a zero dead
6.2.2.2.3 back to the engineering units. If the communication band suppression. A configurable range around
capa city and processor capabilities are not an issue, zero can be exempted from the alarm zone, even
then scaling to floating point values is performed as if the value zero as such would be within an alarm
near to the process as possible, i.e. immediately after zone.
AID conversion and measurand calculation.
Instrument transformer: Relative accuracy at nominal value 0.5 % Ar accuracy of 0.5 % in average, is normally
transforms kV to range use:: for plausibility check of measurands -
of +1-200 V me·;: details see in chapter 5.
Interposing transformer Relative accuracy at nominal value 0.1 % Ac-l5 as barrier against disturbances
from 200 V to 10 V as ::ell
Filter Influences frequency range only;
no influence on the RMS value.
AID converter 16 bit Conversion inaccuracy can normally be An 3 bit measurand (either for transmission,
neglected. The inaccuracy depends on the or r'om AID conversion), leads to an accu-
bit range that is used for the measurand racy of 2.5 %, a 12 bit measurand
range (e.g full 16 bit signed used for need- (11 bit + sign) to 0.25%
ed range = > accuracy is 2·14 = 0.006 %)
Scaling Can be neglected, if the result is 32 bit floating point has a mantissa
a 32 bit floating point (accuracy of 24 bits -
better than 16 bit integer)
Communication oscillation Depending on the delta: to get a The inaccuracy of cyclic sending is zero at the
suppression delta sufficient communication load reduction, moment of sending. If the maximum change
often around 0.1 % of the measurand rate of the measurand is not known, no
normal/nominal value is needed accuracy can be estimated in between.
103
6.3 Operative Functions substation specific functions comm
and performance attributes, a tion
which are nor mally not the n
needed in standard industr:al contro
SCADA sys tems. The same center
applies for the specific and the
6.3 safety related switch control toring
Operative functions are all those functions,
functions. data
which directly enable an operator to control
acquis
the substation. These are the typical SCADA
If a network control center functio
functions: Supervision,
remotely controls a sub station, SCADA
£:ontrol nd Qata cquisition. The data
then with the exception of the might
acquisition part of SA systems contains some
implem
d at the substation. This monitoring part
tion, and the HMI and archiving related
could be completely implemented locally
functions are located in the remote control
with the possibility of remote operator access
center, which might cover a number of
to the sub station data. Another possibility is
substations. For special purpose applications
to have only the data acquisition function
like asset management even a separate remote
implemented at the substa-
monitoring center can be used. The following
sections describe the operative functions in
detail.
Figure 6-6 Process state single line diagram for local substation operation and supervision
Tr 101 (- ··;<
Gl1':-':···:" >:·,Q1_,
'
.
\
104
The typical monitoring functions are
• Event management
• Alarm management
• Data storage and archiving
• Disturbance recorder/fault data retrieval Hierarchical windows: starting from a high level 6.3.1.1
• Log management overview window showing the complete system you
navigate with a mouse click to windows showing the
wanted subarea of the system with more informa
6.3. 7. 7 Process state display tion details. This is typically used if geographical neigh
bourship is not so important. but you need fast navi
gation to any subarea or even specific information
There are different methods to browse through the
categories, and information condensing to higher
process state of a system:
levels. It is easy to change the way of presenting infor
Zoom and pan: one can move a window across a mation in different layers of the hierarchy
virtual picture of the whole system (panning) and can
zoom in an area to see more details, or to get an The following examples Illustrate the hierarchic win
overview out of an area respectively navigate to an dow approach.
other (sub-)area. This is typically used for big systems
or geographical views in a geographical information The actual state of the whole switchyard is shown in a
system (GIS), and mostly if one wishes to navigate graphical overview, and in more detailed pictures by
into a neighboring area.
Figure 6-7 Process overview example of a small system with busbar coloring
1'02
f"item<1 ·I:J:IIl i
---- 1 -- ---o I
v v
I1 D
I
- .. ·.·,
•
D·
.T 105
or earthed. Apart from this, the different voltage levels
means of a single line diagram that contains
all sub station equipment (Figure 6-6) can be distinguished with different colors, or parts of the
This state typically comprises substation with different power infeeds can be distinguished
by appropriate colors (Figure 6-7).
• Positions of switches (circuit
breakers, disconnectors,
earthing switches etc)
6.3.1.2 Process overview display
6.3.1.3
• Voltages (kV) and currents (A) at In contrast to the state display showing the state of one
busbars: voltage level in detail, the overview display provid-
lines, and transformers
• Active power (MW) and reactive Figure 6-8 System configuration d1sp/ay for a small SA system
power (MVAr)
Main
---
·-----------
Options Reports Sta!Wns Help
Tuesday (WS) ! * •
--------- --
<111.. !17-01-28 14:59 System
Supervision
Ack. Alann P7-01-lB 10:12:32' E :.Quiiioin& HA7 Q9 Ear11uw. pom!Wn indica!Wn :!:
L
o
c
a
l
A
r
e
a
N
e
t
w
o
r
k
(
L
A
N
)
M
a
l
r
i
x
P
r
i
n
l
e
r
106 SPAD346C
'' J
· --
6.3.1.4
6.3.1.4 Event list and and process events, or for different parts of the
handling pro cess. In modern systems this feature is however
sel dom used because of the availability of highly
The event list contains a time stamped log of all reliable disks of big storage capacity. This avoids the
events that have occurred in the system in problem of running out of paper, which is by far
chronolo gical order (Figure 6-9): more often a problem than loosing some events on
• State the disk.
changes
Due to restricted storage capacity, the event list is
• Alarms appearing and often kept in a ring buffer. If the ring buffer is full the
disappearing oldest events are overwritten. New events must
• Limit never be lost, even in the case of power supply
violations failu re. Therefore, all events are also stored on non-
• Operator's actions: commands vola tile storage media. The high capacity of modern
and acknowledges etc sto rage devices allows to keep much more events
than in the past. Nevertheless some, at least today
Each event can be directly printed O!,!t on a log manual, overflow management, e.g. with yearly 107
printer (logger). It contains the time when the event transfer to a tape or CD, is necessary. Other external
happen ed, an identification of the object (device or applications
signal) to which the event belongs, and the specific
signal state, which has been caused by the
event. Sometimes there are different log printers
provided for system
k7 ,-
for specific data evaluations should also have
access to this data e.g. for maintenance or
planning purpo ses.
The display function for the event list has often
incor porated filtering capabilities. In case of a
6.3.1
.5
failure only those events are displayed
which have occurred in 8 ....------.._
'"
the fault related time window or are Alarrr. comes Alarm com
identified by a Alarm
s
goes Acknowledge
fault expert system. 4
I!!I Ef
108
'(
· '?
?
control system related alarms have to be separated from
switchgear related alarms.
§P 001030.FlT 1!!1£1
Automatic Fauij Location FLT2.0ff
i
1. Event: = Preda (31)
I . Station name =I
Station = 11-Jun-1918:55:44.410
r- - -- -- - -- -- - -- - Event date and = 30
number
time
= Preda (31)
= 94.5 km
Event = C:\1650\EVENTS\001030.EVE
number = 1029.2 ms (-200.0 ms .. 829.2 ms)
Ut(t) Line
name
Line
length
Event file
; Duration of
recordmg
I
I 2. Trigger = Digital signal
Type of trigger (3) =?
•• I
mr .;......------"'--"'-' -1-llll·-----
Trigger
signal
3. Faul1 Location:
, Fau11type = R- 0
, Fault duration = 70.8 ms (-28.3 ms .. 45 ms)
i Region with stable impedance, variations<= 3.1 %
- · - · - Impedance at16.7 ms = 8.43 Ohm,
71° primary
; Distance to fault = 24.7 km (± 3.1 % = ± 0.8 km)
, Faul1 resistance big, about 24 % of total loop resistance
110
I
l.
6.3. 7.9 Archiving
The analog and binary values are constantly sampled 6.3.2 Control Functions
and written into a ring buffer. As soon as a predefined
event like a fault has triggered the recording function, Control functions are used for the normal day to day
the recorded data around a time window before operation of the substation. They are performed via
and after the trigger is frozen in the buffer. an HMI (human machine interface, e.g. screen and
Thereafter, another buffer is activated and the keyboard) that is located either locally in the substa
procedure is restarted for a possible next recording. tion or even in the bay, or remotely at a network con
This continues until all memory buffers are full. In trol center. The HMI presents the process state to an
order to avoid loss of recorded data the files have operator and enables him to control the process
to be retrieved and stored somewhere else, e.g. on (Figure 6-13). The response time of the operational
a station level hard disk or transmitted to a remote functions and the correlated communication is typi
substation monitoring system. A standard storage cally a second (human reaction time scale). It is often
format of this data on disk is the COMTRADE distinguished between monitoring and supervision
format (IEC 60255-24 resp. IEEE Std C37.111- functions thaf retrieve data from the process for per
1999). Dedicated evaluation soft ware is used to formance analysis, and the control functions that
view the recordings and to conduct fault initiate actions on the process. Nevertheless monito
evaluations like the determination of the dis ring and process state display is the prerequisite for
...Trl02 I
·iiiiW
Figure 6-7 3 Human Machine Interface (HMI) for SIS control and monitonng
Commands that directly control the process 6.3.2.1 Control management functions
can cause severe damage if they are issued
wrongly. Therefore, control functions have to be The operator's access to functions, especially to ope
protected against unauthorized access, and rational functions, has to be restricted by a set of
safeguarded that no dangerous and unnecessary or rules, which are defined in the access security
unprompted com mands can be issued. Examples of mana gement as indicated below. They concern
such safety related control functions are: human user's access only, while the access security
• Access control and operator identification between the different devices is handled at system
configura tion time.
• Operative mode
control
The Authentication: The control system shall sup
• Control of switches (commands port user authentication for user access in order to
and back-indications) ensure that only authorized users are permitted to
• Control of transformers (raise/lower use the application. The user authentication process
commands on tap changer, tap allows the system to differentiate between user res
ponsibilities and roles (for example substation opera
position)
tors, administrators, maintenance sta1t, etc) and then
I
• Management of spontaneous
change of positions to select role specific access rights. Under certain cir I
cumstances, e.g. for sensitive information retrieval or i
• Parameter setting
high security control an encryption procedure may
I
112 be used in addition to authentication. I.
I
i·
• A create privilege allows the user to create •
certain classes of application objects. A
• A delete privilege allows the user to delete g
application objects. et
/r
• A view privilege allows the user to acquire e
details concerning the existence of an object a
Access control is a function that provides the capabi lity to and the object definition. d
restrict an authenticated user to a pre-deter mined set of • A set/write privilege allows the user to set pri
functions and object properties. Access control is attribute values of an object. vil
implemented using the following privileges: · eg
e
allows the user to get attribute values of an lowest level is the primary equipment itself, the next
object. higher ones are the bay and the substation level or a
• An execute privilege allows the user to execute the remote operator place for the substation, and the upper
permitted application service. level might be one or more remote network control
centers. The access from these control loca tions must
Each system function and system object may provide be coordinated for safety reasons. Allo cating the higher
access types for user roles with an allocated set of 6.3.2.1.1
access priority to the level that is clo ser to the process
access rights. The sets of access rights may be defin ed normally does this.
by:
• The type of action: e.g. control of the process, control An operator at bay level is authorized to take over the right
of the system, maintenance of the system,· etc for bay operation by putting the bay into the local mode,
e.g. by physically turning a key locked local! remote
• The area of expertise: e.g. operation, switch into its local position. This auto matically blocks
protection, control. etc. commands from higher system levels in the control
• The level of competence of the user: e.g. hierarchy of this bay, e.g. from substa tion level or network
manager, substation operator, administrator, etc. control centers. The same pro cedure is applied on all
• The concerned part of the substation, when a hierarchy levels. In addition to this, a split of the control
substation controlled by one system is shared by system into certain regional sub-systems is possible. If an
different utilities: the bays or diameters, equipment. operator takes over the responsibility for a certain region,
or voltage level concerned. this blocks all the other operators on the same hierarchical
level to con trol that region. This may happen dynamically,
Access control privileges may be altered dynamically to in con trast to the statically allocated access priorities
resolve conflicting requirements of multiple users. de scribed above. For synchronization purposes on the
same level it may be sufficient if the initiation of a
Control can be performed at a lot of places in the control action e.g. by selecting an object blocks all other
system, on various system hierarchy levels as well as on control actions.
multiple work places at the same level. The
113
'.l
6.3.2.1.2 The "Execute" command is subject to miscellaneous If the controlled object is in an unknown state
conditions that assure that there will be no damage (e.g. phase discrepancy which causes a double
if the control action is conducted: point state with 1-1 value) the object has to be
tripped and blocked.
• Correctly working control device. The self
superJision of the control device will detect failures This last check can be suppressed if the object has
and block the control function if necessary. one common operating mechanism for all phases.
• Interlock validity. Interlocking is a parallel
function that delivers a state to enable or disable The control command is cancelled if one of these
a control action. The control circuit may contain conditions is not met, or if a cancellation order is
an interlock override switch (hardware or software) received form the control point. Figure 6-14 illustrates
for manual control in interlocked condition. where on the control path which conditions are
checked.
• Synchrocheck validity. When closing a breaker,
the synchrocheck function will verify voltage
synchronism before the breaker is closed. This 6.3.2.1.2 Control dialogs
function may also be overridden in certain cases.
Control dialogues are used to open and close all kind
• Locked (blocked) state. A controlled object of HV or MV switches. They are aiways performed as
may be locked if the associated part of the a two-step process with a select and an execute
substation has been put into the maintenance phase. They mostly are initiated at station (HMI) level
mode. This as shown in Figure 6-15, from there the commands
for example prohibits any control of the breaker are sent across the communication link down to bay
if some repair work is carried out on the line. level, and then from bay level to the process (Figure
Note that locking an object is also a control action. 6-14).
• Control privilege. This privilege of an For safety reason it is a principle, that a command
operator is checked if he wants to control an within the dialog shall only be allowed, if all condi
object. tions as described above are fulfilled. This means that
• Substation and bay mode. The substation de-blocking is only possible for a manually blocked
must be in the remote mode to enable command, for a command that is blocked by the pro
control from remote (i.e. from network control cess de-blocking can only be made (if at all) by an
center) or in the local mode to enable control override. Some process conditions are only checked if
from the substation level. The bay mode must the switch is selected for operation. In this case the
be in remote mode to enable control from the ..Select" step might be allowed, but the ..Execute"
station level or from the remote control level. command is later blocked, so that normally only a
cancellation of the command is possible.
· • State of the controlled item. The control
action shall be physically possible without causing Figure 6-15 shows an example of the Select/Execute
damage, i.e. sufficient gas pressure in a GIS switch diaiog, which-appears after the selection of the switch
and sufficient stored energy is available to perform E1 QO. It only allows to select the Close command.
· the Intended operation successfuiiy. It shail further The Open command is dimmed, because the switch
be assured that the controlled object has a is in the open position. After verification of the correct
valid position for the intended command, i.e. it
must be impossible to initiate an "OFF"
command on
114 a disconnector that is already in the open position. selection.the operator can click the "Execute" button.
Substation and bay mode state
Correctly working control device For safety reasons it is important that this two-step 6.3.2.1.2
Interlock validity procedure is performed at each control level. For cir
Synchrocheck validity cuit breakers mostly all the check conditions de
scribed above apply, while for disconnedors and
earth-ing switches no synchrocheck function is
Control authority ------l-- requir ed. Figure 6-15 shows one way of working.
State of the controlled Item (breaker) > in Figure 6 -16. The Select open respective Select Go
contacts determine the turning direction of the motor.
Figure 6-74 Influencing commands from station HMI The Execute contacts then conned the DC supply to
to switchgear the motor. If the motor becomes too hot, the thermal
Lasi
. llOkV . Substation
Q1 Q2 -BB2
Q1
·z.
Q51
QOQ5 ,
Q51c ... - 'Q52
0 ao:_.·.· r_;
ObjectMiiU m
115
+125VDC
contacts disconnect the DC supply, and an alarm is If parameter sets are switched from remote, it should
initiated by the drive supervision contact. For safety be kept in mind, that a faulty communication link dis
reasons all relays have an extra contact, which is ables the reset to a "safer" parameter set. Self-moni
mechanically coupled to the switching contact to toring features of the relay can however handle this.
supervise their correct working in order to detect a
faulted, e.g. melted contact that might cause a wrong,
unwanted and possibly dangerous motor operation. 6.3.2.1.5 Synchronous or point-on-wave
switching
6.3.2.1.3 Transformer control Circuit breaker operation can sometimes cause unde
Transformers are often equipped with automatic on sirable transient overvoltages and overcurrents in
load tap changer control, which has the task to high voltage networks. This is particularly true for
keep the secondary voltage within a preset voltage reactive load switching, e.g. shunt reactors, shunt
range and to minimize the circulating current capacitor banks, unloaded power transformers and
between pa rallel transformers (master-follower and unloaded transmission lines. In these cases, the mag
others). The automatic control can be switched nitude of the switching transients can -either exceed
off to enable manual control of the transformer: the maximum allowable switching insulation level
after the selection of the transformer it is possible (SIL), or it may endanger in the long-run the electric
to either raise or lower the tap changer position endurance of the HV equipment in the network
step by step. All con trol conditions. except
synchrocheck and interlocking apply in a transformer The traditional measure to protect transformers or
116 specific way. reactors against overvoltages caused either by light-
Voltage
withstand
characteris Voltage withstand
tic characteristic
corresponding to tamin
Arcing time
window for Transient
synchronize Tripping impulse recovery
d switching voltage
without 6.3.2.1.5
synchro
nized interrupti
on
switching
Target for
contact
separation
Ran
ge of
conta
ct
sepa
ratio
n
ning strokes or by switching operations is the sion lines. The desired degree of
instal compensation depends on the operating
lation of surge conditions of the network in terms of load
arresters. profile. Therefore shunt reactors are frequently
operated.
Switching oveNoltage can further be caused by
high current inrush on long transmission lines or
The interruption of shunt reactor currents, which
capacitor banks. The measure against such
are very small in comparison with the rated
oveNoltages is to equip the associated circuit
short circuit current of the circuit breaker, may
breaker with closing resis tors to limit the inrush
lead to current chopping. This generates high
current.
oveNoltages in the shunt reactors, which may
The most modern technology for switching exceed the voltage with stand characteristic of
surge control to substitute closing and opening the CB and cause re-ignition of the arc in the
resistors on circuit breakers is the synchronized or interrupting chamber. This generated steep front
point-on-wave switching. voltage waves stress the insulation of the shunt
reactor winding and may lead to aging and
The function Synchronous switching avoids finally to failures of the insulation. Therefore the--
oveNol tages by closing or opening of the opti mal solution is toavoid current chopping by
circuit breaker exactly at the current zero point. means of synchronized or point-on-wave
The example (Figure switching.
6-17) shows synchronized opening for shunt
reac As all synchronous switching needs very exact
t timing, there are, despite the advantages, up to
o now not
r many commercial implementations installed.
s 117
.
.. ... ...
.
'? '?
'?
6.3.2. 7.5. 7 Synchronized Closing tad traveling time is continuously monitored. The set-
tings of the function are adapted from breaker ope-
The objective of synchronized closing is that the main ration to operation accordingly.
contacts of the breaker are closed exactly at the in-
stant of equal potential on both sides of the contact 6.3.2.7.5.4 Synchronized switching and
to avoid or minimize pre-arcing during the closing synchrocheck
6.3.3 operation. Therefore, the instantaneous voltage va-
lues on both sides of the open breaker contacts have Less demandi:1g and powerful but serving also the
to be compared to calculate the optimal instant of minimal purpose of connecting only voltages, which
contact touching before the closing operation is ini- are in phase as defined by specified limits for U,
tiated, considering the specific breaker closing time. M,
and cos cp, is the very common synchrocheck (see
This calculated instant of closing shall be reached 6.3.4.1).
within a tolerance of +/- 0.1 ms to minimize pre-
arcing that occurs in the course of the closing 6.3.3 Protection and safety related functions
opera- tion before the moving and the fixed contact
touch. Protection and safety related functions need to be
fast and autonomous, and they interact directly with ·
As the line potential has to be compared with the
busbar potential the associated VT has to be selected the process and the process data without the inter-
in relation to the actual busbar configuration. This i
terence of the operator. This means on the other
information may either be provided from the station hand, that they must work safe and reliable. The
level or already be available at the bay level. dedicated functionality (i.e. without data acquisition or
operator interface) relates either to a specific piece of
The high accuracy required for comparison of the val- primary equipment or to a bay. The processed data
tage samples can be achieved either by synchronized belong either to the specific primary equipment or to
sampling or by asynchronous samples that are time a bay. There is an HMI provided for parameterization,
tagged with the same accuracy as applied for wave- or for disabling and enabling of the function. In
prin- form reconstruction. This depends on how the tunc- ciple three classes of these functions can be
distin- tion is implemented and on the selected communi- guished:
cation implementation (bus/protocol), in case the
vol-
tage values have to be retrieved via serial communi- • Protection: this is the active safety level, which
cation. The sample time accuracy should be better supervises the process for dangerous situations
than 50 f!S. and responds to clear them by tripping the
associated circuit breaker(s). ' I'
6.3.2. 7.5.2 Synchronized Opening (Tripping) • Interlocking: This is a passive safety level for
all kinds of commands. It identifies dangerous i'
I.
operations and blocks commands, which might t·
The objective of synchronized opening is to assure l·
that breaker contact separation occurs exactly at the become dangerous.
optimal instant near to current zero, so that the short
• Auto-matics: these are sequences of actions I
circuit current can be extinguished within the
performed automatically, after some trigger
i
minimal
t. .
arcing time. The calculated instant of contact separa-
tion shall be obtained within an accuracy of 1 ms. impulse has started them. They may be triggered
either by an operator or by another automatic
Current information from the bay CT is needed to cal-
function like protection, or by the process i
culate this instant of time. ------- (_
condition supervision. In the last case, normally
the condition supervision is an integral part of
6.3.2. 7 .5.3 Common functionality the automatic function. Each automatic function
should have its own safety checks, and reside on
Since the successful timing is determined by the the top of underlying interlocking and protection
118 mechanical behavior of the specific breaker, the con- functions.
63.3.1 Main protection functions This protection concept comprises the following 6.3.3.1
devices.
In general within a substation the protection of pri-.
mary objects is used: protection of a line, a busbar, a 1. Overcurrent protection
power generator or a transformer. Therefore, the 2. Distance protection
main protection function is dedicated to the object to 3. Autoreclosure relay
be protected, although a lot of protection fur,ctions 4. Differential protection
like overcurrent protection can be used for different 5. Directional earth fault protection
object types. Here a short overview is given. More
6. Overload protection
details can be found in the vast protection literature.
7. Frequency relay
8. Voltage relay
6.3.3.1.1 Protection concept for a substation
9. Earth fault indication relay
A typical concept for a substation comprising line, 10. Busbar protection system
transformer and bus coupler is indicated in Fig. 6-18. 11. Buchholz protection, thermal monitoring
10
[jJ
: 5]
I
1
I
Auxiliary : Auxiliary I
'f" line t line •
0 Optional protection
Figure 6-7 8 Protection concept for a substation 119
' '?
• Medium voltage (300 - 600 V):
Transportation industry
• High voltage (greater than 600 V):
6.3.3.·1.2 6.3.3.1.2 Line protection Long distance bulk transmission, submarine,
and major system interconnections
Alternating current (AC) lines are commonly classified
by function, which is related to voltage level. While Most faults experienced in a power system occur on
there are no utility wide standards, typical classifica the lines connecting generating sources with usage
. tions are as follows: points. A line protection relay protects a line against
all kinds of overload, especially caused by short cir
• Distribution (3.6 - 36 kV): cuits. There are seven protective techniques com
Circuits transmitting power to the final retail outlet. monly used for isolating faults on power lines:
• Instantaneous overcurrent
• Subtransmission (17.5 - 145 kV):
Circuits transmitting power to distribution • Time-overcurrent
substations and to bulk retail outlets. • Directional instantaneous and/or time-overcurrent
• Transmission (72.5 - 765 • Step time-overcurrent
kV): • Inverse time-distance
Circuits transmitting power between major • Zone distance
substations of interconnecting systems, and
• Pilot relaying or line differential
to wholesale outlets. Transmission lines are
further divided into: The most common function is the simple overcurrent
• High voltage (HV): 115- 245 kV protection, the most sophisticated the impedance
based zone distance protection, the most selective
• Extra high voltage: (EHV): 300 - 765 kV
but demanding from the communication infrastruc
• Ultra high voltage (UHV): greater than ture is the line differential protection (Table 6-1).
765 kV
Several fundamental factors influence the final choice
· Direct current systems can be classified as follows: of the protection applied to a power line:
• Low voltage (24- 250 1. Type of circuit: cable, overhead, single line con
V): figuration, parallel lines, multi-terminals etc.
Auxiliary power in power plants and substations,
controJ circuits and, occasionally, utilization power 2. Line function and importance: effect on seiVice
in some industrial plants continuity, realistic and practical time requirements
to isolate the fault from the rest of the system.
I • Direction comparison
Table 6-1 Short circuit and earth fault protection for medium voltage (MV), high voltage (HV)
and extra high voltage (EHV) transmission lines
120
3. Coordination and matching requirements: com
patibility with equipment on the associated lines
and systems.
Table 6-2 Faults that endanger the operation of transformers and reactors 121
6.3.3.1.3
AI
j_
Protection for a small 2 Protection for a large 3
windings transformer windings transformer
> 100 MWA
Figure 6-19 Typical transformer protection schemes
Modern design practices and improved materials For any particular hazard, the initial operating and
lead to low frequency of failures in generators, yet maintenance costs of protection schemes and the
fail ures can occur and may result in severe damage degree of protection must be carefully weighted
and long outages. For this reason, abnormal against the risk encountered if no protection is
conditions must be recognized promptly and the applied. The amount of protection that should be
trouble area must be quickly isolated. applied will vary according to the size and the impor
tance of the machine.
Abnormal conditions that may occur with generators
include the following:
Internal faults in the generator generally develop as
• Faults in windings
ground fault in one of the phase windings and may
• Overload
occasionally involve more than one phase. Differential
• Overheating of windings or bearings protection is the most effective scheme against multi
• Overspeed phase faults. In differential protection, the currents in
• Loss of excitation each phase on each side of the machine are com
• Motoring of generators pared in a differential circuit. Any current deviation is
• Single phase or unbalanced operation used to disconnect the generator from the power
• Out of step network (Table 6-4).
For big generators the protection schemes rare. But if a fault occurs, the damage can
are always duplicated and both schemes be wide spread by causing disastrous
are completely sepa rated, and each cascade tripping of generators and lines
scheme is provided with a separate and finally the collapse of large parts of
auxiliary power supply. For safety reason it the power system.
is not recommended to keep a generator in
operation if one of the two protection
6.3.3.1.5
The term busbar protection is related to
systems is out of service for a longer time. special pro tection schemes that acquire
· short circuit and earth fault currents within
the area of the busbar in HV and EHV
It should be noted that very often the substations. The task of a breaker failure
differential pro tection covers not only the protec tion function is to detect that a
generator but also the · attached step-up breaker has failed to clear a fault on the
transformer as one single genera tor- busbar, and to trip all the remain ing
transformer block protection. breakers feeding into the busbar section
con cerned to clear the fault. Busbar and
6.3.3.1.5 Busbar and breaker failure breaker failure protection respond in a
protection similar way to busbar faults, therefore both
protection functions are usually inte grated
The busbar of a transmission substation is in one common protection scheme.
the most sensitive node in the network. Due
to the merging of many supply circuits, Differential protection is the most sensitive
high current magnitudes are involved. and relia ble method for protecting station
Busbar failures due to lightning strokes or busses. However, problems can result from
connectors melting because of overload are a large number of circuits
relatively
0
Control room
L
Switchya i
rcl n
e
P
r
o
t
e
c
t
i
o
n
lnterbaybus
Bay
Protectio
n
Q
1
QO\Tc QO\
QO\-n: p
F Double
Busbar
T1 T1 •
125
QO\
T1
T1.
't
A busbar protection scheme has to fulfill the follow
ing requirements to ensure save and reliable opera
tion.
127
( ."
I'
6.3.4 Distributed automation support functions are opera- bay, where the bay VT output can be directly connect-
If
ting with data directly from the process and supply ed to these devices. Nevertheless, the output of the
II
decision data to other functions, which act directly busbar VT providing the busbar voltage either direct-
locally on the process without the interference of the
operator. In contrast to the local process automation
ly or via a busbar image remains to be switched to
the appropriate bay.
ll
(support) functions they use input data from the
whole switchyard. The core functionality (i.e. without New fast and high capacity communication media
data acquisition or HMI) uses data from several bays. nowadays allow transferring the needed busbar val-
There is an HMI for parameterization, or tor disabling tage across the communication bus in digital
form, and enabling of the function. avoiding any needs for physical switching. Due
to the
time delay caused by the communication special
I[·.·
There are essentially two automatic support means are however necessary to synchronize the
functions:
time of the voltage data retrieved from the two sour- I
I\
I
• Distributed synchrocheck, ces, bay ar:d busbar, with accuracy around 20 [.tS. I [
• Station wide interlocking.
The upcoming communication standard IEC 61850
6.3.4. 7 Distributed Synchrocheck will be an enabler for the implementation of this
cost
effective function, as it has the features to achieve
Distributed synchrocheck is essentially the same func- accuracy and to provide the necessary
this tion as the local synchrocheck, however the data of
communica- tion band·.vidth in a standardized way.
at least one voltage transformer is coming via the
communication system. This may be the voltage from
the busbar, or from another bay, if no voltage trans-
formers are available at the busbar (respective not on 6.3.4.2 Busbar image
all bus bar segments). The determination of which VT
has to be taken to obtain the correct busbar voltage If the busbar voltage transformer has been omitted in I
l\
is often called busbar image (See 6.3.4.2). the switchyard to save costs in the primary system, a
busbar image function has to be applied to deter-
Traditionally one synchrocheck device was used per
mine which line is actually connected to the busbar.
substation or voltage level. For closing a circuit brea-
The VT of this line is taken as the busbar voltage I
ker with synchrocheck the corresponding line voltage
source e.g. for synchrocheck or for the busbar
VT output as well as the busbar voltage VT output
volta-
ge measurement. This busbar image is based on the
were connected via relay contacts to this synchro-
topology of the substation single line, i.e. the
check device. The result of the voltage comparison
momen- tary state of all switches as well as their static connec- I
was fed back to all bays inclusive that one concerned. [_:_
tions. This busbar image can naturally also be used to
This VT output switching was rather dangerous and
determine the voltage at the busbar, even if there is
had to be made in a very controlled and supervised I
I'
way, because if accidentally two VT outputs were no busbar VT available (Figure 6-23), and to show I
this calculated busbar voltage at station leveL I
conneeted, the VTs could be destroyed. Using this
hardwired solution, power may be accidentally fed
back from the loaded to the unloaded It should be noted that such a busbar image is not
line. only needed for busbar protection but also for other
With the numerical bay level protection or control distributed functions like distributed synchrocheck or
128 devices the synchrocheck became a function at each station wide interlocking. i
I
i..
6.3.4.3
Cable Overhead
!
Transformer Bus
line coupler
IJJ Distance protection
Autoreclosure
Figure 6-23 Distributed synchrocheck for autorec/osure
[I) Distributed synchrocheck after a line earth fault trip
isolate. So a next switching operation has to wait • Do not connect two feeders directly.
until the switch has reached its end position
again.
• Do not interrupt power flow by disconnector. indicate that the protection of the line has been
The power flow will damage it. switched to the bus coupler circuit breaker.
• Do not enlarge parts with unknown states.
Failure limitation
'
• Earth/unearth only isolated nodes or an open circuit breaker (weak version for AIS:
isolated I
circuit breakers. to an isolated node).
• Do not switch a disconnector near a partly earthed • Connect a feeder via a disconnector only to
circuit breaker, or if itself is only partly earthed. an open circuit breaker, or (in case of a bypass
disconnector) to an isolated busbar part.
• Do not close a partly earthed circuit breaker near
an earthed transformer.
• Do not open a bypass disconnector in a live
feeder, if the bypassed circuit breaker is open.
I
• Do not transfer earth potential (by closing
Fault
'(
The reconnection of feeders and consumers is made Any actions are started by deviations of voltage or
134 in a proper sequence according to some predefined reactive power from their set points. For more than i
l
f (Hz)
f N
6.3.5.8
f Lim 1
f Lim 2
L----or----+---------- - t (s)
Figure 6-27 Automated load shedding
one transformer, it is considered additionally if the over has to take place bumpless in such a way
cir that no problems regarding the synchronization
culating reactive current is above its accepted limit. of lines and loads (e.g. motors) appear.
In case that one of the two line circuit breakers of line requires that the CB of the MV bus section is preci
F1 or F2 is spontaneously tripped because of line or sely closed at the instant when the voltages are syn
6.4 transformer faults, the high speed power transfer chronous taking in consideration the motors slowing
scheme assures that supply for both busbars is main down. After the fault has been eliminated the re
tained without extensive stress of the motors. This transfer of the loads can be automatically conducted.
This ply to vital auxiliaries in power plants and sensitive
functi industrial processes.
on is A substation automation system normally consists
prima out of a set of standard software packages, running
rily on a distributed system, and a lot of substation and
Figure 6-28 High speed busbar transfer
used customer specific configuration data, function para
to meters, and specifically developed software. In the
maint ideal case all software is stable, and any necessary
ain adaptations during operation or for eventual later sys
powe tem modifications and extensions can be just done
r by configuration and parameterization; this means by
sup adaptation of the appropriate data, which describe
the switchyard, the control system and its functions,
High-Speed
Busbar Transfer
Transformer
Protection
136
· ?
?
set of the engineering functionality, which is of
needed during commissioning, and during
operation and maintenance of the system. Note
however, that the limits between software and
data are fluent and depending on the view
point. So on one extreme a Java program is just
data for the Java compiler. On the other extreme
and its connections to its environment The System a selection of options for a data object can
Configuration and Maintenance functions are a sub completely change its behavior. Therefore this set
functions cannot be clearly delimited and parameters as well as their physical storage often fol
described. lows the physical (lED based) structure of the auto
mation system, and only within this structure,
In any case these functions must mark all the objects there might be function related substructures.
(data or software) describing a system instance with Additionally to this lED based structure there must
revision information. This must as a minimum exist a system configuration description, which
identify the revision and contain the date of the contains the system related configuration data 6.4.2
last change. As this is normally not done for a holding the single lEOs together in the system. A
single item of a configuration data base, this data typical example is a com munication connection
must be structured into entities with a common scheme with connection information.
purpose, which then have a common revision
index. This allows to track changes during the life System configuration functions allow to store, load
time of the system. Normally more than this and modify configuration data in a systematic
absolute minimum in revision history and change way, and to keep the version or revision history.
tracking should be provided, otherwise error
tracking and removal, and adaptation and
enhancement of a system will be a Sisyphus work.
6.4.2 Application Software Upgrade
and Maintenance
6.4.1 System Configuration and
Adaptation It may happen, that errors found in a base
software package cause a replacement by a newer
The system configuration consists of all data describ version, or that the new hardware implemented
ing the individual configuration of a system. It after a hard ware defect is not 100 % compatible,
exclu des those data which are normally so that other drivers or a newer operating system
changed/adapted during operation. In some cases, version has to be installed. Sometimes these
e.g. for the limits of certain measurands, it might modifications can be done on top of the existing
depend on the opera tion philosophy of the system. But mostly the repla cement of some base
customer if these are opera tional parameters or software requires a reinstalla tion of all correlated
configuration parameters. packages, and especially of the system specific data.
Sometimes, some system speci fic data have to be
Configuration parameters normally have to be converted into a new physical for mat, or even
resto red during replacement of hardware, and some new configuration parameters have to be
they are changed only, if the system is modified or set, before the new package can fully per form its
if they con task It is important,
tain errors. Therefore the structuring of configuration sions of the application have to be installed. 137
65 Communication Functions
6.5 Communication functions are suprort functions, systems. It provides binary and analog process relat
which are necessary due to the fad, that ed data as well as time stamped events for a net
work control center. For this functionality the
• either the system is widely distributed and the standard protocol is today IEC 60870-5-101, which
communication performance is not sufficient when is especial ly designed for slow speed, unreliable
all functions would individually and directly access modem or power line carrier connections. With
the same data source, the advent of high speed wide area networks e.g.
• or devices from several manufacturers or through optical cables contained within the
different implementation generations have to be earthing rope of trans mission lines, there is a shift
connected with different protocols. to the IEC 60870-5-104 protocol, which is a TCP/IP
based variant of 101. In future, the new
communication bandwidth capa bilities together
6.5.1 Data Exchange withithe Substation with the IEC 61850·protocol could make a gateway
function superfluous. A simple bridge, router, or (for
Data exchange within the substation is needed in dis security) firewall device could then be sufficient. It
tributed systems, or for coordination purposes within should however be kept in mind, that at least for
redundant systems, respectively between parts that control not everything of the lower level shall be
have been physically separated because of reliability directly accessible at all higher levels. A control
reasons. A typical communication function within the coordination, data concentration and data filtering,
substation enables data exchange between the perhaps in specially designed firewalls, will always
con trol devices or the station level devices at one remain.
side, and the protection devices on the other side.
This task has become simpler since the IEC 60870-5- New functionality and new needs lead to a second
103 standard exists for the serial connection of kind of wide area connection directly to substations:
protection devices to a substation automation connections from maintenance centers. These com
system. munication functions are already now mostly based
on TCP/IP connections, because maintenance func
Another usage for communication functions is to inte tions are not time critical. Therefore here the slow
grate devices with 'third party manufacturer' specific speed of modem connections and higher protocol
protocols like DNP3, Modbus etc overhead is acceptable. IEC 61850 will also here sim
plify life further by standardizing also the application
Only with the upcoming lrC 61850 standard for level, especially for new asset management and
communication within the substation it can be expect power quality functions.
ed, that the communication as a special function
gets invisible at least for new systems.
6.7 References
6.7 [1] Walter A Elmore (Ed.)· Protective Re(aying Theory and Applictions,
Marcel Dekker, New York (1994)
141
7 Substation Automation Structure
Network Control
>
Q)
Center NCC
....1
1:
0
i.....
U)
G)
m
>
Q)
....1
Q)
! Iiiii
-'f
HV equipment
GIS or AIS Switchgear
>
Q) Instrument Transformers
....1
)l Power Transformers
t/1
t/1
Q)
u
... Surge Arresters
0 -Q) -09 -
....
D..
-Q1
142
7 2 Station Level
7.2
The station level provides the Human Machine Also the interfaces for the communication with remo
Interface (HMI) as central place for substation opera te centers for network control, monitoring or main
tion. This is normally located in a central room, which tenance are usually physically located at the station
should be shielded against electromagnetic distur level. The station level equipment is often separated
bances from the switchyard. Further also all general into two rooms:
purpose hardware, screens and printers are concen
trated on station level. This commercial equipment •. the operation room providing comfortable
working conditions and noise protection for
needs air conditioning and AC supplied by a special
operators is equipped with the Human Machine
uninterruptible power supply (UPS). The rest of the
Interface that consists of scr€ens, keyboards,
substation works with 110 or 220 V DC, which is
tablets or mice, printers, and in earlier times
supplied by the station battery, directly in the
also a control panel (Figure 7-2),
switch yard environment. Consequently, all general
manage ment and station level functions like • and a communication equipment room,
event logging and printing, archiving and history where the computers,..backup printers, and
data stonng are located at station level, as well as communication equipment reside, which may
more complex sta tion level automatic functions be more noisy.
that can easier be implemented on powerful, Due to the miniaturization of electronics the PC
general purpose compu ters. hosting the HMI software can also run parts of the 143
room
where
equipm
operational and communication software, may
so that this PC is normally located in the integra
operation room. In case that this also one de
applies for the telecommunication
equipment. all can shrink down to one
least for small to medium size ...
substations.
7.2.4 ed on one general-purpose computer, the .,
additional-
72.1 Human Machine Interface (HMI) ly needed work places are realized
as terminals, which are associated to this
central station level com-
The human machine interface (HMI) seNes to puter. The central station computer provides the
opera-
te and supeNise the substation. In modern substa- access to the process and conducts the
archiving, log- tion automation systems it comprises one or several ging and station
operator places. Each operator place has one or, in
r
automation functions. It has to be kept
in mind, however, that all station level automatic rare cases, even two to three screens, a
keyboard, and functions must be coordinated with
the operator's a mouse. Sometimes also functional keyboards or actions whether taken
on station or on bay level. graphical tablets are used, but the mouse in combi-
nation with active buttons on the screen pictures is
more and more standard practice, so that 72.3 Substation Database and Archive
functional keyboards are no longer required.
Exceptions to this are screen-based HMis in The large storage capacity that is available on station
harsh environment. which ,,
must be sealed against dust or humidity. Here often level by means of hard disks, tapes and nowadays
touch screens are used, or specially designed functio- CDs, naturally leads to a system
architecture, that locates the data archive for all archiving
nal keyboards.
functions on station level. Also the data for engineering and
A printer for screen hardcopy and reports supple- system configuration as well as for
maintenance are ments the operator place. In earlier times, also event usually stored on this
level. if not even higher to allow log printers have been used in order to overcome the
central administration for a lot of
substations. Depen- limited computer storage capacity by "storing" event ding on the purpose,
J
either data files or relational history on paper. The disadvantage was that the prin- databases are
used for data storage. Because of per- ters could run out of paper. In view of the huge star-
formance requirements actual process r
status data is age capacity that is today available on modern hard very often held in
manufacturer specific real time disks in combination with the advent of high capaci-
databases implemented in the RAM memory. New ty backup media like CDs or tapes as well
as of the technologies like object oriented
databases, OPC (OLE, possibility to use high speed communication links to i.e. Object Linking and
Embedding, for Process Con- maintenance centers the event log printer is slowly trol) for
process data access, as well as the increasing outdated. computer performance will change this
present prac- tice resulting in an object oriented data storing con-
72.2 Local Control and Station Level cept that provides data access via multiple views res-
pective different usage aspects.
Automatics
,.
Depending on size, complexity, and required reliabi-
lity, station level automatic functions may 72.4 Process Data Access
reside on a I
separate station levellED with the same reliability and All station level functions need to have-
access to the environmental quality than the bay leveiiEDs. These process data. This has
to be enabled via specific com- functions may also be implemented into the station
munication functions depending on the kind of data HMI computer or another station level
general-pur- to be accessed as well as on the
communication pro- pose computer, which then normally needs special tocol to be
used. In order to decouple the station measures like redundancy to obtain the needed avai-
level functions from the communication
protocol. a
144 lability. If all needed functionality can be concentrat- process access layer is implemented in between.
. '?'
GPS
Master
In SCADA systems a central process database is typi clock 7.2.5
cally used provided with relatively slow wide area
communication links. Its state is regularly updated
lnterbay bus 1
from the process via the communication system, and
the process related information is used by all station
level functions. Industrial control systems with high
speed LANs rely in contrast on distributed process
databases that are located in the bay level controllers
Master
and are accessed from the station level functions via
clock
LAN.
., --,""='"="""""
1,
-
Figure 7-4 Bay control and protection cubicles in a control building
disturbance data. Up to now this has been conducted 7.3 Bay Levei
on the basis of manufacturer specific communication
protocols often derived from existing protocol stacks
The physical bay level is close to the switchyard
and adapted at application layer to the specific
equipment, i.e.
needs. Depending on the manufacturers tradition,
master/ slave protocols or multi-peer protocols • In the case of medium voltage equipment this is
have been used (see chapter 8 for an explanation the medium voltage cubicle. Modern control and
of these com munication modes). This also had an protection IEDs can be incorporated directly into
impact on the implemented control system this cubicle in order to save material for a separate
architectures. Master/ slave based protocols lead to cubicle as well as cabling costs. The IEDs' built-in
star structures with a central master, while multi-peer HMI can be used directly to safely operate the
protocols allow the distribution of functions bay. .,_
between bay level devices and also distribution of
• In the case of high voltage switchgear it has to
station level functions to dif ferent devices. The new
be distinguished between air insulated
IEC standard IEC 61850 har monizes these practices
substations (AIS) and SF6 gas insolated
and leads to a new flexibility for control system users
as well as to improved main tenance quality. substations (GIS). GIS 147
is normally housed in a building for protection
against rain, temperature variations, wind and dust.
73.3 Bay Level Monitoring
•
73.2 Bay Level Protection !
Digital microprocessor based protection relays can be Alarm annunciators indicate causes of failures, and
placed into the bay cubicles as well. Typically,the the state of the protection and control equipment It
state of a relay and some important alarms are further displays the current position of the switches,
shown with some LEOs at its front side. Often and bay related measurements. The control panel
numerical protection relays have a LCD based built- can either consist of a LCD panel that is integrated
in HMI, which allows checking the last events and into the control device (Figure 7-5), or it can merely
the activated protection parameters. Sometimes this comprise some LEOs as in the case of protection
is done additionally or instead with a plugged-in devices.
148 laptop computer and spe cial parameterization
software.
r·
Station HMI
7.4
Control Protection
cubicle cubicle
For HV or EHV transmission substations the HMI • Connection of conventional or electro-optical CTs
can be located in a completely separate control and VTs for voltage and current measurements.
panel with mimic and key interlocked operation
over swit ches or push buttons, complimented • Sensors for non-electrical measurements like gas
with alarm LEDs, analog measurement density, oil and gas pressure, temperatures,
instruments, or digital LED bars for the indication of vibrations etc., providing electrical signals or serial
the measured values of voltage, current, frequency, telegrams.
active and reactive power (see Figure 7-6) • Serial communication links if applicable.
Operation at this level means direct manipulation of
A separate control panel operating on 220 V DC
the switchgear (Figure 7-6). With the advent of the
has the advantage that the switchgear can be
unconventional sensor technologies for voltage and
operated even if the controllED is out of operation.
current measurement, electronic sensors are directly
In such an emergency situation the functionality of
located in the switchgear, so that the hard-wired pro
the local con trol cubicle is degraded, i.e. the
cess interface becomes an electronic serial process bus
interlocking and syn chrocheck functions are not
interface (Figure 7-7). A prerequisite for achieving ge
active.
neral acceptance for this new technology is how
ever the availability of a world standard for process
bus communication, as it is coming with the standard
IEC 61850.
74 Process Level
If this kind of technology is widely accepted, then,
The process level comprises: apart from unconventional sensors, also other archi
• Hardwired cable connections to the tectural changes are possible. They range from·-sim
primary equipment. ple remote inputs and outputs to reduce the cabling
up to additional functions incorporated in the sensor
• Auxiliary switches indicating the switchgear
positions. electronics, which support e.g. maintenance and asset
management. These are then called intelligent sen
• Electromechanical control relays with associated sors and actuators, and the whole concept is known
solenoids to transfer the switching commands as intelligent switchgear. 149
into mechanical switching operations, or IEDs
Actuator
for
01
Line
Protection 1
Process
Bus
Phase 1
Q8
Figure 7-7 Bay protection and control with intelligent primary equipment
·
8 Substation Automation Architectures
8.2 8.1 Introduction like electromech_anical relays and push buttons only.
The main characteristic from the system structure
In the previous chapter we looked onto substation point of view is that each function
automation system structures from the switchyard
geography and from the operator location point of • is realized within its own dedicated hardware,
view. Here we will have another look from the up • needs its own inputs and
grade possibilities of existing conventional systems to
typical communication structures, and from the • delivers its own outputs to the
relia bility and availability point of view of these process and to its own HMI (Figure 8-
structures. 1).
II)
...1
c:
0
-
•
i
(I)
G)
>
II) Local
...1
Control
•
m
-
II) -._
...1 GIS or AIS
ttl
ttl
II)
Switchgear
e
( J
0.. -Q1
The advent of the microprocessor in the substation This leads to the following typical structure for IEDs
allows to process data in digital form. Therefore, the (Intelligent Electronic Devices) used at bay or process
data must be converted to digital form, before it can level close to the process (Figure 8-2):
be processed. For all binary data like alarms and switch • An internal bus connects the central
positions this is not a big problem, because this data processing unit (CPU), the needed RAM, ROM,
is already available at (relay) contacts. For analog data EEROM or flash memory and the serial
the analog/digital converters (ADC) are used to con interfaces for communication at one side, and
vert measured values to digital samples. The advan digital as well as analog 1/0 modules at the
tages of providing data in digital form are: other side.
• Digital data cannot be distorted by aging of • An EMI barrier against disturbances and over
the hardware. Data gets and stays much more voltages consisting e.g. of opto-electric couplers
accurate than before. No calibration or testing or separating relays and interposing transformers
is necessary after commissioning. But the super shields the 1/0 from the outside world.
vision of the ADC may be recommended at least
• A local HMI, either built in or via a
fm protection.
serially connected PC allows to
• Data in digital form can easily be exchanged configure_the lED.
by serial communication. This reduces the
former bundles of cables to a thin serial bus, 153
usually in form of optical fibers.
...
·
.,
?
Line bay Process Communication
Interfaces Interfaces
..
y
Bl
..
8.2.1
B O Local MMI
G •
AI
.. [][] ..
Bl .. .. • SA
• SMS
,------1
Bl
• j- ...-, ...
In spite of the fact that a microprocessor is able to The resulting principle system architecture is shown in
perform a iot of functions, some redundancy must Figure 8-3.
be kept in the data acquisition part as well as in the
hard ware performing the functions to assure the
required availability. The data is acquired at the proces's level by means of
remote 1/0 units (RIO) and intelligent sensors and
The ever-growing communication bandwidth makes actuators (PISA= j)ocess )nterface for ensors and
the communication-related problems treatable. The 8ctuators). The process bus connects them to the
new bus technology together with multi-purpose bay level equipment, where the bay related protec
processing capacity allows separating availability issu tion and control functions including the bay level HMI
es from the functional issues, and both can be tai are located. The bay level units talk either to each l_
lored as needed. other or to the station level servers via the interbay
bus. The station level functions implemented on the
This fact allows structuring a modern substation auto station servers talk via gateways either to network
mation system according to the operational needs as control centers or monitoring centers, and to each
it has been described in the previous section, and in other. The station level control unit performs station
154 accordance with the physical layout of the substation. level process related tasks like switching sequences.
External systems
HMI components
NCC
Station level
lnterbay bus
Bay level
/ . .
;··t :. fJ ::-.:\ : Process level
This architecture leads to a high degree of • The bay related control and protection functions as
dependa bility. Functions for lower hierarchical levels well as the safety related functions like station level
are imple mented in appropriate parts of the interlocking are executed on bay level. If the
control system and remain operative even if devices process bus is an internal bus inside the lED and
on higher levels or other parts in the same no external process bus exists, and the EMI barrier
hierarchical level become faulty. Further, the (relays, opto couplers etc.) is internal as well, then
environmental conditions are the harsher the closer the IEDs can directly be connected to the process.
the hierarchy level is to the process, which requires But the devices must withstand the harsh environ
an appropriate physical design of the used ment of a HV or MV switchyard and must be
components. able to be built directly into bay level cubicles
close to the switchyard.
The system is divided into the three hierarchy levels • The process level comprises the connection to the
described already in the previous section: switchyard (the process) via cables from the bay
• On station level there are the HMI and archiving level 1/0s, via remote 110 devices (RIO), or via
functions, and the connections to the external sensors and actuators (PISA) with integrated
world: to a network control center (NCC), to tele electronics, which may additionally contain sqme
alarm systems, remote work places, protection process related functionality. All these devices are
maintenance systems, asset management systems, either located in the vicinity of the switchyard, or
office systems etc Also devices with control func are even integrated into the HV or MV switchgear.
tions covering more than one bay are related to
Each level contains a bus to allow communication
the station level. Station level devices can some
between devices in the same level and in adjacent
times be placed in office type environment, how 155
levels.
ever, for EMI reasons industry versions are often
needed.
',:
'?
'?
8.3 Communication within
the Substation
8.3 • The station bus is mainly used for HMI connec 8.3.1 Design Aspects for Communication
tions to terminals and printers, as well as interface
to office environments, and for the supervision 8.3.1.1 Communication Requirements
tasks between servers.
As already stated by CIGRE [10] and taken up in IEC
• The inter-bay bus connects bay devices to station 61850 part 5, the communication requirements for
level (vertical communication), and additionally communicating functions can roughly be classified
allows real time communication between bay with three criteria:
devices (horizontal communication). 1. Maximum allowed age: the maximum age
allowed for using the data by the (receiving)
• The process bus connects actuators, sensors, function. This corresponds roughly to the
intelligent peripheral units and remote 1/0 units response time and can be considered as a
with time critical real time data to the bay worst-case response time that can be tolerated.
level processing units. This means, that this response time must be
guarantied in normal operation, and that it must
This structuring is also a logical concept. If the data be detected and handled appropriately by the
transmission capacity of the bus used and the receiving function in the rare cases when it can
com munication protocols allow it. several of the not be kept.
logical busses may run on the same physical bus.
2. Data integrity: the degree of communication
Very often, the station bus and the inter bay bus safety in case of disturbances. Here three levels
com munication are implemented on one and the are identified:
same physical bus. Other groupings are possible as
• High integrity is needed, if the
well, if it is required with regard to the scope of
data directly influence the process
functiona lity and if the bus capacity allow this. The
(e.g. a command);
extreme is that all communication runs on one
physical commu nication system. In such a case, • Medium integrity is needed, if the
however, the reliabi lity of the system has to be data indirectly (via a human operator)
analyzed at communica tion system level as well, and influence the process (e.g. an alarm which
very often the commu nication system itself has to leads to an operator interaction);
be structured according to the operational levels • Low integrity can be used, if the
and groupings respectively. As is shown in [6]. even data does not have any influence on
at the current state of 100 MB Ethernet this might the process, like monitoring data used
also be forced by performance reasons. for later analysis only.
One of the special features of a SA system is the 3. Exchange method: Spontaneous means that
pos sibility of accurate station-wide time data is communicated as soon as any change
synchronization, which may even be region wide if happens. On request means, it is only
radio or satellite clocks are used as substation level acquired
time sources. The time master can in principle be if needed by some function or human being iike
coupled to each level. In most cases it is connected an operator or maintenance engineer.
to inter-bay bus level,
and then all devices are synchronized from here via The following table illustrates this classification for
156 the communication system. some typical kinds of data exchanged in a SA System.
Data type Maximum Data Exchange Remarks 8.3.2
allowed age integrity method
Alarm 1s Medium Spontaneous Alarms are urgent process changes
that must be brought to the
attention of an operator, to perform
corrective actions
Commands 1s High Spontaneous Commands directly act on the
process
Process 2 s (binary), 5-1 0 s Medium Spontaneous Gives the operator an overview
state data (measurands) on the process state
Time stamped 10 s Low On request Sequence of event data is used
events for later analysis of a problem
Interlocking data 5 ms (fast block) High (directly influ- Spontaneous Used to prevent dangerous
ences the process commands
via commands)
Interlocking data 100 ms High (directly influ- On request Used for Interlocking to prevent
(state information), ences the process (upon a dangerous commands; or for
other Automatics via commands) command) automatics like load-shedding
Trip from 3 ms High (directly influ- Spontaneous Used to clear dangerous situations
protection ences the process by fault in the
via trips) power system
or in the switch-
gear
The architecture shown in Figure 8-3 allows in One master accesses a lot of slaves. The slave devic
princi ple that each device connected to a bus es are only responding if they are polled, i.e. they are
can com municate with other devices. But a not allowed to send information spontaneously. This
completely free sending of messages from any avoids message collisions, and the master can per
device at any time leads to telegram collisions on fectly determine how the communication bandwidth
the bus, and thus to communication disturbances. is distributed between the slaves respective the diffe
Therefore, the sending of messages has to be rent kinds of data. However, no direct communica
regulated by communication media access tion betweeslaves is possible.
mechanisms to restrict the communica tion access or
allow the handling of collisions. This has a big The Master /Slave mode is the standard mechanism
impact on the possibilities to distribute a function used for the communication of substations/RTUs to a
between the physical devices. The most common network control center, which is the master. In sub
communication modes are discussed in the following. station automation systems, the station level device is
Observe that these modes might be used on link usually the master. This restricts however the com
level for media access as well as on applica tion munication to a data flow between station and bay
level for application communication. We focus here level only. This means further, if the master fails, the 157
on the second aspect. whole system is down.
8.3.7 ced, like Select before Operate for issuing only protection against electromagnetic disturbances,
commands as known from network control but also special care for adequate earthing of the
protocols. cable shielding.
But even if the residual error rate is small enough, In order to avoid earthing problems and to keep the
messages could be lost due to buffer overruns or bit error rate due to electromagnetic disturbances
overloaded routers and switches. Therefore, lost · practically at zero, optical cables are recommended
mes sages as well as the loss of a message source within the switchyard environment Glass fibers can
must be detected. Also here the methods used are cover a distance up to 2000 m or even more in
depen dent on the bus and protocol types. spe cial cases without loosing transmission speed,
while plastic fibers could be used for shorter
What is important and protocol independent is the lengths of some tenth of meters. As plastic fibers
provision of a means that informs an application pro are ageing relatively soon in comparison with the
gram, that such messages have been lost. In the long life of SA systems, it is highly recommended to
stand ards IEC 60870-5-101 and IEC 61850 this is use glass fibers instead for all distances.
realized by the provision of data quality attributes,
which indi cate beneath the invalid flag also a topical
flag to indi cate that the data is up to date. It
8.3.7 The User Benefits Derived from
depends on the application, however, to define
what up to date means and to take actions if serial communication
the data is not up to date. Further, the application
must be designed in such a way that missing or With careful print design, input isolation and device
late information does not lead to an unsafe state shielding, microprocessors and related electronics can
respective that the probability of an unsafe state is nowadays be installed close to the process. Data in
sufficiently low. digital form allows easy serial communication. So dis
tributed systems can be built, which keep the cabling
to the process straight forward and short, and after
wards distribute the data with serial busses
8.3.6 Communication Media
preferab ly in optical form to all places where they
are needed. This new system architecture saves
Apart from the RS232C standard for serial connec
space for cabling as well as for central electronic
tions of modems the industry process busses often
cubicles, which are eith er obsolete or significantly
used the RS485 standard with shielded twisted pair
smaller. The physical signal marshalling is replaced by
cables. Later the Ethernet bus came up using coaxial
the logical signal marshal ling, which means that the
cables to enable higher bit rates. In order to achieve
complexity is the same or even higher. On the other
better HF shielding, higher mechanical flexibility and
hand, the electrical CAD systems are replaced by
multiple connections in one cable, Ethernet has switch
powerful signal engineering tools. The physical
ed back to twisted pair cables. Therefore, communi
wiring and connection work that remains is
cation links for Ethernet with a speed of ;;;:100
Mbit/s are using shielded twisted pairs or fiber optic straightforward and can be executed much faster.
cables only rather than coaxial cables.
Within the substation environment long electrical Another big advantage of general purpose
cables, however, are sensitive against induced high micropro cessors that are capable to perform all
160 transient voltages and currents, which requires not kinds of func tions is that functionality and
availability aspects can
'? ·,
?
8.4 From Remote Terminal
Units (RTU) to Substation
Automation
be separated to a large extent from each other. The centralization of network operation needs remo 8.4
Distributed systems inherently have a 'built-in' redun te access to the substations. In case of conventional
dancy, however system level oriented rather than substation control systems, this is implemented just
function oriented like in a classical system. A failure of by adding a remote terminal unit (RTU) in the sub
a station level unit leaves the bay level functionality station, which takes the needed data from some
working, and a failure of bay level devices just leads marshalling kiosk and transfers it to the network con
to failed functions of the bay concerned, whle the trol center, respective connects commands from the
other bays and the station level functions continue to network control center to some output contacts at
work. the process. The RTU itself has, apart from pure com
munication handling, only the tasks to time stamp
If there are certain critical devices that perform func incoming data, and to assure the safety of outgoing
tions where failure cannot be tolerated, hardware commands by means of 1 out of N criteria super
redundancy can be added as needed. A typical vision and the select before operate principle. So,
example is a duplicated system at station level, while essentially it is just a digital conversion and serializa
all bay level (control) units are single devices. For the tion device.
same reason, duplication of protection devices is very
common at least for HV substations. The advances in microprocessor technology lead also
to more and more functionality of the PLC (Erogram
General-purpose microprocessors even allow that mable Logic ontroller) type within an RTU, e.g. it
different kinds of functions can be performed on the becomes programmable with function charts accord
same device. This feature can be used for new ing to IEC 61131. Advances in communication tech
redun dancy concepts. However, as especially nology lead to distributed RTUs. These typically con
protection is a 'traditional' business, people are used sist of some core device containing the NCC protocol
to the 'one function-one-device' concept and they processing and the PLC functionality, and remote 1/0
do not easily accept the new system architectures cards for binary as well as analog data. Also a direct
that are possi ble. connection of CTs and VTs via analog inputs can be
added to omit separation amplifiers and transducers
The ever increasing communication bandwidth for (Figure 8-4). Thus, the RTU becomes a very basic SA
wide area communication enables direct access to SA system. Nevertheless, its central or master slave relat
systems from remote, e.g. for secondary and/or pri ed architecture normally causes some restrictions to
mary system maintenance as well as for planning its functional capabilities, performance and availability.
purposes, network monitoring etc This new possibi
lity enables different parties or even companies to Therefore, in a complete SA system, the RTU
share this access and to offer various kinds of functio nality is reduced to a station level gateway to
main tenance services. The Internet offers a the net work control center (NCC), which could
widespread and cheaply available communication run even independent from the station level
medium all over the world, under the condition that HMI,thus enhanc ing the overall system availability.
security aspects are solved.
161
'(
i '·
. ...:v
Network Control Center
8.4.2
_.·_..:.f! r.:::_>'::
8.5 The Integration of Protection availability reasons more than one protec tion device is 8.5.1
required like main 1 and main 2 for transmission lines. M
and Control Systems
In the utility organizations protection personnel used to o
be separated from operation personnel. This caus ed t
functions to be separated to different physical i
devices in order to set up boundaries between the
Historically there was one device per function. This not v
various areas of responsibility - even if this is techni cally
only concerns protection and control functions, but
no longer necessary. It was claimed that reliabi lity of
a
different protection functions as well. Numerical relays t
protection is crucial - but this is true for control as well.
lead to multi-functional devices that perform several
i
protection functions in parallel. Only for relia bility and
o
n for the Integration of Protection A third step is the physical integration of control and
and Control protection functions in the same device. This saves cost
and maintenance efforts (one device instead of two), but
The occurrence of protection events - starts, trips, as well
leads to the question whether the protec tion function
as problems with protection devices themselves
reliability is affected by the additional control
- is critical for substation and network operation. So at
functionality sharing the same HW resources.
least protection-monitoring data should be shared 8.5
between operation and protection maintenance.
Therefore the first step towards the integration of
protection and control responsibility is, that monito ring 8.5.2 Safety andReliability Aspects
data needed from the protection units are trans ferred to
Both, for protection and control functions, the requi
the substation automation system by means of serial
rements for reliability and immunity against their envi
interfaces. This minimal form of inte gration is widely
ronment are equally high. This means, that from the
accepted and is supported by the communication
general implementation point of view there are syn
standard IEC 60870-5-103.
ergies that can be exploited by using the same
system platform for both functions. There are how ever
also differences: control does only work. if a command
can be communicated, while a protection device has to
perform its local protection function also, if no
communication exists. Therefore, a protec tion system
must be designed in such a way that disturbances in
its communication subsystem do not affect the working of
the protection itself. How this is achieved, depends on the
implementation strategy.
-- --
._
·. · ·
8.6
to the extent that the protection func tions are
8.6 distributed. They consist of an input/output i
.I
and communication services. This allows an easy sig
processing function part on process level. a
Allo nal engineering by just putting together logical
·proces sing function part on bay level, and an HMI
cati nodes and allocating them to physical devices. The
function part on station or bay level. Those par-s of
Fig. 8-5 gives some examples, how logical nodes
on a function that must be allocated to one physical
can be used to implement functions.
of device and cannot further be distributed are called
logical nodes (LN) according to IEC 61850. One
Fun physical device may host several logical nodes. On
The left column of Figure 8-5 lists several
logical nodes. Each of the remaining columns
ctio the other hand, the same logical node type can be illustrates by crosses in boxes how these logical
ns instantiated on dif ferent physical devices. All nodes are used to implement the functions
functions are implemented in te system by means Synchronized or point of wave CB switching,
of communicating logical nodes. The physical distance protection and over current protection
communication path is provided by the physical (vertii:al boxes). Horizontal boxes indicate the
communication connections between the devices, physical devices, which host the logical nodes.
Most to which the logical nodes are·allocated. We use
of the the term horizontal communication for data The functional specification of the functions
substa exchange between logical nodes in the same defines their implementation by means of logical
tion level, and vertical communication for data nodes and interfaces between the logical nodes;
autom exchange be tween logical nodes on different especially also what kind of data does the client
ation levels. logical node need.
functio
ns are
dis
tribute
d; at 8.6.1 Criteria for the
least Allocation of Functions
Figure 8-5 Functions and logical The overcurrent logical node shouldbe placed at
nodes the bay level, where it can acquire data from the
bay CT and has access to the circuit breaker.
For all common functions in substations the The HMI LN is placed in the HMI device- a
standard IEC 61850 identifies the logical nodes and station level PC, a bay level control panel, etc as
164 their inter face to other logical nodes providing needed.
data objects
'? '? ?
This allocation of the functions into the various levels 8.6.3 Local Control Function 8.6.4
has then to be matched with the physical substation
layout, which reflects the reliability considerations for Local control can be performed from station level,
the substation, environmental conditions, installation from bay level, or directly at the primary equipment.
costs, communication and lED performance aspects For the first two the associated HMI logical nodes
as well as operational considerations. should reside at the relevant levels as illustrated in
Figure 8-6.
8.6.2 Remote Control Function
The remote control function allows operating of the 8.6.4 Local Automation
substation from one or several remote network con
trol centers. The interface to the NCCs therefore resid Local automation can either concern a bay, or the
es on station level. It uses, however, the same control whole substation. The allocation of HMI logical nodes
function parts to perform a control function as used or just of the executing LNs to the relevant levels is to
for station or bay level control, provided that it is al be done accordingly. Examples for general automatic
lowed to do so. The coordination with station level functions are shown in Figure 8-6 on the left, and for
and bay level control has to be provided. a voltage regulator function on the right.
Voltage
Regulator
LN for
station level
Interlocking
on
I VC I
functions Station Level
Automatic
Process Control
means
Generic Node for all
.............undefined functions ,......"'-', Interlocking
LN for on
bay level Bay Level
Tap
functions Changer
Controller
Figure 8-6 Interaction of LNs for the command function and (automatic) transformer control function 165
HMI CBC CB
8.6.5 Safety and Reliability Circuit
Criteria Breaker
From the safety point of view all logical nodes T la interlo
can be classified as follows: h s cking s
i si and a
• Active safety: if the process f
s c blocki
(switchgear) is in an unsafe condition, e
i al ng
8.6. active safety functions clear the fault This t
s t functi
5 is the classical task ot protection. y
t a ons.
• Passive safety: these functions prohibit h s • r
(block) actions, which lead to an unsafe e k N e
state of the process or could cause possible o o l
damage of equipment or endanger people. c f t a
t Sel
ect
e
d
(
Contro j
" l I·
·
circuit
)
for (
a i
.."
:
l
comma
r c
r
nds
e
"
C
Ii
n i
E
o
I
i
Indication
r E
0 for circuit
m (
) breaker
position
a
l
l
y
a
l
l
o
t
h
e
r
f
u
n
c
t
i
o
n
s
.
(active safety) should clear this F
From the architecture point of view it is fault Therefore the logi cal i
important, g
nodes CBC, CB, DIS, and IL u
• that safety related functions can not be have to be regarded as r
safety related, while HMI is e
blocked by other functions,
not safety related, as long as it
• that a single failure e.g. within the needed 8
can not block or affect
resour ces (processor, memory, 1/0 -
otherwise any of the other 7
channels, support functions,
LN's.
communication) of any function cannot
C
lead to unsafe behavior, o
The safety of
also assured commands
by the spe is
• that all logical nodes, which supply data m
m
for safety related functions either to block a
them, or to influence their safety related n
behavior, have to d
be regarded as safety related.
s
e
The Figure 8-6 gives an example: The q
command out put of the circuit breaker u
controller (CBC) is a function that may cause e
n
damages in the process, if it is activ ated
c
wrongly. The interlocking function (I L) e
providing passive safety should prohibit this
to happen at the operational level. If,
however, this happens accidental ly due to cont
interlocking failure, the protection functions ext
as shown in Figure 8-7 A Select command is sent from the
HMI to logical node CBC. The CBC, after checking if a i
command is allowed at all, for wards this select request to I I
the CB lED. After success ful selection of the CB lED the I ·:
Selected response is distributed back Now the operator at !
the HMI is al lowed to give the Operate command, but I
only for exactly the same switch.
8.8 Asset Management Support Short down times are achieved by means of
• extensive diagnostic functions down to
replacement module (circuit board) level with
associated reporting,
• a modular hardware
8.9 Modern asset management systems need condition design,
related data from all primary and secondary equip • fast reconfiguratiqn and restart after repair,
ment in the substation. The SA system allows to • automatic restart after a power supply failure,
acquire such data and to transmit them to one or
• combined with an efficient repair.
several centrally located disturbance evaluation and
c:sset management systems. This means, that this nor
mal data acquisition, archiving and logging facilities of The basic distributed architecture allows very high
the SA system are used for the data acquisition as system availability and functional redundancy for the
well. In cases where maintenance activities are need most important SA function, namely control, even if
ed relatively fast, these may binitiated by means of no explicit redundancy is used. If the NCC connection
dedicated evaluation functions at substation level in function runs on another hardware than the SCS ser
conjunction with the alarming facilities. The open sys ver for station level operation, then only the power
tem features of modern SA systems and the Internet supply modules of a passive star coupler of the inter
based communication possibilities will allow to inte bay bus must be redundant. This assures that there is
grate this data exchange even more into asset and no single point of failure for the control function of
maintenance management concepts. the complete system (although control of one single
bay may tail). Apart from this, all functions are de
The upcoming interfacing standards IEC 61968 be signed for graceful degradation in case that a com
tween distribution automation andmanagement munication connection or one of the connected devi
func tions, and IEC 61970 for power application ces fails. From an overall system point of view, also
functions at network level will accelerate this process. the power supply for the SA system should be redun
The imple mentation of the data exchange into an dant, i.e. by means of a redundant station battery.
open com munication architecture must, however,
be done in such a way that neither the power Even in a non redundant system critical data like com
network opera tion can be endangered, nor the mands and interlocking states are secured for safety
database can be accessed by unauthorized people. reasons by two hardware channels from/to the pro
cess and appropriate information redundancy on the
communication system. These two channels as well
as the timely updating of needed information are
supervised, and a fault leads to an invalid state or
blocking of command execution. Even if a part of the
8.9 Dependability system fails, the system-wide functions can continue
to operate safely, but eventually with restricted
scope of function (graceful degradation). Note that
8.9.1 General such an invalid state or blocking shall only be reset
by human intervention, to avoid that a second failure
All hardware and software components of the can endan ger the safety.
Sub station . .utomation system are designed and
manu factured in such a way that they meet the If a higher availability is needed, then redundant (dupli
high avai lability requirements. This means a high cated) devices or modules can be used. It should
reliability (long MTIF times) as well as short down however be kept in mind that redundancy introduces
times (low MTIR) in case of a fault. (see chapter 12 more hardware, i.e. the overall failure rate and there
for general fore repair activity is duplicated, and that redundant
168 definitions with regard to reliability). devices mostly need some additional, often not re-
.
·
dundant hardware for supervision and switchover. manually. Start up time is in the order of 5 to 1 0 8.9.1
Redundancy can be introduced: minutes, archived data on the failed part, which
• At station level by redundant servers has not been secured, is probably lost.
and • Warm standby: a standby part constantly
HMI devices. super vises the active (hot) component. In case of
• At the inter-bay bus by redundant power supplies a failure it takes over automatically. There is a
and duplicated lines between star couplers and small risk that time stamped events may be lost,
to station level. but all archived data is preserved, and commands
• At bay level by redundant control devices are reusable after 1 0 - 30 sec. If the failed
and several protection devices. system
is repaired and put to standby mode again, its
• At process bus level by duplicated PISAs/RIOs
archive and configuration data is automatically
together with duplicated protection devices. In
updated.
this case each protection system needs its own
physical process bus. • Hot standby: a standby part constantly super
vises the active (hot) component. In case of a
A prerequisite to achieve higher availability is that failure it takes over. No time stamped events are
even inactive redundant hardware parts (spares, lost, no archived data is lost, and commands are
standby parts etc) are regularly supervised and repair reusable after 1- 5 sec. If the failed system is
ed in case of a failure. Experience with electronics repaired and put to standby mode again, its archive
shows that the failure rate on unused equipment is and configuration data is automatically updated.
as high as on normally used (not overloaded) equip In the case of bay devices where the switchover
ment. times are usually below 100 ms, this
switchover is called bumpless.
As indicated below, there are different possibilities
• Duplicated Components: two devices are
how redundancy can be used or which class of
running in parallel (hot). This means: commands
redundancy is needed in the system under the
are always usable at least on one of them. But
consi deration of the length of the down time and
configuration data, event- and alarm lists as well
loss of historical data. The choice depends on the
as archived data may be and mostly are different,
availability required, the functions considered as well
resulting from different operations at the systems.
as the struc ture level. What kind of redundancy is
Further a special management for common
the recom mended will be explained further below.
resources (e.g. serial connections, event loggers) is
• Spare parts: diagnosis and repair of faulty parts needed. The two hot systems may supervise each
inclusive reloading of configuration data by trained other to give an alarm if the other system fails.
people can be done in less than 2 hours in case
of bay or process level devices, less than 4 h for
station level devices. But, the traveling time to site Warm and hot standby systems need a manual
should be short. switch over function to be able to perform
maintenance. This allows a controlled shut down of
• Cold standby: a standby hardware device exists, the hot system and the communication, so that even
which is physically connected and preconfigured on a warm standby system no events are lost, and
(but it may be used for other purpose). In case of the data integrity of the shut down system for later
upcoming is guaran
a failure the operational software is started
. ·
teed.
169
Net Operator
wor Remote
k workplace
cont workplace
rol
cent
er
8.9.2
Hardcopy
Printer
b .F
Alarm/EVent
Printer
Ethernet (TCP/1 P)
:·
Protection
Protection
Unit ·
Unit
It has to be kept in mind, that availability pletely independent from all station level units.
considera tions always refer to the availability of This concept in conjunction with a redundant
a function with in the whole system. This power sup ply in the star couplers (which are
concerns usually the control function, if not other the possible single point of failure in this
functions are specified. Control as a system system) assures a very high availability for the
function is regarded to be available even if one control function. The NCC control io:; functionally
bay has failed, as this has only seldom an redundant to station level control, which is, on
impact on the interlocking scheme. If this the other hand, functionally redundant to bay
would be the case, it could be circumvented by level control. If the availability of control from the
means of the interlocking override function. NCC is an issue, then installing a separate
remote work place at the NCC, which is directly
connected to the SA server, could enhance this.
This workplace can be used e.g. over the
8.9.2 Functional telephone network in case the NCC server
Redundancy connection is disturbed.
The Figure 8-8 shows a single SA system, where The separate protection devices, which are
the SCS server and the station level HMI use connect ed to the NCC server, are not relevant
another hardware device than the NCC server. for the control function, they are however not
Both servers are completely independent from available if the NCC server fails. Usually, remote
each other, al though they supervise each control is the more impor tant function. This is
170 other. Further, the interlocking function across the reason why they are connect ed to the NCC
the interbay bus is com- server.
. '-?
In case that the station level operation is most impor
tant, they might be connected to the SA server
instead.
if both lines are working. is not so important, a duplicated hot-hot system 171
8.9.3.
3
can be applied. This allows to have different
confi gurations on both servers, e.g. for
testing configu ration changes/extensions or
new functions only on one server, while ! ...
operation is performed by
the other server. The process database on both
172 although eventually .with reduced accuracy. If a
systems is always up to date, so that in case
high accuracy across the system is needed to
of a shut down of one server the other one
fulfill its func tionality (e.g. for distributed
can continue giving commands without
synchrocheck), then a second bus master
interruption. The management of common
clock should be used. If high accuracy
resources like disturbance archive, NCC
against absolute time is mandatory, even the
connections, event log printers etc must
satellite/radio clocks themselves should be
however be specified and engineered on a
per project base. Archives may be different dupli cated.
(although equivalent) even if both systems
are operating, and holes in one archive
during shut down are not automatically filled 8.9.3.3 Inter Bay
on system startup. Event lists are different, Communication
because e.g. commands and alarm
acknowledges are logged only on the The behavior of inter bay communication
executing system, and opera tional depends a lot on the type of bus that is used,
parameters like measurand limits and dead and how it is phy sically implemented. The
band may be different if they are following example assumes that the
interactively changed during operation of communication network distributes messa ges
the system. only on physical level. Schemes with redundant
communication might have to be designed
• In case of HMI devices like terminals and different ly, if the physical network includes
printers always duplicated components shall switches and rou ters, which are also complex
be chosen. electronic devices. An appropriate example is
If more than one physical device (PC) exists, shown in Figure 8-13.
pre ferably an HMI terminal should run on
each of them (e.g. one on the hot system
and one on the standby system). Additional The inter-bay communication scheme
terminals can be added as X-Terminal devices discussed below consists physically of star
at the station bus. The supervision of the couplers that inter connect the bay and station
HMI hardware like screen, keyboard and level devices by means of optical links (Figure
mouse has to be done by the human users. 8-9). Within the passive star couplers the
physical bus consists of wires with an
availability of practically 100 %, and for each
The Figure 8-9 shows a standard connect ed device there is one opto-electrical
configuration, where NCC server and SCS server converter. So the common points of failure of
are running on the same physical server. The the star coupler are:
redundancy is configured as a hot standby
• The power supply. This can and should
system. Therefore each physical ser ver is
be duplicated, and (if possible) each
connected to an alarm unit, the master clock,
power supply supplied from another
and with a fall back switch to the NCC line and
power source.
to the serial communication to bay devices
with master slave protocol. Printers and a third • A common mode failure of the
HMI are connec ted to both servers with the opto electrical converters to the
station bus. This means that the printing bus. This probability can be neglected,
function is not redundant, but has a high if the couplers are carefully designed.
reliability, as no (electromechanical) switches are
used. The redundatlcy of the time • A failure on one line (e.g.
permanent
synchronization is assured (except for the
light), which blocks the whole star
satellite/radio clock itself), because the SCS
coupler. This is prevented by appropriate
server can take over synchroniza tion in case
design of the star coupler converter
that the inter-bay bus master clock fails,
modules.
8.9.3.5
The optical glass fibers have practically an availability a main1, main 2, and backup protection. This practice
of 100 %, unless they are endangered by a special results not only in physical but also in functional redun
environmental aspect like frequent construction work. dancy, if different protection algorithms are employ
In such a case the links to the station level devices ed for the main 1 and main 2 protection.
and betvveen star couplers should be duplicated and
laid in separately routed cable channels, and they
8.9.3.5 Redundancy on process bus
should be supervised to detect interruptions.
If a process bus is used, it should be redundant, in
8.9.3.4 Bay level particular in case of redundant protection, and also
The usage of redundant control units is possible, al
the most critical PISAs (for a,
VT and circuit breaker)
should be duplicated. A simple way is to provide a
though in most cases not necessary. A functional
dedicated process bus and dedicated PISAs for each
redundancy (e.g. emergency circuit breaker control
bay device together with redundant bay devices.
with use of protection devices) is sufficient in most
More sophisticated ways of how to achieve redun
cases, if redundancy is needed at all. Apart from this,
dancy depend on the process bus type.
a possibility for either direct switchgear control or a
backup panel can already provide the means for If redundancy on PISA level is considered, then the
emergency control. failure rate of the PISA has to be compared with the
failure rate of the sensor. Often the PISA electronics
Redundant protection, however, is necessary at least has a much higher reliability than the sensor. Then
on HV transmission level. On the functional level this redundancy makes only sense if also the sensors are
means the usual duplication of protection device as duplicated. 173
Network Control Center
Nc' ·' ( wr
.- . - serveF·
8.9.3.6
-;;;-
P rot
-
ectio n
*) it should be noted that with the fast increasing use of switches in industrial applications, the MTIF will be improved
continuously.
• All 749 999 hours (= 65 years) a repair has • MTIF with repair: 8
to be performed. years
• If the repair can be made within an a mean • Availability: 99.9887 %
time to repair (MTIR) of 8 hours, the MTIF with
In case that fibers could be damaged, or faster
repair that can be achieved is
aging plastic fibers were used, this would have to be
321 065 years.
taken into consideration accordingly.
• The corresponding availability with repair is
NCC gateway single
99.99999999 %. MTTF(h):710n (y): 8.113858180MTTF for repair(h): 71077
MTTR(h)8.0 MTTF(y) with repair: 8.113668881
Availability(%): with repair: 99.98874566 no component repair: 99.98874593
opt.connection NCC Server NCCModem
• If a repair is only done in the case the system MTTF(h):11750000 MTTF(h)251000 MTTF(h)100000
Bus system
Table 8-4 shows the availability figures for the HMI
MTIF(h)3000000(y): 342.4657534 MTTF for repair(h): 749999 part, which consists of the SA server and the HMI
MTIR(h)8.0 MTTF(y) with repair: 32106512.61
Availability(%): with repair. 99.99999999 no component repair. 99.99973333 console, and is connected to the star coupler similar
star coupler PS [ as the NCC server above:
MTIF(h):1500000 r
• MTIF with repair: 7 years
star coupler PS
• Availability: 99.987 %
MTIF(h):1500000
175
· '?
The Table 8-5 shows the availability figures of bay • The second one, MTIF with repair of 8 years,
control units (BCU) which are also connected via the is the resulting system MTIF, if any failure is
optical fibers to the star coupler: repaired within in average the MTIR of 8 hours.
• MTIF with repair: 90 • MTIF between any repairs 26239
years hours
• Availability: 99.99899074 % = 2.99 years
8.9.3.6
A
Control ProteCti<).ri
Protection BayN ····.··
Bay1
Bay 1
Remote
•:Jt
I .? F:t"t'
HMI :··
Modem
L_Telephone networ1<
Aif Modem/
NCC (GW)
server
:a ;mA-r
C
server t m- ·· '
Star coupler
45
Control
Protection
Bayt
• Bay;1
It is assumed that this is PC based, having the • MTIF with repair: 47359 years
same MTIF as the SCS server with HMI and two
• MTIF for repair: 1.63 years
modems. The resulting availability figures are
indicated in Table • Availability: 99.9999807 %
177
8-8.
=ingle Sys, rem.HMI
MTTF(h): 130945 (y): 14.94816226 MTTF for repair(h): 14286
MTTR(h): 8.0 MTTF(y) with repair: 47359.69576
Availabilily(Ok): with repair: 99.99999807 no component repair: 99.99389098
Remote PC+Modem
MTTF(h): 61000
CC gateway single
MTTF(h): 71077
Table 8-8 Availability figures with redundant NCC workplace for control
As can be seen, this measure changes the availability Due to the relatively low MTIF of the serial switch the
figures only marginally, but it provides genuine redun overall availability of control from NCC is much lower
dant remote control. than for the system with remote HMI above. On the
other hand, there is also only one communication line
The calculation in Table 8-9 is made for a system required. This example shows the high impact of com
where both, NCC server and SA server run on the mon/voting equipment in case of redundant com
same but duplicated computers (Figure 8-11). A seri munication. The provision of either a more reliable
al switch and a modem are used at each server but switch or a second communication line to avoid swit
the NCC connection between the two PCs has to be ching can help to obtain reliability figures that are clos
switched over. The resulting availability figures are: er to the above ones.
• MTIF with repair: 23 years
Only a slightly higher availability could be achieved if
• MTIF for repair: 1.42 years
the HMI part (screen, keyboard etc.) or the modems
• Availability: 99.99599444 % would be switched (e.g. by manual plugging) bet-
=
MTTF(h 901 (y): 5.924858153 MTTF forrepair(h): 12498
MTT h :8.0 MTTF(y) with re air: 22.79846674
Availa · ): with repair: 99.9 9444 no component repair: 99.98458863
Bus em Serial Swtlch HM arts Modem
BCUll
MTTF ):839285 MT F(h): 9 MTTF(h):100000 -
MTT (h):3000000 MTTF(h):200000
(n-1)o n: 18
178 Table 8-9 Availability figures for SA and NCC server on the same but redundant PC
Network Control Center
q;_
NCC(GW)
server - : scs serJci' 8.9.3.6.1
Switch
...... Switch.'
A••I'W'Switc h -- • ., {witc_..h.).liiii.-
'Proteeti.on
--Bay 1..
Control
Bayl
...... Protection
Bay N
coiiff6i
Bay·N_ -
Figure 8- 7 3 Ethernet ring configuration
ween the two computers. An automatic switching from the availabiiity modeling point of view, this is
would further reduce availability due to the common similar to a 1 out of n BCU configuration plus
component switch at the lower layer, and PC plus switch at
the station layer The protection IEDs are disregarded
for the con trol function. A bus system as such is,
however, no longer needed, as all communication
goes around the ring, which is regarded as faulty
8.9.3.6.1 System availability for Ethernet
only if at least two switches ha;e failed (1 out of n
based station level
of Bay).
communication equipment
179
'?
'?
with the substation and often also a station level HMI
with the distributed 1/0 units (Figure 8-4).
=_Sv.ltem, rem.HMI
MTTF(h): 95102 (y): 10.85641651 MTTF forrepair(h): 8873 devices, which corresponds to the number of the
MTTR(h) 8.0 MTTF (y) wilh repair 7379 092508
Availability(%): wilh repair. 99.99998762 no component repair. 99.99158870 bays of the SA systern.
SCS se!Ver+SwOCh SYS500MMI
BCU+Swil:h MTTF(h): 157680 MTTF(h) 87600 In view of the high processing power required at the
MTTF(h):
(n-1) ofn: 18
central part. we assume a higher integrated device
with more electronic chips and therefore -regard the
Remote PC+Modem
MTTF(h): 61000 MTIF by 25% lower than for a bay unit. For the dis
tributed 1/0 units that are simpler we assume a 25 %
E_NCC gateway
higher iviTTF. Further, we assume point-to-point opti
MTTF(h): 61473 cal connections to the distributed 1/0 units. This might
not be practical for 20 or more connections, but it
leads to better reliability figures than if an additional
Table 8-11 Availability figures of a complete system central star coupler or switch was implemented.
including communication availability
Vlo unit+oflt.
MTTF(h) 020565
RTUbase
MTTF(h)650000
Modem
MTTF(h):l 00000
(n-1)ofn: 18
Table 8-7 3 Availability figures for a redundant control via NCC and local HMI
The RTU system with redundant control via NCCI Further for the comparison of the architectures it was
modem and via local HMI. not considered how the synchrocheck functionality is
• MTIF with repair: 74 implemented in a system with distributed RTU. Very
years often one central device is taken for synchrocheck,
which is then switched to the relevant CB that has to
• MTIF for repair: 2.5
be closed. This synchrocheck device would, however,
years
introduce a further single point of failure, which does
• Availability: 99.9876 not exist in a distributed SA system, where the syn
% chrocheck function runs on each BCU or protection
device.
If we compare RTU based systems with an SA system
that incorporates functional redundancy, we find that
the MTIF of RTU based systems without repair is
slightly better (13 years instead of 12 years), but the
MTTF with repair is drastically lower (74 years
instead of 30903 years) due to the RTU base
being the one single point of failure.
8.10 [1] G. W. Scheer, D. A. Woodward·Speed and Reliability of Ethernet networks for Teleprotection
and Control, Schweitzer Engineering Laboratories Inc (SEL), 2001
[2] G. W. Scheer, D. J. Dolezilek ·Comparing the reliability of Ethernet network topologies in Substation
control and Monitoring Networks, Schweitzer Engineering Laboratories Inc (SEL),
(Western Power Delivery Automation Conference 2000, Spokane, Washington), 2000
[3] L. Andersson, K.-P. Brand, W. Wimmer · The impact of the coming standard /EC67850
on the life cycle of Open Communication Systems in Substations,
Distribution 2001, Brisbane, Australia, November 2001
[4] L. Andersson, K.-P. Brand, W. Wimmer · The communication standard IEC67850 supports flexible
and optimised substation automation architectures, Integrated Protection, Control and Communication
Experience, Benefits and Trends, Session IV - Communication for protection and control.
(pages IV-17 to IV-23), New Delhi, India, 10-12 October 2001.
[5] T. Skeie, S. Johannessen, 0. Holmeide · Highly Accurate Time Synchronization over Switched Ethernet
In Proceedings of 8th IEEE Conference on Emerging Technologies and Factory Automation (ETFA'01),
pages 195-204, 2001.
[6] T. Skeie, S. Johannessen, and C. Brunner· Ethernet in Substation Automation, IEEE Control Systems
Magazine, 22(3): 43-51, June 2002
[7] K.-P. Brand, K. Frei, 0. Preiss, W. Wimmer ·A coordinated Control and Protection Concept
Medium Voltage Substations and its Realization, CIRED 1991
[8] 0. Preiss, W Wimmer · Goals and Realization of an Integrated Substation Control System,
DPSP&C 1994, Peking, 1994
[9] EWICS TC7, Dependability of critical computer systems, Elsevier Applied Science, London, 1988
[10] CIGRE - Technical Report, Ref. No.180 · Communication requirements in terms of data flow
within substations. CE/SC 34 03, 2001, 112 pp. Ref. No
182
. ·
9 Asset Management Support
183
9 Asset Management Support
9 Asset management in the broadest sense is the opti management support discussed in this chapter is
mal management of all assets of a company accord focused on:
ing to the company goals. In this book we consider
transmission and distribution (T&D) utility companies, • The power system
and restrict to the assets necessary to supply power • The protection system
to the utility customers, i.e: • The SA system
• The power network consisting of lines and
substation primary equipment The task of utilities is to supply power. The focus of
• The protection system the detailed company goals might change due to
deregulation. Government owned utilities put the
• The network control system
focus on reliable power supply, while privatized utili
• The substation automation systems (SA) ties will focus rnore on return on investment The
asset management policy is influenced by the com
The protection system can be seen as part of the SA pany goals, policies and resulting strategies.
system, and the network control system is outside
the scope of the book, but its asset character may be Figure 9-1 tries to give an overview on the depen
treated similar as the SA system. Therefore, the asset dencies between utility activities to illustrate the diffe-
L I
t
Maintenance
really necessary. This is called detective main- on a time-driven basis (scheduled maintenance) with i_.
An examples with fictive figures might illustrate this: Power system monitoring in a narrower -sense
A power line in the transmission backbone is critical addresses faults and problems in the network. As
for the whole power flow. A loss of the line might these are often cleared by the protection system, and
cause costs of 500 k$ per hour due to not delivered this also delivers necessary data, it is often also
called protection monitoring, although it
additionally delivers power system problem
diagnosis data like
power and penalties. Preventive maintenance increas- fault locations on a line. 187
9.3.1 Data acquisition • Disturbance recorders
• Event recorders
The trend within data acquisition goes to intelligent
• Statistical value evaluation
electronic devices (lED) for protection or control.
Besides their primary functions, they host more and • Power quality analysis
more additional functionality. Many of these additio With computing power making its way into the pri
9.3.1 nal functions provide a sound foundation for basic mary equipment together with new sensor techno-
monitoring systems, are cost-effective and may com
prise (Figure 9-2):
logy, high voltage equipment can be made available to • Switching currents
more the outside at reasonable costs like • Manufacturing data
and
• Switching counters • Original value of key performance criteria
more
intern • Thermal information
al • Quality of isolation media This kind of data is the source of valuable condition
data information and exploited for building up condition
• Timing curves of switching operations
from monitoring.
. ...,
_ _
'>.olli .. IT o oe '•· ,.. 1 • '- .,.. '"" o •
•••t•
II
Uo0• :>"',"' •
!Advanced analysis
f.
:tools
; ,.,_ .11
j,
,
1:
188 Figure 9-2 Typical example of data acquisition from various lEOs in a substation
Event printer
9.3.3
......................................
Star coupler
lnterbay-Bus
9.3.2 Substation monitoring changes Monitoring systems are scalable solutions ranging
data into information from single IEDs respective an add-on communica
tion kit for existing single IEDs up to complete stand
Substation monitoring systems are often defined and alone systems with one or several PCs for decentra
understood as functional and even physical subsets lized as well as centralized data evaluation and failure
of substation automation systems, with mostly the analysis. It archives the data which is collected from
control functionality not being included. This is how the IEDs like numerical protection devices through a
ever a rather restricted perception that does no justi substation wide bus. A typical structure of a local
ce to the importance of the monitoring applications, system (i.e. within a substation) is shown in Fig. 9-3.
and neglects the currently growing interest in The data is presented after analysis on dedicated
condi tion monitoring applications as well as the SMS operator displays (Figure 9-2).
increasing need for business related information.
Therefore, a more general definition of monitoring is
better suited to describe the state-of-the-art 9.3.3 Disturbance recording for fault loca
monitoring approach: tion and power quality assessment
Substation monitoring is a station or network mana In the last decades, the power systems have been
gement technique, which exploits the regular evalua monitored in order to be able to determine the exact
tion of the actual operating condition, in orderto type of fault, to find the proper ways to clear the
minimize the combined costs of power transmission/ faults, and to check the reactions of the protective
distribution operation and maintenance. devices. This was mainly done for reporting purposes,
i.e. extracting the exact picture of the fault. to include
This means effectively, that it might cover condition these data in reports. Another goal for this
monitoring as well as protection system monitoring monito
at least at the concerned substation. ring system was network engineering oriented, that is 189
'( '?
'( '?
improving the theoretical models of the
electrical net works, thus studying the
appropriateness of the "cal culated behavior of
the network" against the "actual behavior of
the network".
These monitored data was used as well in issued to the public This is particularly true
9.3.
litigation context, where the responsibility with the deregulation occurring on the
3
between several actors in the electrical markets, where legal interfaces have to be
networks was to be looked into for cost defined to more than one actor in the Energy
assignment in particularly severe conse quences market.
of faults on the electrical network. In some I:'
cases a very accurate analysis of the fault was When a disturbance record file is uploaded
requir ed to know the exact values of the from a fault recording system, it can
electrical para meters just before the faults, to automatically be evaluat ed and the result of
see whether such piece of equipment was the analysis printed in the form of a "short
right to have failed to work or not. fault report': and faxed to the protection
engineer (Figure 9-4). This kind of automatic
With the power quality concerns, the goals are fault location and analysis even helps to bring
diffe rent. If the use of the data for internal the system faster back into operation. Under
engineering purposes are still valid, a new a fault recording system we understand here a
approach is to evaluate the level of quality of system with dedicated recorders with mostly
the electrical supply, giving information on higher resolution than those integrated in
which legal contractual agreements can be protection devices.
based upon, and providing data which can be
i-
190
9.3.3
Figure 9-5 Central retrieval and evaluation of event and fault records
SMSSystem
r--M-o-de-m'-----,1-A
Functionality Station SMS
I
I • Summary reports
I • Device HMI
• Data Transfer (on request, automatic,
Data Compression)
• Collection of Disturbance Record files
from Foreign devices 191
c '
: I
9.4 9.3.4 Power system condition assessment connections can be set up on demand by the
for better knowledge center, i.e. via modems, and therefore do not need
perma nent connections like an NCC. But also other
Precondition for condition based maintenance is to kinds of wide area connections like routed packet
know more about the equipment, its load, and switched networks are possible.
the operation conditions. For this many data has not
only to be gathered, but also to be evaluated, What the Figure 9-6 does not show is, that from the
correlated, and after evaluation some configuration central system the evaluated data is again distributed:
data in the system to be modified. A central power to office work places via intranet LAN, or to mainte
system moni toring therefore offers some or all of nance personnel via mail. fax, SMS, pager etc
the following features (Figure 9-5):
• Protection related information as input for
protection system supervision and fault location '
I
• Direct access to substation monitoring
and automation system supervision data
• Parameter setting from remote 9.4 Monitoring of Substation
• Assessment of power Automation System
quality
• Historical data base for enterprise resource
planning 9.4.1 Different levels of monitoring
• Visualization of critical areas via geographical
information system (GIS) The Substation Automation System or any dedicated
Monitoring System is supervising both the phenome
• Identification of weak spots in combination
na in the power network and the allocated
with lightning data base
switch gear. These phenomena may require fast
• Support of maintenance and asset management response by protection or automatics, or actions by
systems the opera tor e.g. an acknowledgement of the
related alarms. They also produce non time-critical
The results of monitoring systems are not needed for
data for mainte nance and planning.
direct power system operation, but more for
mainte nance and planning. Therefore they are often
The loss of the substation automation system would
gather ed separately from the network control
have a severe impact on the operation of the power
centers, al though some of their data should also be
system. Same holds to a much larger extent for the
correlated with data gathered in network control
network control and management system. The deg
centers.
radation of monitoring systems would affect the
Therefore, typical Power system monitoring (PSM) asset management and cause problems at least mid
term.
systems might look like Figure 9-6.
Highly sensitive components should be duplicated to
Local SMS systems, substation automation systems,
avoid that a single failure can block the functionality
or even directly protection devices or disturbance
recording systems are connected to some central
192 place via wide area connections. These wide area of a complete system. The redundancy of campo-
nents is however limited both because of costs result will be an input for the utility
and technical feasibility for reliable switchover. Apart asset management system.
from this, the increased quantity of redundant
devices would decrease the mean time to failures In the following two sections, the
(MTIF) for repairs in the system. As is shown in basic monitoring procedures for
chapter 8, the decrease in availability is, however, systems are explained.
relatively small if the failed component is not
replaced as fast as pos sible (see system MTIF
without repair in contrast to MTIF with repair).
Therefore, all these systems have to be supervised
carefully to detect any degradation in time. The
9.4.2 Self-supervision of devices (EMI). Reliable and often redundant power
supplies contribute to the robustness of lEOs.
Each intelligent electronic device (lED) has a lot of interacting
components. The design should be made in such a way that all
components have a high MTIF, and that the complete
arrangement is insensitive against electromagnetic interferences
9.4.2
193
! i
·
9.4.4 Nevertheless, self-supervision is necessary. AJD con • Self-supervision of communicating devices
version that might be subjected to aging should be • Supervision, if all nodes in the
supervised by means of a reference signal. Watch communication network are still operative and
dogs should supervise the response times from pro responding
cessing algorithms. If memories are used for the
sto rage of data, checksums should be used to • Detection of errors in telegrams at least on
detect any failure. Loss of power supply should be the receiver side
monitor ed as well. The question, how many • Supervision on communication overload and
percent of the device should be covered by self- acceptable response times
supervision, is very academic A typical example for • Counting of lost messages and detected errors
self-supervision of an lED is shown in Figure 9-7
In Table 9-1 the MTIF for the JED is in all cases assum
ed to be identical, i.e. 50 years, to see the effects of
self supeNision and remote supeNision. It is further
assumed that if no supeNision is done, then failures
are only detected in the course of periodic mainte
nance every 6 months. This leads to an average error
detection time of 3 months. In the case of JEDs with
self-supeNision, but no remote monitoring, the MTIR
is assumed to be 3 month, as the periodic inspection
time has to be added to the delay of repair. Apart
from this, the error detection time of the self-super
vision is assumed to be 1 hour. Any delay in commu
nicating this by remote monitoring is within the 24 h
MTIR. It can be seen immediately that the self-super
vision alone mainly enhances the· safety. In order to
obtain a similar degree of improvement of the availa
bility, at least daily supeNision is necessary in addition.
And it should be kept in mind that the availability
of protection is the security of the power system.
195
9.5 References
9.5 [1] F. Engler, A.W. Jaussi · Intelligent substation automation - monitoring and diagnostics in
HV switchgear installations, ABB Review 3/1998
[7] V. Lohmann, I. De Mesmaeker, B. Eschermann · New Maintenance Strategies for Power Systems
supported by Substation Automation, Cigre Conference June 1999 in London/UK
[8] V. Lohmann, 0. Preiss · Less Impact of Power Failures Due to Substation Automation,
CIRED Conference, 1999 in Nice
''
196
10 New Roles of Substation Automation
197
. ·
10 New Roles of Substation Automation
10 10.1 Impact of the Deregulation ness that continues to develop new technology to
meet the demand for more electrical energy. The
of the Power Industry engineering decision-making process now must con
sider, in addition to engineering and financial issues,
Over the past decade the electricity supply
the impact on the local and global environment in the
industry has been subjected to dramatic changes.
form of environmental studies and life-cycle assess
World-wide the trend is to restructure vertically
ments. Consumers now regard electricity as an essen
integrated utilities catering for generation,
tial ingredient to improve the quality of life, and the
transmission and distributions into smaller
industry faces the challenge of satisfying the demand
"unbundled" companies. The new plant owners are
for energy in a manner that has minimum impact on
pushed to minimize costs through great er utilization
the environment. The large interconnected national
of existing assets. This can be achieved by reducing
and international transmission systems that bridge
operating security margins. As a matter of fad, this
geographical and political boundaries continue to offer
new operation philosophy is enabled by the rapid
the opportunity to optimise and share the use of
advances, which are made in the field of digital
energy efficient resources.
technology applied for protection, control and
communication. These developments drive significant
In the increasingly competitive arena there is signifi
changes in power system management, substation
cant pressure on power providers for greater syst_em
automation and broadband communications.
reliability ard improvement of customer sat1sfad1on,
while similar emphasis is placed on cost reduction.
Various aspects of the utilities needs have been dis
These cost reductions focus on reducing operating
cussed in the Cigre 99 London Symposium on the
and maintenance expenses, and minimizing invest
subject: 'Working Plant and Systems harder'Enhanc
ments in ne.v plants and equipment. If plant invest
ing the management and performance of plant and
ments are [CJ be made only for that which is absolu
power systems is being addressed widely at many
tely necessary the existing systern equipment must
international conferences. The overall conclusion per
be pushed :o greater limits in order to defer capital
ceived is that there are a lot of new technologies
investments
available, which will help planners and operators to
find new solutions to maxirnize the use of the power
systems and adapt to the fast changing environment. 10.1.2 Working Plants Harder
Enhancing Lhe management and performance of
10.1.1 Reshaping the Business plant and power systems is being discussed widely at
many interrational conferences. The overall conclu
The final decade of the 20th century saw sion perceived is that there are a lot of new techno
unprece dented changes in the structure of the logies available, which will help planners and opera
electricity industry as the "deregulation fever'' tors to find new solutions to maximize the use of the
spread around the globe. With deregulation of this power systems and adapt to the fast chanqing envi
historically con trolled market, shareholder and ronment.
customer interest became a key factor in the
competitive free market as corporate officers traded The innovations which can be developed and imple ..i
unbundled business sec tors internationally for the mented to enable to work the system harder include i
highest stakes. These board room-level issues have
overshadowed the ever
198 changing responsibilities for the engineering busi- the following:
• Better modelling and more detailed technical of power system pr
analysis. Using these techniques it is often conditions are vital. es
possible to assign enhanced ratings to • A reduction in the timescales in su
transmission equip ment, and hence increase which the control engineer can re
system power transfers. act. To this end better alarm cata s
• Better analysis of system conditions. As a result analysis is required, together with to
of increased power transfers across the system automatic instead of manual re
there is a reduction in operational "margins for actions. du
error'. This means that accurate prediction and ce
analysis In addition to the pressures to "work th
the system har der:there are also e
overhead costs of the system operation function.
.
This implies a need to use more efficient
working practices, for example telecommand and
sequence switching and extensive automatic ·
voltage control equipment.
I .
10.1.2.3 Real Time Network
Analysis
The real time network analysis (RTNA) is an
invalua ble tool for the control engineer,
especially if the system is being operated at or
close to its limits. Whilst off-line studies give
accurate results they can never fully reflect the real
system because of such factors as demand
estimating errors, changes to the scheduled
generating plant and transmission system
reconfigurations. If real time data is used the
RTNA can, in certain circumstances, give significant
enhanc ements to system capability. The quality of
the state
10.1.2.3
199
10.2 estimation using the RTNA depends on the accuracy All of them have become great enabler with regard
of the existing metering and the representation of to new business opportunities, challenging market
adjacent and lower voltage systems. needs and new requirements, in view of the fad
that the pressure on utilities for cost reduction and
1 0.1.2.4 Post Fault pro ductivity improvement requires new concepts for
Actions • Energy management and power system
management
Frequently it is necessary to identify post-fault actions
such as re-switching a substation or rapidly reducing • Substation automation
MW generation to mitigate the consequences of cre • Feeder automation
dible system faults. Utilities specific procedures spe
cify maximum numbers of actions considered per However, for working plants harder the moderniza
missible within a given timescale. Generally, manual tion of exiting substations is a prerequisite. In addition
actions in less than 10 minutes are not considered to this, utilities will in future need more comprehensive
feasible. If these actions could be carried out auto service and support.
matically then the timescales could be reduced, which
allows greater short term ratings to be utilized allow 10.2.2 Efficient data exchange for
ing system transfers to be increased. Certain up-to-date information
automa tic schemes are often installed but these
only cater for a small number of eventualities. Also, The prerequisite for the provision of up-to-date criti
these sche mes tend to be hard wired, inflexible cal operating information to engineers and account
and expensive to install. Advanced automatics may managers is an efficient communication network. This
overcome these limitations in the future. must be capable not only to support remote control
from network control centers but also retrieval of
data on loading, interruptions, voltage disturbances,
and other electrical events from all substations
10.2 Motivation for Modernizing throughout the utility service area for the protection,
maintenance and planning departments.
Substations
It is recommended to split the communication system
10.2.1 Contribution of IT to Provide into two partial networks:
New Opportunities
1. Real time communication between the network
Over the past thirty years the following key technolo control centers for supervisory control and data
gies and marketing developments have affected the acquisition (SCADA) and energy management
entire electric power transmission and distribution systems (EMS) as well as between the various
world: substations for control actions:
····power ·Power,
·fio l'er · . Consumers
Distribution ·
Transrriission ill
AI
The objective of the Advanced Power System titude of proprietary communication protocols that
Management (APSM) concept is the optimization of
the power system performance in tf'rms of reliability
and availability at minimal operation and maintenan
ce costs.
. ·
• PC human machine interface (H'/11)
with all necessary software, drivers,
net:lork managment.
• Local Area Network (LAN) with
:lterfaces for all IEDs Programmable
logic contro er (PLC) and remote
The estimated costs to provide fud substation 1/0 modules.
auto
mation for this arrangement would range from • Full compliment of IEDs with
$100 000 to $200 000 and induce pr;'ilary and secon dary protection
schemes on all r-ajor equipment. For
most economical arrangemeIEDs
are
located nearest to the eqipmenc :hey • Full drawing management software package
protect. for all substation physical, schematic, wiring,
• Transformer management sense'S and arrange menand other technical drawings at
software. the site with as built changes, forwarded to
drafting for revision and returned to the
substation via included wide area network
10.2.4
management software.
• Full system configuration,
tesinstallation, documentation and
commissioning.
It is obvious that the benefits exceed the
implemen tation costs for new substation
construction. The esti mated implementation
costs may vary according to the level of
redundancy required and conservatism with
respect to the use of traditional mimic style con
trols. The least cost system will locate lEOs
nearest the controlled equipment and use only
one HMI (PC).
. ·
10.2.5 Cost comparison SA versus
conventional
The costs benefits as per section 1 0.2.4 refer to the
following cost structure for conventional protection
and control of a typical distribution 138/15 kV sub In this specific case the estimated costs for SA are
:0.2.5 station with 6 feeders 138 kV and 12 feeders 15 kV smaller than indicated in the Graph 10-1.
[1].
The main savings are achieved with the following
Cost Items % cost items:
Control Panels 16 • Wiring substituted by fibre optic cables
Protection Panels 8 • Less cable conduits
Metering Panels 2 • Annunciaters and fault recorders are
Feeder Protection Relays 9 integrated in the IEDs for protection and
Cable Conduit 5 control
Wiring 13 • Reduced space requirements for the control
Control Building 9 building
Remote Terminal Unit (RTU) 13 • RTUs are no longer required
Fault Recorder 8
Sequence of Event Recorder 6 The cost benefits for SA compared with transmission
I i
Annunciator 2 substations of 245 kV, 420 kV and 525 kV are even I ;
more significant due to the vast space requirement I I
SAT. Commisioning 9
and the large amount of wiring and cable conduits
Total costs 100 required as shown in Graph 10-2.
Table 7 0-3 Cost splitting of conventional control and The comparisons of the installation costs reveal that
protection for a 7 3817 5 kV SIS SA is the most cost effective solution in every case.
Graph 7 0-7 Cost comparison between conventional control and protection and SA for a 7 3817 5 kV SIS
1'800'000 10.2.7
1'600'000
1'400'000
1'200'000
0 1'000'000
(/)
800'000
600'000
400'000
200'000
0
115115 k\1 2451123 kV 420/123 kV 525/123 kV
With higher system voltages the impact of the instal to fully automated substation environments will inclu
lation cost for conduits and wiring becomes the main de metering, protection, SCADA, and maintenance.
. '
driver for the steeper increase of the installation costs. These groups have enjoyed the autonomy associated . r
SCADA/EMS
• System operation Utility Back office f
• Energy Management • Engineering
• Power Quality • Planning
• Maintenance
206 Figure 7 0-2 Nine upgrade steps towards advanced power system management
·
'(
:
into substations, the same engineers may be rather be based on a busi ness pull and . '
suffering from data overload. They may even technology push, not the other way around.
have more data than can be processed and Business requirements should always be the
assimilated in the time available. leading arguments.
20
8 1 0.4 Business related impact
of SA
With privatization and deregulation of the
power business in mind pure technical
arguments as men tioned above are not
convincing enough for the justi fication of SA Figure 10-4 Substation automation
Therefore, the following questions should be (SA) leads to more power
raised:
1. What can be gained with the
implementation of SA?
2. What are the criteria the decision to
implement
SA should be based on7
More power in this context means:
Systemwide
Master Clock
lntersubstation
SA SA SA real time SA
Substation 1 Substation 2 Substation 3 communication Substation n 209
1 0.5 References
i ..
10.5 [1] Ryan Bird ·,1ustifying Substation Automation, Black & Veatch http/ /tasnetcom/justa.shtml
[3] V. Lohmann, J. Bertsch · Information Technology (IT) and the Application of Numerical Protection
and Control Devices to enhance management and Utilization of Power Networks, International
Distribution Utility Conference, Sydney/Australia, November 1997
[4] V. Lohmann · Integrated Substation Automation enables new Strategies for Power T&D,
Southern Africa Power System Conference in Johannesburg/South Africa, November 2000
[6] REIarp, MA. Lee, C. Proudfoot · Working the Protection Engineer Harder,
Cigre Symposium June 1999, in London/UK, Paper No. 320-1
, r
210
11 Wide Area Protection
'·
11.5.12.1 Improvement of system stability 244
11.5.12.2 Reduction of set-point of LTC 244
11.5.13 Quick increase of synchronous condenser voltage set-point 245
11.6 Voltage stability assessment guidelines 245
11.6.1 Off-line studies and on-line studies 245
11.6.2 Voltage stability margins and criteria 246
11 11.6.3 Voltage stability assessment 247
Table of 11.6.3.1 PV-based margin computation 247
content 11.6.3.2 QV-based margin computation 248
11.6.4 On-line VSA functional requirements 249
11.6.4.1 Introduction 249
11.6.4.2 Contingency selection and screening 250
11.6.4.3 Voltage security evaluation 250
11.6.4.4 Voltage security 9nhancement 250
11.6.4.5 General requirements 251
11.6.5 Contingency definition 252
11.6.6 Contingency selection 252
11.6.7 Contingency screening 252
11.6.8 Contingency analysis 253
11.6.9 Voltage stability criteria 254
11.6.10 Security monitor 254
11.6.10.1 Security monitor capabilities 254
11.6.10.2 Direct (scan rate) monitoring 255
11.6.11 Security enhancement 255
11.6.11.1 On-line determination of preventive actions 256
11.6.11.2 On-line determination of remedial actions 256
11.6.12 Modeling and data requirements 257
11.6.12.1 Modeling requirements 257
11.6.13 VSA Data Requirements 258
11.6.13.1 Model Data Requirements 258
11.6.13.2 Default data 259
11.7 On-line VSA execution modes 260
11.71 On-line VSA execution control requirements 260
11.7.1.1 On-line VSA execution trigger 260
11.7.1.2 VSA execution abort 261
11.7.1.3 Execution control 261
11.7.1.4 Validity of VSA results 261 I
. · ..
11.8.2.3 Applications of the on-line VSA function 263 11
11.8.2.4 Direct (scan rate) monitoring 264 Table of
11.8.3 Operations planners/engineers user requirements 264 content
11.8.4 Manager user requirements 264
11.9 Interface requirements 265
11.9.1 Consideration of existing automated operating orders 265
11.9.2 Interface with EMS functions 265
11.9.3 Interface with EMS services 266
11.10 The implementation of Wide Area protection 266
11.10.1 System Set-up 267
11.10.1.1 Hardware system set-up 267
11.10.1.2 System protection center 268
11.10.2 Voltage Instability Prediction 269
11.10.2.1 Options for guided control actions 272
11.10.2.2 Control of On Load Tap Changers 272
11.10.2.3 Load Shedding 273
11.10.3 Interaction with SA and SCADA systems 274
11.10.3.1 Wide area protection on network level 274
11.10.3.2 Disturbance Recording 276
11.10.3.3 Communication to SCADA/ EMS 276
11.10.3.4 Communication to power system monitoring 276
11.10.3.5 Communication to station level 277
11.10.3.6 WAPS communication to bay level 277
11.10.3.7 Substation monitoring system 277
11.10.3.8 Protection adaptation 277
11.11 References 278
213
11 Wide Area Protection
11.,1 11 .1 The Role of Wide Area In the times of deregulation and globalization of the
power industry it is for sure that an increase in power
Protection exchange between companies and countries will
Power systems are planned, built and operated in occur. This contributes to making the interconnected
such a manner that customers should not be power systems less able to face large incidents if
affect ed; within given limits, by possible appropriate measures are not implemented. This
contingencies. Even if a power system is planned to evolution leads to a new conception of defence
withstand cre dible contingency, it may be affected plans and to a proposal concerning more
by more severe disturbances, resulting from coordinated defence actions between
multiple and simulta neous outages. companies/countries.
Beyond such occurrences of credible contingencies, a A group of experts on "Defence Plans Against Major
power system may also be affected by more severe Disturbances" elaborated some suggestions and re
disturbances, resulting from multiple and simulta commendations, which are summarized below, for a
neous outages, with possible conjunction of protec better international coordination of defence plans
tion or regulation failures leading to severe electro and the normal and emergency control actions to
mechanical and slow transient phenomena with prevent system incidents or to limit their consequen
sta bility problems, vo!tage collapse and large ces in large interconnected power systems as in the
frequency deviation. Even if the probability of such case of the European System (East-West Inter
disturbances is very low, the result may be a system connection). These suggestions and recommenda
collapse for the whole network or a large part of it tions are based on the reflections of the Group,
start ing from the answers to a Questionnaire
To face such severe perturbations, the utilities adopt
distributed to all the companies/countries who are
special defensive measures under the name of
members of UNIPEDE (International Union of
"defence plans": these measures, which must be
Producers and Distributors of Electrical Energy,
automatic and very fast, are intended to keep the
Paris/France).
spread of disturbances inside the network of each
utility. or even in the whole interconnected power
In view of the fad
system. In this respect, whereas interconnecting
that:
powe(systems result in better security in case of
limit ed outages or imbalances between generation • the interconnected power system should be
and demand, it provides conditions for a wider planned to withstand credible contingencies with
propaga tion of complex incidents. or without activating any emergency measures or
or defence plans, tested both from static and
The reason is that most of the measures adapted by dynamic points of view (suitable reliability criteria),
the companies/countries in the frame of defense
plans have been conceived, more or less, in a scope • appropriate agreements, which regulate the
confin ed to each company/country and the ultimate common use of the operational reserves should
action may be to open interconnections at be taken into account to cover some defined
boundaries. Even outages in operation planning and operations
if the achievement of an overall coordination is very · stages,
difficult due to both technical reasons and high costs, a set of preventive and curative coordinated measur
it is however suitable to improve the coordination of es should be foreseen in terms of defence plans to
defence plans because the electric phenomena do prevent major incidents or limit their consequences.
214 not stop at boundaries.
Definitions: • Normal: following any credible contingency, action
all loadings are within the continuous s
Defence plan: A set of measures to be taken to capabilities of system components, with must
pre voltage and frequency within prefixed be
vent major incidents or to limit their consequences. operational limits and overall demand is taken
supplied. rapidl
Credible contingency: any single or multiple
• Alert: the system is in acceptable conditions, y to
outage of system components taken into account,
but, if at least one credible contingency occurs, preve
such as losing any single-circuit line, losing any
the system will enter the emergency state. The nt
double-circuit line, losing any generator, etc.
alert state requires short-term or immediate unacc
States of the system: action: the existing conditions are such that eptab
le
overloading, voltage conditions, frequency changes
11.1.1.1 Cascade line tripping
or compo nent outages caused by pro(ections
operation. control
• Emergency: loading, voltage or frequency un The cascade line tripping may affect tie-lines be
acceptable conditions already exist on the system. tween a part and the rest of the power system,
Or the demand has been lost, or the system is when this part is importing or exporting much power.
11.1.1
split. Actions must be taken immediately to bring It may occur after multiple line fault and/or multiple
the system into an acceptable condition. genera ting unit tripping and/or during an expected
extreme increase of the consumption, or as a
11.1.1 Wide Area Power System Disturbances "transfer effect" between parallel tie-lines when
some of them trip, which increases load flows on
A list of the most severe phenomena which can the remaining ones.
cause major incidents may be the following:
The protective relays whose activation is responsible
• Cascade line tripping, for the cascade line tripping can be overload relays
• Voltage collapse, ("static overload") installed in order to prevent over
• Undamped power swings, heating of the lines or distance protective relays "tran
sient overload': when these relays are not blocked
• Loss of synchronism,
against power swings.
• Large frequency diminution.
The dynamics depend on the relays involved: from
Some of these phenomena are often present several minutes for the static overload relays, to less
together. In the following, for sake of simplicity, each than one second for the distance protective relays
of them will be dealt with separately along with its activation.
control measures. This approach is based on preven
The consequences can be voltage collapse, undamp
tive and curative actions for controlling phenomena
ed power swings, loss of synchronism, or a direct
which can deteriorate the system performances and
net work splitting.
the load after reconnection can be higher than • Voltage values of busbars
222 before the disturbance happened. • Real and reactive power values of the tie-lines
.
.
. ·
I -
'
11.2 condition that the network splitting does not The task of the power system planner is to find a
cause other disturbances, e.g. cascade line tripping technical and economical trade-off between invest-
in the neighboring countries. ments, operation costs and customer service quality.
• To control the frequency variation in all the WAPS play a significant part in this trade-off and are
separated section of the interconnected system by mainly used on a power system to: :I
')
balancing generation and load, if a controlled
network splitting or network separatior. could not
• Improve power system operation. WAPS are
often conceived by operational planner specialist
l
be avoided, or in case of a large deficit in the
interconnected system Particular attention must be to cope with
paid to frequency decline because of insufficient • operational difficulties imposed by
particular power system characteristics,
frequency regulation: In such a case, a common
and coordinated automatic load shedding scheme • operating conditions that involve heavy
should be activated energy transfers due to generation
co-ordination, i"
'
In order to achieve the objectives mentioned above, • higher exposure to multiple faults than
a number of preventive and curative actions has been what was originally planned and
recommended.
• special operational problems imposed
by long UHV transmission systems with
Finally, the increase of the mutual cooperation among
the partners of the interconnected system, in hydro generation located far away from
particu- lar between neighboring utilities could load centers
require:
All examples of those situations are often mitigat-
• The on-line exchange of agreed measurements
ed by WAPS.
and signals.
I!
I
• Common studies on the system dynamic behavior • Operate power system closer to their limits.
for an off-line detection of potential critical In many power systems, the operative safety mar- I
Situations (or possible risks) during planning or gins began to decrease quickly as a consequence I;
II
operation-planning phases. A list of data to be of restrained possibility of network development
exchanged and a procedure as proposed above caused by environmental problems or as a conse-
that enable to conduct such studies. quence of financial difficulties in following the
schedule of the transmission expansion planning.
• The coordination of the main steps for restoring
the grid to normal operating conditions after • Increase power transfer limits while main-
common load shedding has been executed. Such taining the same level of system security.
a coordination should comprise the roles of the WAPS may be used to postpone some trans-
Operators and Control Centers as well as the mission expansion projects to cope with scarce
exchange of signals and possible mutual agree- financial resources while maintaining the same r·
j i
ments. level of power system security. In many power I
l..
utilities, \fl/.f'>..PS is one of the key elements in the
power system planner's toolbox to meet system
performance requirements.
• In temporary installation to compensate for
delays in the construction program, e.g. as a
226
temporary solution before a new transmission line is ducted to determine their effects on power system relative
constructed. performance and to measure the robustness of the ly low
power system. The use of WAPS to increase power a smal
• Increase the power system security particu larly
system security is a world-wide acceptable practice to number
towards extreme contingencies leading to system
counter extreme contingencies, when experience of
collapse. Extreme contingencies
proves that these events occur too frequently and/or WAPS
usually refer to events resulting in multiple campo-
causes system collapse. are
. nents removed or cascading out of service such as the
probab
loss of transmission lines on a common right of-way or It is recognized that it is not feasible or possible to ly
faults with delayed clearing (stuck brea ker or protection predict or prevent all multiple contingency events that sufficie
system failure) on a bus section. Extreme contingency could occur randomly and could lead to power nt to
evaluations are usually con system collapse. When the complexity of a system is
protect the system adequately. However, large systems
must call upon a set of coordinated measures whose
11.3 Power system phenomena with
design and operation must involve high levels of complexity. possible WAPS solutions
This is necessary to ensure the system is able to cope
with all possible major incidents.
A defence plan can be considered as an additional level The main purpose of this section is to identify if an WAPS is
of protection, designed to initiate the final attempt at required and to determine the type of WAPS that will prevent
stabilizing the power system when a widespread a loss of network integrity. The deci sion is based on the type
collapse is imminent. At pre5ent, very few power systems of instability and the-struc ture of the power system on which
are equipped with such a defence plan and depending the WAPS is to be applied. After a severe disturbance some
on the power system design they differ significantly. of these phenomena will occur together, but for
Individual WAPS based on generation rejection, load simplicity, each will be discussed separately. The discussion
shedding, shunt switching or system splitting must be will consider the possible WAPS actions that can be used
regarded as basic actions, that can be used within a for controlling them. 227
defence plan.
. ?
11.3.1.
Densely meshed system Lightly meshed system with
with dispersed generation localized centers of
and demand generation and/or demand
Table 11-1, presented at the end of this section, lists er when the system is loosely meshed or the
the types of WAPS most likely to be used to limit power flows are high. The main consequences
the consequences of transient angle instability, are large disturbances for customers (voltage dips,
frequency instability, voltage instability, and instability frequency deviations) and/or large transients (real
resulting from cascade line tripping. Particular WAPS power, volta ge, frequency etc.) on the generating
solutions are described in detail in section 11.5. units and on the system. The latter may significantly
increase the risk of fast disconnection of units and
system separa tion due to incorrect line protection
11.3.1 Angle instability (transient and operation.
sma·11 s1. gnaI,) To prevent loss of synchronism, rapid and massive
actions based on the direct detection of the contin
11.3.1.1 Transient angle instability gency are often required. The following WAPS func
tions have proven to be especially effective in this
The transient stability of a power system describes role:
the ability of all the generators to maintain synchro
nism when subject to a severe disturbance such as a • Generation rejection and fast valving
heavy current fault, loss of major generation or loss of • Dynamic braking
a large block of load The system response will invol • Reactor switching near generators
ve large excursions in generator angles and signifi • Automatic load shedding
cant changes in real and reactive power flow, bus vol
tages and other system variables. Loss of synchro
nism can affect a single generating unit, a power .I.., I
..•..,.J'."I ". "'".Jr/1:tOl.l....;t)ef':j/IQ/ Qff':JI
plant consisting of multiple units, a region of the net ,·nstabl·z,·ty
work or several regions connected together. The loss
may appear suddenly (during the first swing) or after Small signal stability refers to the ability of the power
228 a series of divergent swings. The risk of loss is great- system to maintain in synchronism when subjected
to small disturbance. Power systems contain many
modes of oscillation due to a variety of interactions of
•
59++"-+"-,...._--i+
i}
.t
Time in minutes
work integrity, network separation Figure 11-1 Steam turbine
occurs, it is impor tant to keep the limitations
frequency under control. Generators can during abnormal
operate without restriction within ± 0.5 frequency
conditions
Hz from normal frequency (50 or 60 Hz
system) and for a limit ed time outside
these values (according to manufac A major problem for a steam turbine
turer's constraints). is the frequen cy drop resulting from a
sudden loss of generation. In a large
Figure 11-1 illustrates typical steam interconnected system, this is
turbine limitations during abnormal particularly onerous if immediately prior
frequency conditions. The curve is to the disturbance signi ficant power
derived by considering the worst case transfer is taken place from
limitations spe cified by five turbine one·region of the network to another.
manufacturers. (Note: steam tur bines If an interconnection or a power plant
are generally the weakest type of outage occurs in a region with a
turbine when considering under- gene ration shortage, a severe under-
frequency operation.) In this figure, frequency disturban ce will result.
time spent in a given frequency band Under-frequency operation (frequency
is cumulative but independent of the deviation >-2.5 Hz) can lead to the
time accumulated in any damage of ther
mal unit turbine blades and to life period reduction.
229
. ,
• Changing the operating mode of a hydro
gene rator from a synchronous compensator to
a synchronous generator.
• Islanding of thermal power units with local
loads. The purpose of this measure is to keep
the thermal units in service prior to the splitting of
11.3.3 Consequently, 'to protect the unit, the time duration islanding of the system. After the split, these
for underfrequency operation is limited. In some units should maintain supply to the consumers
situa tions, the frequency drop can be so deep, that within the islanded area.
under frequency relays will disconnect thermal • Overfrequency tripping of some or all of
units from the network, which· increases the power the units in hydro power plants (f > 61.5 Hz)
deficit. The other problem associated with operation to avoid thermal unit tripping.
at low fre quency is the effect on the output of plant
• Automatic load restoration initiated by the ope
auxiliaries (fans, boiler .feed pumps) and the reduC:ion
ration of overfrequency relays, designed to correct
this caus es in the output of the main generating
a frequency overshoot following the operation of.
unit.
an under-frequency load shedding.
If we now consider the region of the network with a
The main influencing factors for frequency variation
surplus of generation and assume that the inter-ties
can be summarized as: the power deficit (P), the
used to transfer power to the remote loads are sud
load damping constant (D) in the power deficit-area
denly tripped, the "local" system frequency will start
and the inertia constant (I) of the units. The
increasing. If the frequency increases above a pre-set
frequency deviation in a large interconnected
value (normally 61 Hz on a 60 Hz network) the
system can be expressed as:
governors may go into an over speed mode and
close their main valve. If the over-frequency is not .M(%) =- P(%) (1-e-lff) K
reduced within a pre-set time period the unit will be where K = 1/D and T = M/D
tripped because of the unstable boiler condition. The
problem of overfrequency is less troublesome than
underfrequency because tripping of the unit will
11.3.3 Voltage Instability
cause a frequency reduction. However, if the reduc Voltage stability is concerned with the ability to main
tion is insufficient, further units will need to be trip tain steady acceptable voltages at all buses under
ped, or if excessive an underfrequency will result. normal conditions, and after being subjected to a
disturbance. Voltage stability results from the attempt
Load shedding WAPS are used on most power of loads to restore above the maximum power that
system networks to control the frequency. Types of the combined generation and transmission system
WAPS that have proven especially effective in the can deliver to them. This maximum power is directly
control of frequency are: influenced by electrical distances between generation
• Underfrequency load shedding used to stop or and load centers, as well as by the reactive power
reverse a frequency drop. This must occur before limitations of generators. Voltage instability takes on
the thermal power plants are underfrequency the form of a progressive drop of voltages at the
tripped. The main objective is to hold the system transmission level under the effect of load
frequency above a pre-set level (58 Hz on a 60 restoration. In turn, the sagging voltages may result
Hz network) and keep the network in a system collapse causes by generators loosing
interconnected with the power plants on-line. synchronism and indudion rnotors stalling.
• Automatic tripping of interconnection lines by r
A distinction is made between short and long-term
underfrequency relays. voltage instability according to the time scale of load
• Start-up of a unit in a hydro power plant, restoration. Induction motors restore their active
normally initiated when the 60 Hz frequency
drops below
230 59.5 Hz. power consumption in a time interval of one second
(short-term) while loads fed through Load Tap a large disturbance. Voltage instability may be caused by
Changers (LTCs) restore over one to several minutes a variety of single or multiple contingencies. With
(long-term). The same holds true for thermostatically respect to long-term voltage stability, the main con
controlled loads. This is also the time scale on which field cern is the loss of transmission facilities (mainly be
(and in some cases, armature) current limiters ad to tween generation and load centers) or the tripping of
protect generators from thermal stress, thereby generators (mainly those located close to the loads
removing voltage support. and supporting the voltages of the latter). With res
pect to short-term voltage instability, the slow clear ing
Although the simplest voltage instability scenario is a . load of a fault may cause an induction motor dominat ed
increase above the maximum deliverable power, most load (e.g. air conditioning) to become unstable.
experienced voltage incidents were caused by
The main factors influencing voltage stability are:
c System strength (long electrical distances between
generation and load centers)
• Lack of fast reactive power reserves (generators,
synchronous condensers and SVCs)
• Lack of other reactive power reserves such as • Fast increase of generator voltages (througn
capacitors, etc. AVR set-points)
• High power transfers and high loading conditions. • In the last resort, load shedding
• Low power factor loads A proper amount of load shedding, at the proper
• Load characteristics, in particular load power location and with a proper tuning is very effective in
restoration through LTCs stopping a voltage instability process. The objective is to
restore a long-term equilibrium (operating point) for the
The following actions can be taken against voltage system. It is also aimed at avoiding the system to reach a
instability: point where collapse occurs due to loss of synchronism,
motor stalling, etc. Low voltages at transmission buses
• Shunt compensation: automatic switching of in load centers are typical signals but other variables
shunt capacitors or tripping of shunt reactors, may enter the decision logic as well.
• Emergency control of LTCs: blocking, return on a pre-
defined position, decrease in voltage set-point. In many cases, the required amount need not be large
to restore an acceptable voltage profile for fre quency
• Automatic tripping of interconnection lines (if it is
instability resulting from a lack of spinning reserve, but
acceptable to the area which imports power).
shedding must be fast enough. However, for voltage
• Modulation of HVDC power instability the location plays an important role.
• Fast unit start-up
11.3.4 Cascade line tripping
Cascade line tripping refers to an uncontrolled
sequence of transmission line disconnections trigger ed by
an incident at a single location. In some situa tions, a
severe disturbance on a transmission system can initiate
major oscillations in real and reactive power flows
and instability in voltage levels. These oscillations may
initiate the operation of some pro tection devices or
control equipment, which can occasionally result in
uncontrolled cascade line trip ping. Overload or thermal
problems may also cause cascade line tripping. Cascade
line tripping will affect inter-ties between regions of the
power system and will be particularly problematic when
one regiqn is importing power and another exporting. In
such situa tions the consequence of a disturbance may
spread over a wide system area and could result in the
loss of supply to a large number of consumers.
I
QJ
(])
t
(\)
>-,
s c: -i3
(])
;lO"l :J 0
+-' _c: (])
"Q) I 0 ..c
(\)
+--'
Ui.s 01 -o
> 0...
Vl
:J-o 0...
+-'
Vl
0
QJ
c:
0 0 Vl
a: +--' (])
(\) (\) ·v; (])
+--' -oC:
Vl
c: c: +--'
(\)
'+- 0
Vl
0"-o
001 - 01
·¥ 01
o
(]) 0
01
Transient instability X X X X X X
Frequency instability
- Frequency diminution X X X X X
.. -
- Frequency rise X
Voltage instability X X X X X X X
232 Table 11-2 Most used WAPS actions to counteract power system phenomena
11 .4 Classification of WAPS
Electric variables
Normally, WAPS ad after a disturbance such as a fault r--1 PCM'er System
·
most likely used to limit their consequences. The time
scale is logarithmic, full line represents the typical ope
11.5 Detailed description of the
rating range for each WAPS while the doted part various WAPS actions
indi cates the overall potential operating range.
There has been a marked increase in the use of
Also indicated in Figure 11-3 are the important areas
WAPS, particularly to withstand design criteria contin 11.5
at the extremes of the duration spectra which are not
gencies, as economics and regulatory problems have
covered in this document, but which deserve men
led to less robust transmission system. While impro
tioning since they represent Important areas of acti
ving system stability, the application of WAPS imposes
vity that could also be classified under the general
duties on system and equipment that must be based
subject of automatic actions but not under the sub
on a prudent assessment of the benefits and costs.
jed of switching WAPS. First extreme is the important
This Section presents short descriptions of the various
area of electro-magnetic switching transients c:mcern
WAPS actions available to improve system stability
ed with overvoltage and automatic measures taken
and reliability whilst discussing potential problems or
mainly to protect .equipment (protection system, over
harmful effects on the power system. The intention is
voltage protection and system separation). The other
to provide a starting point for detailed investigation of
extreme in the duration spectrum concern manual
a particular WAPS and to help designers of a new
operation and automatic actions taken to help sys
WAPS to select the most suitable type of WAPS to
tem operation after power system changes.
counter a specific phenomena.
238
11.5.5.3 Potential problems or harmful connected by over-speed protection. Methods event,
impact on equipment system of limiting over-frequency frequency include high- shunt
speed automatic load. restoration, braking resistors capaci
Special attention must be paid to establishing the and fast HVDC power change. tors
amount of load that can be disconnected by UFLS. If, that
following a UFLS action, the system or areas of the Due to the tripping of generators and the remain
s tstem have a power surplus (caused by over-shed operation of UFLS, large voltage variations often in
come with large frequency deviations. When loads service
ding), the system frequency will increase to an over
frequency condition and generating units may be dis are shed sud denly during an under-frequency may
cause serious over voltages. The same situation seconds. It is expected that after the shedding, the
may also happen on long UHV transmission lines voltage will recover to an acceptable value.
because of the high levels of charging current. Developing appropriate settings for the UVLS is a
Because of this, shunt capacitors on the sub- challenging problem. Load shedding is often initiated
transmission system should ei ther have automatic in steps to avoid over shedding and the selection of
over-voltage protection or be tripped by under- appropriate time step is an important factor in effec
frequency relays. If the over-volta ges are severe 11.5.6
tive under-voltage load shedding.
enough, they should be tripped as an integral part
of the UFLS scheme. When available, shunt reactors UVLS plans should be examined to determine if
on EHV transmission system could also be switched- acceptable over-frequency, overvoltage, or transmis
in by over-voltage relays used to control these over- sion overloads might result and all potential unaccept
voltages. able conditions should be mitigated. For example, if
over-frequency is likely, the amount of load shed
11.5.6 Under-voltage load shedding could be reduced or automatic over-frequency load
restoration could be provided. On the other hand for
Power systems with heavy loading on transmission over-voltages, the load shedding program could be
facilities an united reactive power control can be vul modified (e.g., change the geographic distribution) or
nerable to voltage instability. In some unplanned or mitigation measures (e.g. coordinated tripping of
extreme situations, when all others solutions have fai shunt capacitors or reactors) could be implemented
led, load shedding when voltage collapse is to minimize that probability. If transmission capacities
imminent may preserve the system stability. Under- are exceeded, the relay settings (e.g. location, trip, or
voltage load shedding (UVLS) is analogous to time delay) could then be altered or other actions be
under-frequency load shedding and provides a low- taken to maintain transmission loading within the
cost mean of pre venting system collapse. capabilities.
pre-set threshold for a time of greater than a few choice of the type of load to be shed must be made. 239
11.5.9
11.5.7 Remote load shedding these oscillations are not attenuated, system instabil
ity could occur. The DC power can be controlled to
Remote load shedding is similar in concept to gene improve transient stability by rapid discrete power
ration rejection but at the receiving end of the power level changes or to improve damping by use of con
system. Remote load shedding is a dormant system tinuous proportional control. The DC power can be
design to operate after extreme contingencies affec either ramped down or ramped up (taking advanta
ting the system's transmission capacity (e.g. loss of ge of short-term overload capability) to assist power
several transmission lines), whose severity largely system stability. 'The beneficial effect of DC modula
exceeds the robustness of the power system. This tion on the AC system is similar to the effect of gene
kind of extreme contingencies endanger transient, ration rejection or load shedding. HVDC controls
dynamic or short term voltage stability. In these cases, modulation may be used to:
rapid and massive actions based on the direct detec
• regulate reactive power,
tion of the extreme contingency are required. Remote
240 load shedding is one of the means that could be • support dynamic AC voltage,
used to maintain power system stability in that • damp frequency oscillations
situa tion. and
• improve transient stability.
The components of a remote load shedding system
can be categorized as follows: The controllability of HVDC links is often cited as an
• Inputs: mainly direct detection of the disturbance
important advantage of DC systems. This controllabi
lity can be valuable in improving dynamics perfor
• A central co-ordinating system: usually mance of AC system but only if DC control systems
required to decide the proper action (quantity perform adequately for various disturbances and
and localisation offload to shed) system conditions. These controls, which could be
• Output: feeders tripping quite powerful must not interact unfavourably with
other high performance controls and systems. HVDC
Remote load shedding involve direct tripping of low control robustness is therefore a major concern.
priority industrial/commercial load or residential load.
Remote load shedding can employ the same load When the DC line is the major connection between
shedding relays used to perform underfrequency two AC systems, the rapid modulation of the DC link
load shedding. These relays could have a dual func could be effective in attenuating transient disturban
tion, allowing both the direct execution of remote ces. A problem with this control method is that a
load shedding orders and the execution of load disturbance in one AC system will be shared by both
shedding as a function of local frequency conditions. AC systems. That is, a disturbance on one system will
appear as a sudden load change on the other
system. Unless there is some mutual benefit, the un
11.5.8 HVDC fast power change faulted system may not care to share the disturban
ce of the other system. Rapid modulation would also
HVDC transmission link is a highly controllable device require reactive power compensation capability on
and it is possible to take advantage of this the AC system near each converter to maintain pro
unique characteristic to improve transient stability of per voltage during the DC power flow modulation.
the AC system. Power flow on HVDC links can be
modulated by controlling the converters. HVDC
modulation can provide powerful stabilization with
active and reactive power injection at each 11.5.9 Automatic shunt switching (shunt
converter. reactor/capacitor tripping or dosing)
During a transient disturbance such as a fault on an WAPS are widely used to control the voltage levels in
interconnected power system, generator rotors swing a substation. This is achieved by automatic switching
to new angle in response to accelerating power. If of shunt reactors and capacitor banks. Shunt reactors
can be installed at the HV busbar in a substation, or units. They ad like reactive power consumers and create
at the tertiary winding of a transformer in an determi ne which generating units need to d by
EHV/HV substation. Depending on the measured produce more reactive power. This results in a event
voltage level they can be tripped or reconnected. more favorable tran sient stability condition s that
Capacitor banks are installed in many substations during a short-circuit fault Switching out shunt cause
to improve the power factor of the consumers load reactors following a severe con tingency also a
or for feeder vol tage control. They are greatly improves transient stability. major
automatically switched in accordance with the reduct
Two basic functions could be
busbar voltage level. This is nor mally achieved using ion in
performed:
a minimum voltage relay. the
• Over-voltages control: The closing of shunt powe
Shunt reactors on the HV busbar in a power plant reactors (or the tripping of shunt capacitors) r
improve the transient stability of the generating could be used to deal with overvoltages previo
usly flowing on the power system (e.g.
generation and/or load losses).
• Under-voltages control: The tripping of shunt
reactors could be used to deal with under-voltage
created by events that mainly affect the system's
transmission capacity (e.g. multiple loss of lines).
has been generally studied and applied as a 11.5.10
switch ing in of shunt resistors. This is normally for
11.5.10 Braking resistor a fixed insertion time and occurs immediately after
a fault has been cleared on the system. The
Dynamic braking is the concept of applying an components of an WAPS used for dynamic braking
artifi
can be catego rized as:
cial electric load to a portion of the power system. It
• a shunt
resistor,
• a switching equipment
and
• a control
system.
l+sT, l+sTc +
APLD lag
241
Figure 7 7-4 Accelerating power level detector (ADLP)
:_·,,
1 ..
11.5.11 During system fault conditions, the machine output following a major disturbance involving loss of gene
power drops as a result of the depressed system vol ration or imminent instability between areas. Con- ·
tages. The machines in the vicinity of the fault accele trolled system separation is applied when specific
rate during this time. During the fault and also after load and generating areas can be defined within a
the removal of the fault, the speed gain continues to large interconnected system. The instability between
increase the angle differences between these and areas is usually characterized by sudden change in
more remote machines, which may lead to loss of tie-line power. The instability is detected by monito
synchronism. The drop in machine output power may ring one or more of the following quantities:
trigger the energisation of the braking resistor. The
increased power demand from the braking resistor • sudden change in power flow through
now opposes the speed increase acquired during the specific tie-lines,
fault incident and reduces the machine angle diffe • rate of power change,
rences. This generally improves stability for faults in • change of bus voltage angle.
the vicinity of the braking resistor.
As interconnected systems grow, it becomes more
A sensitive trigger setting may lead to the energisa difficult to define system separation points that will
tion of the braking resistor for more remote faults. be applicable for all possible system emergencies.
This may reduce the stability of the system. During a Controlled separation as a planned method to achie
fault machines electrically close to the fault tend to ve power system stability is not widely applied main
accelerate more than the machines remote from the ly because it is difficult to define points of separation
fault. Simultaneously the energisation of braking resi that will be acceptable for all system conditions.
stors tends to retard the acceleration of the machines Controlled system separation is mainly used in power
close to the fault more than those machines that are system where load and generation are reasonably
remote from the braking resistor. Consequently, if a matched and transmission tielines to external power
braking resistor is energized for a remote fault, it system are easily definable.
tends to increase the angle difference between the
machines close to the fault and the machines close to The opening of inter-area transmission interconnec
the braking resistor. This increases the likel"1hood of tions shall only be initiated after the coordinated load
instability. shedding program has failed to arrest frequency dec
line and intolerable system conditions exist.
The sudden shocks from the switching in braking
resistors on the turbine can result in high levels of When an operating emergency occurs, a prime con
shaft torque. Studies must be carried out to ensure sideration shall be to maintain parallel operation
there are no adverse effects on the shaft fatigue-life throughout the interconnected power system. This
resulting from the combined effect of a fault, its clear will permit rendering maximum assistance to the
ance, the switching in, or out of the braking resistor power system(s) in trouble. Because the facilities of
and the possibility of unsuccessful auto-reclosure. each power system may be vital to the-secure ope
ration of the interconnected system, every effort shall
11.5.11 Controlled opening of be made to remain connected to it. However, if a
interconnection power system determines that it is endangered by
remaining interconnected, it rnay take such action as
Controlled system separation generally represents it deems necessary to protect its own system.
242 the last measure toward saving the power system
Tripping tie-lines is not without risk. If the inter When machines of two areas are electrically separat ed, occurred.
connection is supporting the individual system, then pole slip protection should split the systEm at a location To initiate
tripping the tie-lines will almost certainly mean total designed to improve the generation, - load balance in a trip, the
collapse for that individual system. If the individual each of the two isolated systems. Pole slip protection impedanc
system is supporting the interconnection, then trip ping operates significantly slower than distance protection e locus
the tie-lines will put the interconnection at great er risk. and consequently, distance relays may operate and can enter
Unless sophisticated relaying is implemented, there is no prevent the pole slip relay from tripping at the desired the lens
way for an individual relay to discriminate between the two location. Effective pole slip protection depends on the from the
conditions. However, the ultimate decision rests with the success of power swing blocking elements in left or the
individual system. From an overall system perspective the conventional distance relays. Most pole slip protection right, but
preferred option is to not trip interconnection lines. relays have a lens characteristic and the time taken for must
the impedance vector to pass through the lens is the
criterion used to decide if a pole slip condition as
traverse completely through to the opposite side of the
lens.
Following a severe disturbance, the voltages will be During a period of voltage collapse the OLTC will detect
a low voltage and after an appropriate time delay raise
the tap position of the transformer. Assuming no
change in the load demand on the transformer during
this period, the load can often be considered as constant
power as long as the tap changer can maintain a
constant load voltage. If the primary voltage level drops,
the current flow in the transmission system is increased to
maintain the load power. This increase in current flow will
further redu ce the transmission system voltage making a
voltage collapse more likely to appear.
reduced over a regional area that may affect many the sub-transmission or medium voltage level, will 243
11.5.12.2
244
make the supply voltage high and hence does not affect the real
situation power consumption (which is relatively inde pendent of
worse, since voltage). This also maximizes the reactive support from the
the tap- power factor correction capacitors.
changer
nea rest the
consumer Local blocking schemes are implemented using vol tage
will try to re- 7 7.5. 7 2. 7 Improvement of system stability relays and a time delay to sense the voltage level on
establish the the high voltage bus at the substation. The threshold
Normally, where the real power loads have some vol tage voltage is usually chosen to be a level that is less than
load vol
dependency, appropriate control actions can be used with that which occurs during maximum acceptable overload
tage. This
the OLTC to reduce the severity of the vol tage collapse. conditions. Blocking is initiated if the abnormal
means that
Blocking operation of the OLTC has been widely undervoltage condition exists longer than a predetermined
the reactive
offered as a method to reduce the negative effect on time. The time period may vary from one to several seconds.
power
the system. Load voltage reduction can also be used to The OLTC is unblocked when the voltage has recovered
losses will
reduce the loading on the sys tem. This is similar to peak to an acceptable level for a predetermined period of
increase in
shaving systems based on voltage reduction, widely used at time, typically
the
many utilities. There fore the on-load tap-changer may 5 seconds. Since the blocking action will be removed
distribution
be both a cause and a partial solution to the problems if the voltage recovers, usually a single phase-phase
system at
of· voltage collapse. voltage measurement is adequate for this scheme.
the same
time as the
reactive The simplest method to eliminate the OLTC as a con A coordinated blocking scheme can be utilized to block
power tributor to voltage collapse is to block the automatic raise operation of OLTCs in an area where voltage instability is
generation operation during any period when voltage collapse imminent. The coordinated scheme can be accomplished
from shunt appears to be a concern. The decision to temporarily with undervoltage schemes acting independently (as
devices will block the tap-changer can be made using locally derived described above) in a coordinated fashion at various
decrease. information or can be made at a cen tral location and the stations within a region, or it can be a centralized scheme
supervisory system can send a blocking signal to the unit. that recognizes a pattern of low voltages at key locations. In
This action may result in a period of low voltage on the a centralized scheme, the OLTC blocking can be
In some
affected loads. The effect of reduced supply voltages in implemented in substations throughout the affected
cases, tap-
the whole servi ce area must be weighted against the region, even if the voltage at all locations is not yet below
changers
possible alter native of complete disconnection of some a specific threshold.
can have a
customers in a smaller area. Tap-changer blocking will be
beneficial The key to operation of a centralized system is the
more effective for voltage decays slower than the transient
effect. reliability of the communication system. The data
time frame. It will also be more effective on loads that have
Consider for needed for decision making must be collected at the
a relatively high voltage dependency.
instance a central location for analysis. Control decisions must then
case where a be sent to each affected transformer location.
transfor mer
is supplying
predominantly 7 7.5. 7 2.2 Reduction of set-point of OLTC
motor load As already mentioned, a m;re advantageous use of OLTCs
with power than just blocking them consists of decreasing their voltage
factor
set-points. A larger load relief can be achieved. in this
correction
way. As for the blocking of OLTCs the effectiveness is
capacitors.
largely dependant on the characte ristics of the power
The OLTC
system, such as the type of load, the degree of shunt
keeps the
compensation and the number of OLTCs on lower levels.
... --
An interesting strategy for controlling OLTCs is as • In an alert state, where credible contingencies 11.5.1 3
follows: would lead to voltage instability, the MV voltage set- Q
• In a secure state, all OLTCs are controlled as usual. The points of HV/MV OLTCs are decreased while EHV/HV
u
HV voltage set-points are chosen to minimize real losses OLTC set-points are increased. The objective is to
reduce reactive losses and get more reactive support i
in the subtransmission networks.
from shunt elements :n the sub-transmission c
• In emergency conditions, EHV/HV and HV/MV OLTCs
networks. k
are blocked, keeping the minimum possible transformer
ratio for EHV/HV transformers.
increase of synchronous condenser 11.6 Voltage stability assessment
voltage set-point
guidelines
Synchronous condensers can generate or absorb
reactive power depending on the control of their ex
citation system and are an excellent form of voltage and
reactive power control devices. The reactive power 11.5
production of synchronous condenser is not affected by Recognizing that voltage stability is a serious concern, which
the system voltage and voltage regulator (AVR) can must be examined during planning and ope rational
automatically adjust this reactive power to maintain studies, there is a requirement to develop practical study
constant terminal voltage. While AVR is con trolling the procedures, security margins, and cri teria. The traditional
terminal voltage, the reactive power out put can be approach to planning for voltage security relied on
increased until heating limit is reached. The action of the ensuring that pre-contingency and post-contingency
AVR is instantaneous and quite effi cient in case of voltage voltage levels were acceptable for the system states
collapse, if the synchronous condenser is located near the under study. As a result, utilities have developed suitable
load demand. voltage criteria which specify acceptable voltage limits.
These criteria are largely based on equipment
Following a severe event that is leading to voltage tolerances and although they ensure safe voltages, they
decline, the synchronous condenser AVR performs a fast generally provide no assu rance that sufficient voltage
corrective action. In order to optimize the effi ciency of stability margin exists. Put it simply, a system may have very
the synchronous condenser to counteract voltage healthy pre-contin gency and post-contingency voltage
instability, automatic increase of its voltage set-point could levels, but be dangerously close to voltage instability.
be used as supplementary action. The voltage set-point is
increased according to a steep ramp until the The relatively recent concerns for voltage stability have
synchronous condenser reactive power reaches some motivated the development of some study gui delines The
percentages of the compensa tor capability or after some methods adopted will depend largely on the utilities'
maximum time (e.g. 30 s). This WAPS differs from experience, policies, and regulatory requi rements. For
secondary voltage control because it is faster as needed example, if studies show that voltage instability may
to counteract voltage instability following the loss of occur when reactive reserves on spe cific generators reach
several transmission lines and could thus be considered certain values, the utility may use such measures as
as primary vol direct indicators of voltage security. The success of any
such method depends on an unders'"wnding of the mechanism
of, and proximity to, voltage instability for the particular
system under a wide variety of possible conditions. This
chapter pro vides some generalized guidelines for
developing and applying security assessment methods.
11.6.2
246
In the more elements out-of-service. Studying conditions with one
off-line element out-of-service is necessary to provide margin for
environm the uncertainty of operating conditions. Because of main
ent, such tenance and forced-outages, the actual system is rarely
as in state with all elements in-service. Often, for study
operation purposes, each out-of-service element is com bined with
plan each design contingency, to form a set of double • For Models: The representation of loads, gene rator
ning, it is contingencies, which may include unrelated elements such capabilities, field current limiters, switched shunts, ULTC
necessary as loss of a line plus a generator. Care must be taken in this should be equivalent in on-line and off-line studies.
to case to account for the pre-con tingency system re-
determine adjustment which would normal ly occur for creating a In the absence of on-line analysis capability, the off line
the new base case with one ele ment out-of service. study results must be translated into operating limits and
margin indices that can be monitored by the ope rators. The next
for all For on-line studies, the system state and topology is known section describes some technical gui delines for VS
design (or at least approximately known) through system assessment, which can be applied for either off-line or on-
contingen measurements and state estimation. There fore, it is line studies. The present industry practice is to use
cies necessary to study only the criteria contin gencies for all deterministic methods for stability assessment. With
(such as elements in service. As a result, fewer scenarios need to be today's analytical methods and computer hardware, it is
single examined and, less margin may be required than for off- possible to assess a wide range of conditions and
element line studies, in which the system uncertainty is greater. contingencies in reasonable computation times. However,
outa ges, probabilistic assessment methods and criteria may become
double Off-line VS study tools have matured over recent years necessary as inter connected models grow, controls
outages (Figure 11-5) and now on-line analysis tools are being become more complex (including remedial action
of lines developed to compute VS margins, verify that criteria is schemes), and deregulation increases the volume and
on the met, and suggest remedial actions neces sary to meet uncertainty of energy transactions.
same the criteria. One important aspect of practical VS
tower assessment is the consistency between on-line and off- 11.6.2 Voltage stability margins and criteria
lost by line assessment methods. While the two approaches
LLG In general, VS margins are defined as the difference
may examine different scenarios and require different
between the value of a Key System Parameter (KSP) at the
faults, or margins, the basic procedures, and models used should be
double current operating condition and at the voltage stability
consistent. This is essen tial to ensure that the results
critical point. Different utilities may use diffe rent KSPs from
elements obtained from off-line studies can be compared to on-line
lost two main categories:
results.
through For example: • PV-based KSPs, such as an area load or power
brea ker transfer across an interface
• For procedures: The use of PV, QV. or time
failure) • QV-based KSPs, such as reactive power injection at a
domain simulations, should be consistent in
for bus or group of buses
on-line and off-line studies. The definition of how
system
margin is measured should be also equivalent.
conditions Voltage stability criterion defines how much margin is
with all deemed sufficient for voltage security of the system. It
elements can be stated as "the system must be operated such
in service that for the operating point and under all cre dible
and for contingencies, the VS margin remains larger than x% (or
condition y MWIMVAr) of the KSP':
s with
one or For example, when the KSP is defined as the area load,
and the criterion is defined as 7% of this KSP,
v
Pre-Contingency
Post-Contingency
11.6.3.
2
performance is to be evaluated, and the more parts of the system. When the KSP is
actual system operation policy, a selected as the reactive load at a group of
generation dispatch scheme (e.g. governor buses, the same procedure determines the
response, AGC, etc) is used to balance the "Generalized" QV margin of the system.
post-contingency powers and the control
of ULTCs, automatically switched However, traditionally, the QV margin at a
shunts and manually switched shunts are given bus, under pre- or post-contingency
enabled or disabled. conditions, is comput ed by the following
3. Calculate VS margins for a few procedure:
248 selected critical contingency cases 1. A fictitious synchronous condenser
using Time Domain Simulation. The (generator) with unlimited reactive power
approach is the same as that of step 2 is placed at the bus to control its voltage.
above, except that the voltage stability of
2. The scheduled voltage of the condenser is
the system following a contingency is
varied from Vmax to Vmin in discrete
determined by time-domain simulation over
steps.
an appropriate time frame (which may
range from several seconds to tens of
minutes.) Starting with the solved cases
3. At each point (scheduled voltage) the
power flow I
corresponding to the different load levels, is solved and the MVAr output of the condenser
I
\
the system is voltage unstable.
11.6.4.4 Available Transmission Capability (ATC) must take into well, such as required MVAr reserves in different parts
account adequate static, dynamic, and voltage :;tabi of the system and limits on post-contingency voltage
lity margins. When needed, control actions, similar to declines.
the preventive controls for contingencies, should be
found to expand the secure re-gion around the ope There are also cases where computation of VS must
rating point. be carried out in response to postulated conditions
(e.g., to determine if a requested transmission service
Based on the above requirements, the on-line VSA can be accepted).
package must provide the following basic functions:
In addition to evaluating the voltage security of the
• Contingency selection and screening
given system's operating point, it is also necessary to
• Voltage security evaluation know the voltage secure region around this opera
• Voltage security enhancement ting point. This information is useful when, for exam
ple, the system load is increasing or transfers are
Besides assessment of the voltage security of the being increased, and the operator wants to know
present system state, the on-line VSA must assess how much the load or transfer can increase while the
voltage security of forecasted future states, and any system remains voltage secure. This is particularly
specific state specified by the operator. important for determination and posting of the ATC.
·--········C: ·-·-·------
amount of required load shedding) for remedial
action schemes involving automatic load shedding.
Steady-State Analysis i Dynamic Simulation
The on-line VSA must validate the effectiveness of ----------- _1 - -- ---· --- ----- -- -- ----------
the control actions. For corrective controls, this may 1------ ------J
require time-domain simulation of the events and
control sequences. For acceptable performance in an
on-line application, special time-domain simulation
Voltage Security Monitor
techniques are needed, which are computationally
much faster than the conventional methods and still
capture the dynamics and timings important to volta
ge stability.
·
11.6.6 The VSA function must determine the relevant ope- 11.6.5 Contingency definition
rating limits (line loading limits, interface flow limits,
export/import limits, and load change limits) to en- A contingency consists of one or more events occur-
sure voltage security of the system in the event of ring simultaneously or at different instants of time,
occurrence of any of the contingencies designated by with each event resulting in a change in the state of
the operator, the severe contingencies determined one or more power system elements. A contingency
automatically through screening and ranking, or both. may be initiated by a small disturbance, a fault, or a
switching action.
\·
screened as irrelevant or non-critical under present automatically based on the operating data (SCADA) and the results of
operating conditions. In case the contingency list includes other functions (such aStatic Security Analysis). The Contingency Selector
one or more groups of "similar" contingen cies, whose should also be able to augment a contingency definition based on active
relative severity can be logically establish ed based on arming of remedial action schemes. It should also recognize "must select"
actual operating conditions,_ the Contingency Selector contingencies. The must-select list should be dynamic; for example, it should
should be able to select the n most severe contingencies in automatically include any contingencies that required remedial action arming
each such group (with n user-adjustable; default n ='1). in the previous VSA execution.
Moreover, the Contingency Selector should have the
capability to generate new contingencies (add to the list) The Contingency Selector rules should be applicable to any power system
based on operating conditions as determined by a set of data quantity that Contingency Selector can obtain or derive from the EMS
rules. These specific conditions must be recognized and/or VSA database. To support both real-time and study VSA, this
includes data from SCADA the State Estimator, Static
Security Analysis, OPF, and any Operating Orders coded
in the EMSNSA environ ment. Different rules should be
possible for real-time and study analysis. Mathematical
operations applica ble to Contingency Selector's current and
past data quantities must be supported. Logical as well as
alge braic statements should be possible. 11.6.7 Contingency screening 11.6.8
The Contingency Selector must support rules that check Contingency screening may be required to reduce the
whether each contingency's related data quan tities represent number of contingencies selected by the Contingency
a certain status and/or range-of-ope ration condition that Selector before carrying out further de tailed analysis.
warrants activation or deactivati on of the contingency. In
real-time mode, these checks should be possible on A number of voltage stability indices may be comput ed via
an instantaneous, trend, rate-of-change, or time-duration computational short-cuts to help rank the se lected
basis. This should include the ability to construct rules that contingencies in an approximate order of seve rity, or identify
com bine multiple power system conditions via one or harmless contingencies that need not be subjected to further
more logical statements. The Contingency Selector should analysis. Alternatively, rule based criteria may be used as
also activate/deactivate contingencies based on Static experience that is built up with the system. Finally, the
Security Analysis results, using generic or user-defined contingency screening module may be entirely disposed of if
rules. the Contin gency Selector adequately filters the list of
possible contingencies.
.;.. .;..
.;..
ficient voltage stability margin as defined by the vol
tage stability indices should be defined.
incremental arming patterns are determined so as to and configuration of bus arrangements in substa
minimize the number of changes in the active tions. The main purpose is to be able to adequately
arming, while ensuring system stability. Any sensiti represent switching operations in contingencies and
vity derivatives computed in this case are evaluated possible remedial action schemes. The
with the existing active arming. external model network may consist of two sub-
networks, namely:
The operator must, in any case, have the capability 11.6.12
to request a graphical comparison of the existing • the inner external (or buffer zone), where the
active arming and the one recommended by the identity of the external network model elements
VSA func tion. is preserved, and
• the outer external, where reduced models
In the study mode, the engineer/analyst should be are used.
able to study possible remedial action arming
options that would lead to system security. Both flat- Depending on arrangements for data exchange with
start and incremental arming capabilities must be other transmission control centers, little or no real
provided. The VSA system must have the tools to time data may be available about the external
allow easy modification of the arming patterns. model. There may be a need to change the
external model occasionally based on available
scheduling informa tion, seasonal variations, etc.
11.6.1 2 Modeling and data One or more external models may be required to
requirements account for various ope rating conditions in the
system based on scheduling data or seasonal
This section specifies modelling and data variations. For both the internal and external
require ments of the VSA function. Some of these subsystems, busses are grouped into zones. Power
require ments may be in line with the utility's transfPr interfaces from any zone to an adja cent
existing EMS models and data; others may have to one must be easy to identify for the purposes of
be added for on line VSA purposes. interface flow and transfer computations.
259
11.7 On-line VSA execution modes time sequence control (RTSC), which
coordinates execution of the network
security appli cation functions available in
the EMS environment. Figure 11-8 shows
where on-line VSA fits in the EMS real-time
sequence.
11.7 The VSA function must be able to execute periodi cally,
on demand, and upon occurrence of significant changes in The EMS RTSC design is expected to
the state of the power system. It should also be available provide the fle xibility for the operator to
in the study mode. have an execution of the State Estimator
(SE), and possibly the Steady-State
Security Analysis (SSA) function be
11.71 On-line VSA execution control automatically trig gered to precede each
requirements VSA execution.
'?
7 7.77.2 VSA execution abort
It should be possible to assign execution and abort VSA execution under these conditions. However, it is 11.8
priorities based on the type of triggering mechanism also possible that the VSA executions triggered by
that started the current VSA execution, and the source the Change Monitor do not run to completion for
of the incoming execution or abort request. For some time due to frequent changes in system
example, it should be possible to have any periodic condi tions. The operator should then be notified
VSA execution aborted by any event trigger, and that the available VSA results are no longer valid.
have any periodic trigger ignored or queued when an
event triggered VSA run is executing. It should also
be possible to have a forced execution mode such 11.72 Study mode execution control
that if VSA has not run to completion for a period of requirements
time (specified by the user, and longer than normal
VSA execution periodicity), a forced execution is In the study mode, the user must be able to execute
start ed ignoring subsequent execution abort the VSA function using a save case steady-state or
requests (except for manual abort). system snapshot.
The on-line VSA should have the capability to deter This section presents user requirements common to
mine (and warn the operator) when the results of all users, i.e., operators, operations planners/engi
the most recent VSA execution are no longer valid neers, and managers. 261
due to changes in the system or arming conditions.
It is nor mally expected that the Change Monitor
will initiate
. ·
7 7 .8. 7. 7 User interface environment
The VSA should have an effective and user-friendly
graphic user interface with point and click features,
pull-down menus and Windows. Modem graphics
should be used for the quick assessment of complex • Displays that indicate the "new" insecure contin
11.8.1.3 situations. gencies that were not identified as insecure in the
previous VSA run, and the previously insecure
The VSA user interface should provide facilities for contingencies that are no longer insecure.
effective and efficient monitoring of the various indi
ces, margins and trends together with provisions for 7 7 .8.7.3 Save case capability
implementation of preventive action recommendati
ons, and arming of automatic corrective actions (such The user must be able to request the on-line (real
as comparison of sting and recommended arming). time) or study mode VSA data and results to be
saved.
The VSA should be able to store the results of inse
A save case should include the following data and
cure cases and the associated state estimator base
cases automatically when these appear in the on- parameters:
line mode (controlled by the real- time sequence 1. The pre-contingency steady-state base case. The
control). These cases should be archived for future base case may have been generated under real
analysis and consideration by the Engineer. time sequence control (State Estimator solution,
possibly augmented by other VSA or EMS satellite
In both on-line and study modes, the possibility functions, to provide a VSA base case), or via a
must be provided to show the run time since the study power flow solution.
start of the VSA execution, as well as the progress of 2. Additional status and analog·data needed by the
the VSA run (e.g., screening in progress, the number rule base (e.g. remedial action arming status).
of con tingencies processed so far, the number of
3. All VSA execution parameters (tolerances, thresh
remaining contingencies to be examined, etc).
olds, etc) and configuration (e.g. screening
bypass).
A waiting symbol on the screen is required and copy
output capability is required for both tabular and 4. The contingency list selected/produced by the
graphical displays. Contingency Selector.
5. SA results generated according to the execution
parameters. The user must have the capability to
7 7 .8. 7.2 User call up a menu to select the VSA results to be
interaction saved. This should include the capability to select
a variable category, and item, as follows:
The following display capabilities must be provided
as a minimum: • Screening results (contingencies discarded or
retained).
• Displays that indicate the available VSA execution • Ranked lists of severe contingencies along with
control parameters, their current value, and their the value of the ranking index for each
default value. ranking index used.
• Displays that graphically show the variation of a • Overall VSA summary results, including grouping
voltage stability index with a given interface flow, of contingencies into voltage stable (secure) and
the critical interface flow limit for a single contin unstable (insecure), final ranking of severe contin
gency, and its envelope curve for all contingencies gencies, interface flow limits, recommended
processed during VSA execution. remedial action arming, etc
262 • Displays that show the unacceptable
(insecure)
contingencies for the previous VSA executions.
11.8.2.2 Security related information
provided for the operator
.;.. .;..
'? ?
'?
2. Outage dispatching for possible outages of
gene
rators, lines, transformers and reactive
groups. This entails a study mode
application of the VSA function.
3. Incorporation of critical contingency 4. Capability to perform model
11.8.4 results in relevant on-line application reduction/equiva lence for operator's use.
software like the optimal power flow. The model reduction capability may be an
4. Preventive actions: list of possible off-line tool, but the VSA should offer the
preventive measures for operator possibility to test the impact of choosing
decision together with the "cost" different external models, and compare
associated with each measure. them.
5. Arming: Arming recommendations for coor 5. Capability to compare cases with other
dinated automatic corrective action to utilities
ensure "vigilance" against the contingencies through standardized inputs and outputs and the
of concern.
ability to interface with time-simulation stability
6. Corrective Action: following the possible I.
... ...
'? '?
11.9 Interface requirements In the real-time mode, VSA must typically interface
Security
Analysis
with State Estimator results. Other options exist,
function
however, that depend on host-EMS capabilities. For
. in
example, if actual security violations are detected by
which
State Estimator, Optimal Power Flow may execute
case, if
This section addresses the main VSA interface requi automatically to determine appropriate corrective
the
rements with other au omated functions. correc
tive
11.9.1 Consideration of existing automated action is
operating orders projecte
d to
The operating orders involving determination of the give
interface flow limits and/or arming of remedial action rise to
schemes may be available in an automated environ a power
ment at the utility. In this case, most probably an system
automated table look-up process is available. Since the state
states in the look-up table cover only sample with
operating conditions, usually interpolation, extrapola tion conting
or scaling follows the table look-up process to adapt ency
the table look-up results to the prevailing ope rating problem
conditions. The VSA rule base should be a[Jie to s,
accommodate such rules. VSA should interface with Optimal
the Automated Operating Order subsystem to obtain Power
information regarding selected contingencies, interface Flow
flow definitions, interface flow limits, and the arming may
scheme. It should provide the capability to compare run
the operating limits, and arming, obtained by applying once
the operating orders, with those obtain ed based on more
VSA execution. to
determi
1.9.2 Interface with EMS functions ne
appropr
On-line VSA should be capable of using the output iate
results of existing host-EMS functions such as State preventi
Estimator, Dispatcher Power Flow, and Optimal Power ve
Flow to establish the power system conditions to be action.
analyzed by VSA. These conditions may take the This
form of a power flow solution that represents the means
state of the actual power system or the state of a that the
projected or study version of the power system. user
may wish to run VSA on a power flow solution Further, in real-time or study mode, VSA should use
established from: both the power system model and the power flow
results of the EMS function to generate and initialize the
1. Actual real-time conditions, as reflected in the
VSA power system model that will serve as a base
State Estimator solution
case and hence starting point for subsequent VSA
2. Conditions corresponding to "steady-state" processing.
corrective actions, or 11.9
3. Conditions corresponding to "steady-state" VSA should also be capable of using the output
preventive actions. results of the host-EMS real-time and study Steady State
Security Analysis functions. For example, for a given
VSA implementation should allow the user to coordi nate power flow solution,the corresponding Steady State
VSA execution with the host-EMS real-time sequence Security Analysis results may help VSA deter mine the
accordingly. relevant contingencies it should analyze.
In the study mode, VSA should typically interface with VSA should use real-time sequence results as they are
Dispatcher Power Flow results. Host- EMS studies using generated in response to the existing demand, event,
Optimal Power Flow may also be possible. Therefore, and periodic execution mechanisms that serve steady-
VSA implementation must allow the user to demand the state security analysis in the Host EMS. In addition,
execution of VSA on any study power flow solution that however, VSA should be capable of using the output
can be created or retrieved via host-EMS facilities. results of host-EMS functions such as remedial action
arming status, the Operating Orders,
action. The host EMS may then run its Steady-State etc, to determine if a change in the status of breakers 265
11.1 0 The implementation
of Wide Area protection
11.10 and/or corrective device arming should trigger execu Wide area protection is still an important topic since
tion of the real-time sequence solely for VSA purpo system wide collapses occur fre(juently in many
se. In this case, the flexibility to execute a subset of power systems. Since several years much effort has
normal real-time sequence should be provided, e.g. been taken to indicate voltage stability]. The propos
execution of State Estimator without subsequent ed indicators are designed for the implementation in
execution of Optimal Power Flow and Steady-State control centers and base on SCADA data. Two major
Security Analysis. kinds of indicators can be distinguished. The first ones
are the sensitivity-based indicators, the minimum sin
The ability of existing EMS functions to access VSA gular value of the load flow Jacobian. This kind of
output results should also be provided. This should indicators only consider the actual state of the system
include the use of recommended operating limits and does not predict any influence by discontinuous
(interface flow limits) and recommended corrective elements like reactive power limiters or under load
device arming status and associated threshold levels. tap changing transformers. The second ones are all
types of power respectively stability margin calcula
tions in the sense of calculating the difference be
11.9.3 Interface with EMS services tween the actual system's state and a point on the
stability boundary. The continuation power flow is the
VSA should interface with EMS services to obtain
best-known algorithm for this application. All discon
real-time or study power flow solutions, correspon
tinuous and steady-state effects influencing voltage
ding power system models, and the other results
stability are modelled.
from SCADA and Automated Operating Orders that
it needs. These services should provide facilities to
output VSA user messages such as convergence or However, the nowadays application of all these
voltage insecurity warning messages, and provide approaches has the drawback that the basic SCADA
EMS access to VSA results such as interface flow data assumes that the system is in a steady-state
limits. equilibrium. For slow changes in the system, like
changes of the load over day, this assumption is suf
To permit direct (scan rate) monitoring of designated ficient However, a typical voltage collapse mostly
voltage or reactive power quantities, data interface to occurs after cascaded contingencies or faults, which
SCADA should have the capability to transfer selected lead to an unstable system's state. This unstable state
SCADA telemetered or computed data to VSA is a dynamic transient process of several seconds up
every scan cycle (e.g. 2 seconds) or a user- to tens of minutes, which make the voltage stability
selectable mul tiple thereof (e.g. every 10 seconds). problem hard to handle with the nowadays steady
state approaches. In spite of a good theoretical knowl
edge, there are no practical realizations considering
the system dynamics for voltage stability assessment.
· '?
Conclusively, the major drawbacks of all these
11.10.1 System Set-up
approa ches lie in the not appropriate steady-state
system view. The solution for this is a departure
11.1 0.1.1 Hardware system set-
from the SCADA-based approach to a transient
measurement system. Such a measurement system up
together with the voltage stability assessment
and stabilization algorithms will be called wide area The PMUs must be installed throughout a critical area 11.10.1
protection system in the following. of the system. Critical area of the system e.g. in the
sense of voltage stability means to look on critical
Phasor measurement units (PMU), which are weil paths from generation to load areas or dedicated
known since several years, build the technical base transmission corridors. This critical area is the result
for the wide area protection system. They offer pha from a system assessment, e.g. with the help of
sors of voltage and currents together with a satellite model analysis [11] together with critical contingency
triggered time stamp in time intervals down to 20 ms. screening algorithms. For such a critical area an inter
Single installations of such units are in an experimen nal model with appropriate neighbouring models at
tal stage at many utilities. Also voltage stability indica the boundaries must be formulated.
tors are proposed on phasor measurements for con
PMUs with several input channels are able to measu
tinuous changes of power systems. This chapter con
re the primary voltage and currents at a substation at
centrates on the stability prediction after cascaded
the feeders and lines. The analogue values are trans
outages. The described algorithms are designed es
formed in to digital samples by the analogue
pecially for the opportunities that are offered by the
digital converter and processed in the
transient system's view.
microcomputer. They are synchronized via GPS with
an accuracy of 1 11-sec (Figure 11-9).
Current
Primary
Voltage
. ·
'•
,,
..
GPS
---------------------- --------- Satellite
System
-
Protection -- -- ---
-
11.10.1.2
:-,.JJ .
Phasor
-
rsnaps
hot
..
Figure 7 7-7 0 Set-up of a wide area protection scheme with PMUs
The measured data is transmitted from the PMUs state calculation considering the actual grid
to a central system protection center (SPC) topology. On this base the stability status is
where the evaluation algorithms are running. determined in terms of the power margin (PM)
The PMUs are located to make the critical of the critical area. Optimized stabilizing actions
area completely obser vable. Together with are initiated accordingly.
network data, the information of neighboring
stations can be calculated as well. There fore, To let the system protection center operate in
PMUs have to be installed only at each fourth real time, it receives information in the following
substation in the critical area. The form:
I
communication between the PMUs and the • Cyclic data: snapshot of the power
J
l:•t::=::=:=::::: ,-------- PM
Power
Margin
11.10.2 Voltage Instability Prediction
Contingency .':=!·.' ; to
Detection ::;..-. Voltage Voltage stability is concerned with the ability of a
Collapse
power system to maintain acceptable voltages at all
buses in the system under normal conditions and
after being subjected to a disturbance. The main fac
TVSI Transient
tor causing voltage instability is the inability of the
Voltage State
Indicator
power system to meet the demand for reactive
power. A disturbance like an unexpected branch
outage may cause a progressive and uncontrollable
Figure 7 7-7 7 Principle of instability monitoring
decline in voltage. The static analysis allows examina
tion of a wide range of power system conditions
and
gin is calculated all the time for the snapshots of the can identify the weakest lines which are the key con
power system supplied with the cyclic data. The tributing factors ir voltage stability analysis.
power margin is computed by the continuation
power flow (CPF). On this model stabilizing actions The voltage stability study may be limited to identify
are calculated, if the available power margin is too areas prone to voltage instability and to obtain infor
low. mation regarding now system voltage stability can be
improved most Effectively. Operation near the vol
To be prepared against the most critical contingencies tage stability limiTs is impractical and a sufficient
in the sense of (n-1), a cyclic pre-calculation of the power margin is needed. Practically, the idea of P-V
power margin and stabilizing actions is carried out. cuNe is used to determine the maximal MW
This is performed for all contingencies in a contin margin at load buses to avoid voltage collapse.
gency list for an actual power system snapshot.
Thus power margins and stabilizing actions for all The maximum power Pm, which can be transferred is
proba bly worst contingencies, which can occur in reached if the load impedance is equally low as the
the cur rent system's state, are already prepared. line impedance. With increasing load power the vol
When the calculation for the whole contingency list tage will decline gradually until P/Pm = 1. The
is finished, the next snapshot is processed the same effect
way. of decreasing vo age is to monitor the operating
point at actual status moving to the right The
If a contingency occurs, either pre-calculated results opera tor is to be alerted when it passes a
are taken or the transient voltage stability prediction threshold point and he is informed about the safety
is triggered. The transient voltage stability prediction margin leftlmtil instability will occur. Once it passes
needs no pre- processed information, therefore it the instability limit, load shedding is automatically
can follow any contingencies also cascaded initiated.
ones. Whereas the power margin calculation on an
269
actual system state and the pre-calculation is more To find the weakest branch the N-1 post-contingency
or less standard, the transient voltage stability load flow is analyzed. After the outage of a specific
prediction is branch the bus loads are increased along with the
'•
l
P = Pm, Voltage collapse
Precisely calculated instability limit
Actual status
0.6
0.4
0.2
0.0
0.0 0.2 0.4 0.6 0.8 1.0
P/Pm = 1.0 Maximum power
Figure 11-72 PV Curve of a transmission line delivering capability
proportional increase of bus generation to meenhe The idea of the method is to make a prediction from
demand. the beginning of the transient phase into the future
until the steady- state operation point is reached. For
Even if the power system is stable after a contingen this steady state operation point the stability can be
cy, a transition takes place that brings the power sys determined by calculating the power margin (Figure
tem to a new the stable equilibrium. Right after the 11-1 3). If no steady-state operation point is available
contingency, it is not possible to determine with clas the system will run into a collapse. The presented
sical steady-state based stability indicators if the approach maps the actual measured system's status
system state trajectory will end in a stable equilibrium. right after a contingency on an expected equilibrium
point in the near future.
The elements of the power system which cause this
delay of the collapse, are under load tap changing The advantage of the whole process is, that the sta
transformers (ULTC), reactive power limiters of power bility can be indicated directly after the contingency
units with temporary overload characteristic and dyna during the transient phase. If no equilibrium can be
mic loads with a load recovery characteristic after vol found, this model can be used to determine stabili
tage drops. If conventional voltage stability indicators zing actions, which bring this model and
are applied to the power system in such a transient therefore the real system back to a stable operation
phase, the results are faulty or the voltage in-stability point The time between the early detection of an
is detected too late, because the actual load is not instability, seconds after the contingency, and the
the load, which is demanded seconds later. Also it occurrence of the expected voltage collapse can be
will not be detected if power units are in reactive used to take these actions. Possible actions are
power overload or if ULTCs are in a stable tapping load shedding, blocking of ULTC-tapping,
position. activation of reactive power, change of voltage
set-points of voltage con trolling devices (FACTS-
Therefore the transient voltage stability prediction has devices, ULTC, secondary vol tage control, Automatic
270 been invented to assess the voltage stability correctly Generation Control (AGC) or controlled islanding.
after contingencies during the transient phase.
1.:1, t2
Network model:
0-------c=J--.,
!
I
+ZNE/n
vu, t2 11.10.2
Power margin 85
Proximity to
voltage collapse
Safety Margine:
!JS =SforecastMAX-l<: xlt AS = aefg - abed
The algorithm for the power margin LiS calculation is 3. The determined load parameters together with
based on the network model above with the voltage the base loads P0, 00 and voltage V0 are fed
source E, the line impedance ZNrr and the load into a power flow calculation considering also
impe dance Zapp· The maximal power transfer under
capacity is reached if line and load impedance load tap changers and power margins of devices.
become equal. The power margin calculation This power flow model represents exactly the
predicts the proximity to the voltage collapse by steady-state behavior of the completely modelled
taking the gradient of the voltage decline caused by dynamical system. The convergence of the power
the current It, at the instant t, into account and flow leads to the steady state solution respectively
estimates the situation at the instant t2 with the to the equilibrium point of the dynamic system.
assumed current t2 . This equilibrium point is the predicted state of the
system, which might be tens of seconds in the
The algorithm has four steps. A flow chart is shown future. If the power flow does not converge and
in Figure 11-13. no equilibrium is found the transient phase will
1. While the ystem is running in a steady-state end up with a collapse.
situation the steady-state values of bus voltages 4. If the power flow converges the power margin
V0 and load powers P0 and Q0 must be traced is calculated with the continuation power flow.
and contingencies as changes in the topology
must be detected. The system set-up traces continuously the ·state
2. The parameters of a dynamic load model, values of the system like voltages, currents and
which describe the voltage dependency of the active and reactive power. From the current
power, are determined. For this a sliding window measurement at the minimum at one end of a line,
of values of voltage V and load P, Q at each bus the outage of the line is detected (Step 1). After that
is evaluated. These values are the output of the a sliding win dow of measured bus voltages and
state calculation in the SPC. feeder loads is
collected (Step 2). 271
...
...
'?
'? '?
Load Tap
Load
Islanding Shedding AGC Changer FACTS
Control
Controlled Load Generation Tap Changer Cos<p dS: Safety margin as proximity
System Adaptation Adaptation Blocking Adaptation to voltage collapse
Separation
transformer protection relays are installed which genuine voltage collapse and a voltage depression
can respond to a prioritized blocking signal from for other reasons, e.g. transient fault, aftermath of
the SPC. clear in a total loss of voltage supply.
• Adaptation of the AVR set point, this is more
advantageous than simple blocking as it reduces In comparison with conventional load shedding sche
the load. mes numerical technology offers new solutions as
outlined in Figure 11-1 5.
Busbar
11.10.3.1
f Lim 1
f Lim 2
Second attempt:
Load is Load of priority 2 shedded
re-balanced-1'-------;-_.:;.t.a J I:::::::::::::::::::::=:==::::::::::: :.......--
'-----.--+-----------.t (s)
Figure 7 7- 7 6 Load shedding procedure
Figure 7 7-77 Interaction of WAPS with protection, monitoring and control systems
Network
Level
Station
Level
Bay
Level
Remote
Control
Bay Control Load
shedding
PMU
Ull
Generator Transformer Busbar, Line, Disturbance
Protection Station Protection Recording
275
Phasors
I
7 7. 7 0.3.2 Disturbance Recording
Disturbance recording comprises fault location and
recognition of the nature of the faults, which helps to
find and fix problems faster. Fault recorders should be
The WAPS application on network level is consisting installed at several locations of the network. The
11.10.3.4 of three applications, that mainly collect and process disturbance files of the recorders are collected and
phasor measurements from certain locati()ns of the processed by the substation monitoring system in
network (Figure 11-10): order to detect faults and to locate the faulty area.
The faults and their locations are displayed on
1. Phasor Evaluation: The phasors are measured SCADA monitors in the network control center and
by the phasor m asurement units (PMU) an alarm is issued. The operator can take
Figure counter measures to maintain the power supply
11-9 located at certain stations and sent to WAPS and can advice the line maintenance crew
directly or via the local protection centres (LPC). immediately to remedy the fault.
The phasor evaluation is responsible for collection,
pre-treatment, storage and providing of the
phasors for further processing by other appli 7 7. 7 0.3.3
cations.
Communication
2. Voltage Instability Predictor (VIP) will take to SCADAIEMS
the phasors from phasor evaluation, calculate
and display the instability factor of the network Since the network related applications are running on
(VS) continuously (Figure 11-13). The operator WAPS as well as on existing EMS, both systems
can supervise this factor and take counter steps should be able to exchange data via a communica
in order to protect the network from voltage tion link. This link can be a serial line with RTU emu
collapse. These operational steps can also be lation at WAPS side that it can easily be integrated
taken by the system automatically (Figure 11-14). into existing EMS, as the EMS will see the WAPS as a
3. Automated Control Application will define RTU.
precise actions to be taken based on the results
of the VIP (e.g. load shedding Figure 11-15). The WAPS sends the commands from the Automatic
If the system is running in operation mode Control Application (ACA) to EMS for execution by
'Automatic" the Automated Control will issue the the Automated Generator Control (AGC) or by other
commands, which are necessary for perfor ming relevant EMS applications. The network instability fac
the actions and send them to related SA systems tor (VS) can also be provided as input to the power
and devices. If the system is running in operation application software (PAS) for further processing.
mode "Manual" the actions will be displayed on Apart from this data available from EMS may be used
the monitors and can be used as guidance for by the WAPS.
further operation steps. The operator will then
issue the necessary commands manually. The
operation mode of the system can be selected by 7 7. 7 0.3.4 Communication to_
the operator. This allows optimum utilisation of the power system monitoring
results calculated by the system and optimise the
operation of the power system. Power system monitoring ensures reliability and inte
grity of the power delivery by around-the clock
moni toring of the power system. The WAPS delivers
inva luable information about the transients a"nd the
dyna mic behavior of the network and allows the
identifi cation of weak spots in the sense of
276 sensitivity against voltage and frequency declines on
a conti nuous basis.
11.1 0.3.5 Communication to station ·
level
[1] Piere Cholley, Peter Crossley, Vincent Van Acker, Thierry Van Cutsem, Weihu Fu, Jose Soto lndiar'iez,
11.11 Franc liar, Daniel Karlsson, Yasuhiro Kojima, James McCalley, Marian Piekutowski, Goran Rundvik
Roberto Salvati, Olof Samuelsson, Gilles Trudel, Costas Yournas, Xavier Wayrnel,
System Protection Schemes in Power Networks, Cigre Study Committee Task Force SGF 38.02.19,
Final draft v5.0 Conference lnternationale des Grandes Reseaux Electriques (Cigre), 2000
[2] Christian Rehtanz · Online Stability Assessment and Wide Area Protection based on Phasor
Measurements, Bulk Power System Dynamics and Control V, August 26-31, 2001,
Onoomichi, Japan
[3] Claudio (anizares · Voltage Stability Report, http:!/www.power.uwaterloo.ca
[4] Defence plans major disturbances, Large Systems and International Connections Study
Committee 40.01 SYSTDEP, UNIPEDE, Paris/France
278
12 Standards and Quality Definition for Substation Automation
,
12 12.6 Substation automation system 289
Table of 12.6.1 Device Standards 289
content 12.6.2 Information technology standards 289
12.6.3 Communication standards 289
12.6.3.1 Introduction 289
12.6.3.2 Data integrity 289
12.6.3.3 General network req'-lirement 289
12.6.3.4 Protocols 290
12.6.4 Communication Protocols 290
12.6.4.1 Modern Interface Protocol 290
12.6.4.2 Communication with Network Control Center 290
12.6.4.3 Communication within the Substation 291
12.6.5 EMI immunity 291
12.6.5.1 Introduction and general approach 291
12.6.5.2 Conducted disturbances 293
12.6.5.3 Radiated electromagnetic disturbances 294
12.7 Dedicated communication beyond substation boundaries 295
12.71 Power line carrier 295
12.7.2 Tele-protection 295
12.8 Power quality 296
12.9 Data and software standards 296
12.9.1 Disturbance recorder data 296
12.9.2 Function block programming · 296
12.10 Documentation and designations 296
12.10.1 Documentation 296
12.10.2 Graphical symbols 296
12.10.3 Classifications and designations 297
12.10.4 Designation and identification 297
12.10.5 Relationship between standards 297
12.11 System and project management 298
12.11.1 Introduction 298
12.11.2 System management and development process 298
12.11.3 Project execution process 298
12.12 Verification of Standard conformance 298
12.12.1 Application criteria 298
i2.12.2 Conditions to be met 298
12.12.3 Equipment functioning 299
12.12.4 Exceptions 299
12.12.5 Test points for EMI tests 299
12.13 Project Requirements and tests 299
280 12.14 References 300
. ?
12 Standards and Quality Definition for Substation Automation
12.1 Introduction product meets the level defined in the standard, the 12.1
producer has fulfilled his obligations. The compliance
with standards results in mutual trust of all
involved parties.
Standards are produced today mostly by international Standards are very comprehensive and mandatory
bodies like the International Standard Organization for consumer products. For industrial applications like
(ISO) or the International Electric Commission (IEC). In in substations, standards may not cover all needed
the standards itself, there are parts with strict rules, performance and quality requirements as they are
which shall be followed and which can be verified. required for a specific substation automation system.
Other parts are recommendations only but they may Sometimes, those requirements go beyond the
be declared as mandatory in many specifications. International standards, or there may not even exist a
Some rules are not issued as standards as such but standard for a specific application domain or a dedi
represent by its common use so-called de-facto cated feature. Then the missing standards have to be
stand ards. Local and regional standards exist by substituted by "best practices'The final goal is always
history but their importance is fading in a global that a system is running safely and reliably in its spe
world. If new local or regional standards appear cific environment and performing its specified func
today, they are normally complying entirely with tions. Therefore, standards cannot replace specifica
the corresponding International Standard. On the tions but should be integral part of them.
other hand, local or regional standards might be
submitted to an interna tional standardization
authority like IEC to be declared as international 12.1.3 The structure of standard information
standards if applicable and accept able.
In this chapter, you will find a short introduction to
Many standards have been declared by govern the application area per section. Relevant standards
mental authorities as mandatory to guarantee a com will be listed and complemented by short
mon quality, security and reliability level. The users or descriptions or comments if needed or helpful. As
juridical bodies may make claims if the standards seen from the beginning, relevant standards are
are not fulfilled. Standards protect also producers. referenced all over
If a the book 281
12.2 Standards itself are not allowed to be published in tem requirements and communications and refer to
any book but have to be ordered from standard system production and testing. As mentioned
organizations like IEC itself for copyright reasons. Big above, not for all aspects and features standards
companies may have a special contract giving for exist.
their employees access to the database of the stand
ardization body and, therefore, directly to the full A collection of standards for substation automation
text of standards. systems is found in
IEC 61850-3 Communication networks and
1 2.1.4 Dynamics of standards systems in substations - General requirements.
The substation shall continue to be operable, MTIF, MTIR and MTBF are statistical values
accord ing to the "graceful degradation" principle, if indicat ing average figures, which are experienced
anyone SA component fails. There should be no over a long period of time taken from large number
single point of failure that would cause the of units.
substation to be in operable. This is a matter of
system design. The relia bility requirements shall be For electronic devices the difference between MTIR
met as described in the sub-clause 3.1 of IEC and MTIF is normally so big, that for many
60870-4. The reliability class severity (R1, R2 or practical reasons (except availability calculation)
R3), as defined in 3.1.2 of IEC MTBF and MTIF can be considered as identical.
60870-4, has to be agreed between the producer
and the user. The MTIR cannot be stated by the system supplier
alone as it is not independent from a specific
12.3.2.2 MTTF and MTBF sub station and the repair organization. It depends
on the accessibility of the substation, the strategic
The Mean Time To Failure (MTTF) is a basic mea
spares available, the maintenance concept and
sure of reli;bility for omponents and systems. It is
facilities of the owner of the substation automation
the mean time expected until the first failure of
system as well as on the maintenance contracts if
a piece of equipment occurs. No reference is made
applicable.
to any repair.
The system supplier should clearly specify the MTIF
of the equipment delivered, including the reference
to the method of calculation.
· ·
There exist no International standards for MTIF
requirements in substations but they are specified in
most user specifications.
·
12.4.1.3 Electrical Insulation Standard
' ?
12.4.1.5.5
286 12.4.1.5.2 Voltage range
i
I.
During storage and transportation the substation auto- IEC 60694 shall apply.
mation equipment shall be able to withstand an air
temperature range as recommended in standard
IEC 60870-2-2, table 2. 12.5.5 Mechanical and seismic
Note that air temperature is as defined in sub-clause Mechanical and seismic qualification of substation
3.3.1 of IEC 60870-2-2. automation equipment shall conform to national and
international standards according to its location and
Where equipment forms an integral part of high vol- service. Where applicable, the classification of tole-
tage switchgear and control gear, clause 2 of stand- rable mechanical conditions and seismic stress shall
ard IEC 60694 shall apply. be stated by the producer, as defined in clause 4 of
IEC 60870-2-2.
12.5.3.2 Humidity
The local requirements have to be provided by the
user.
The communications equipment shall operate satis-
factorily with a relative humidity as recommended in Where equipment forms an integral part of high vol-
IEC 60870-2-2, table 1. tage switchgear and control gear, clause 2 of stand- I
Where equipment forms an integral part of high val- ard IEC 60694 shall apply. I
tage switchgear and control gear, clause 2 of
stand-
ard IEC 60694 shall apply. 12.5.6 Electromagnetic emission
IEC 61000 Electromagnetic compatibility (EMC) The integrity and consistency of the data delivered by
the SAS shall be as defined for integrity classes 11, 12
and 13 (sub-clause 3.5 of IEC 60870-4). The use of a
specific integrity class shall be determined by the
application that uses the delivered data.
12.6 Substation automation system
12.6.1 Device Standards
7 2.6.3.3 General network requirements
Substation automation systems comprise 12.6.3.3.1 Geographic requirements
intelligent electronic devices (lED). These IEDs have to
fulfill a lot of the standards mentioned already The communication network within the substation
above. In addi tion, the devices have to fulfill also should be capable of covering distances up to 2 km
the following standards as far as applicable. as stated in
• RP570/571 (ABB)
12.6.4 7 2.6.3.4 Protocols • lndactic 33/35 (ABB)
• 8fW (Siemens)
There are a lot of private and standardized commu • DNP3.0 (GE-Harris, DNP User group)
nication protocols. Therefore, a dedicated section is
• WISP (GE)
allocated to the protocol standards.
• Modbus (different users especially in the
12.6.4 Communication Protocols power plant area)
• etc
72.6.4. 7 Modem Interface Protocol Definitions are found in the literature or have to be
EIA 232 E Interface between data terminal asked for from the suppliers or user groups.
equipment and data circuit-terminating equipment
employing serial binary data exchange 12.6.4.2.2 Standard protocols (IEC)
This is the actual version of the well-known RS232C IEC 60870-5-101 Te/econtrol equipment and
connector. It specifies signal voltage, signal timing, systems for components - Part 5: Companion
signal function, a protocol for information exchange, standards - Section 707: Companion
and a mechanical connector. It is intended for short standard for basic tete-control tasks
distances up to 15 m and the communication is du This protocol is on dedicated communication lines
plex or half-duplex. between Substation Automation Systems or RTUs
ElA 485 Electrical characteristics of generators and Network Control Centers.
and receivers for use in balanced digital
IEC 60870-5-104 Te/econtrol equipment and
multipoint systems
systems for components - Part 5: Companion
This is the actual version of the well-known RS485 standards - Section 7 04: Transmission protocols -
connector. It specifies signal voltage, signal timing, Network access for /EC 60870-5-101 using
signal function, a protocol for information exchange, standard transport profiles.
and a mechanical connector. It is intended as serial This protocol allows to transfer data according to
link (point-to-point-duplex) for long distances up to
standard IEC 60870-5-101 over a communication
several km or as bus (half-duplex).
network
Further to the interface standards above there exist IEC 60870-6 Te/econtrol equipment and systems
also interface standards from ITU (CCITT), which con for components - Part 6 (TAS£2) lntercenter
cern different aspects like functional characteristic or protocol
electrical characteristic separately, however mostly the
packaging in the RS standards are used. As an This protocol is intended for communication between
exam ple the RS232C is identical to ITU V24 network control centers. Therefore, it is often called
(functional) ICCP Qnter enter ommunication Qrotocol)_ It is used
+ ITU V28 (electrical) + ISO 2110 (mechanical). in some few cases for substation-Nee links also.
The informative interface for protection devices in For communication with third party IEDs having pro
substations is defined by prietary protocols, protocol conversion is needed. This
conversion is outside the scope of any standard but
IEC 60870-5-103 Te!econtrol equipment and needs the information about both involved stand
systems for components - Part 5: Transmission ards.
....
r
Referenced Standard IEC 61000 levels according to IEC TS 61000-6-5
IEC 61000-4-5 2 3 2 2 2 2
Surges 1.2/50(s (a) 1 kV 2 kV 1 kV 1 kV 1 kV 1 kV
Line to line 3 I
4 3 3 3 3
Line to ground 2 kV 4 kV 2 kV 2 kV 2 kV 2 kV
IEC 61000-4-6 3 3 3 3 3 3
Conducted disturbances 10V 10V 10V 10 v 10V 10 v
induced by RF3
IEC 61000-4-12
2 3 2 3 2 3
Damped Oscillatory 1 kV
0.5 kV 1 kV 0.5 kV 1 kV 0.5 kV
differential (b) 2.5 kV
1 kV 2.5 kV 1 kV 2.5 kV 1 kV
common (b)
4 33 4
IEC 61000-4-16
30V 4 10V 30V
Conducted common mode Not defined
Cont. 30V Cont. Cont. Cont.
disturbances
300V 300 V for 1 s 100 v 300V
0 Hz to 150 Hz4
for 1 s for 1 s for 1 s
(a) For connections to telecom network or remote equipment, also surge waveform 10/700 (s with a 4 kV peak shall be
tested, (b) Test frequency 1 MHz. For GIS, higher frequencies have to be considered. Experience: at least up to 50 Ghz.
Table 12-1 Levels of EM/ immunity to be tested for ports of devices in substations
Equipment installed in
292 Table 12-2 Levels of EM/ immunity of devices against radiation and discharges in substations
The general immunity requirements for industrial
environment are considered not sufficient for sub There are differences in requirements between medi um voltage
stations. Therefore, dedicated requirements are defin (MV) substations and high voltage (HV) substations (AIS and
ed in GIS). The term HV is taken for voltages of 36.5 kV or above,
MV for all voltages below. A different limit between HV and MV
IEC TS 61000-6-5 Electromagnetic interference
can be agreed upon between the utility and the manufactu rer
(EMC) - Part 6: - Generic standards -Section 5:
influencing the EMC test level to be used for the SA equipment.
Immunity of power station and substation environ
ment
Special mitigation measures on site may create a "protected
The contents of this Technical Specification (TS) will environment" and reduce the immunity requirements. This may
remain unchanged until 2005. At this date, this TS include shielded cables pro perly grounded and fiber optical links.
will be transformed either to an International The use of any kind of such measures has to be included in the
Standard, or reconfirmed, or withdrawn, or replaced pro duct specification. In this case, all proofing tests shall be made
by a revised edition, or amended. with these measures.
Details of these requirements and testing procedures
are given in other parts of the series
12.6.5.2.2 Surges
r · '?
12.6.5.2.5 Fast transients IEC 61000-4-8 Electromagnetic compatibility
(EMC) - Part 4-8: Testing and measurement
For fast transients and bursts, in HV substations gene techniques - Power frequency magnetic field
2.6.5,.3 rally class 4 with 4 kV and a repetition rate of 2.5 kHz immunity test
is requested according to
This standard is applicable also for CRT monitors
IEC 61000-4-4 Electromagnetic compatibility according to clause 8.2 of
(EMC)- Part 4: Testing and measurement tech
niques - Section 4: Electrical fast transient/burst CISPR 24 (EN 55024) Information technology
immunity test. equipment - Immunity characteristics - Limits and
methods of measurements
7 2.6.5.3 Radiated electromagnetic The magnetic field requirements cited above are
disturbances complemented by
The equipment shall meet either level 3 (1 0 V/m) of IEC 61000-4-10 Electromagnetic compatibility
(EMC) - Part 4-10: Testing and measurement
IEC 61000-4-3 Electromagnetic compatibility techniques - Damped oscillatory magnetic field
(EMC)-Part 4-3: Testing and measurement techni immunity test
ques - Radiated, radio-frequency, electromagnetic
field immunity test In addition to these tests, it is known that to a certain
or degree induced power frequency voltage will occur
on all copper circuits inside the substation, especially
IEEE (37.90.2-1988 Trial-Use standard withstand caused by primary fault currents that are flowing in
capability (SWC) tests for Protective relays and and around the substation. This common mode
Relay systems effect, resulting from magnetic flux linkages, causes
almost equal voltages being induced in each of the
Regarding radiated, radio frequency, electromagnetic cable cores.
fields. The specific requirements (IEC standard or IEEE
standard) shall be agreed between manufacturer and With the introduction of serial data communications,
user. Criteria for acceptance are summarized in 12.12. injected current tests on the cable circuits are requir
ed to ensure that the equipment is capable of with
12.6.5.3.1 Power frequency disturbances standing typical induced voltages without interfering
with its correct operation. The substation equ1pment
Communications equipment may be subjected to va shall operate correctly in the presence of a power fre
rious kinds of electromagnetic disturbances induced quency voltage in accordance with Table 12-3.
by power supply lines, signal lines or directly radiated
by the environment The types and levels of distur The induced transverse voltages at power system fre
bances depend on the particular conditions in which quency are benchmark values for a substation en
the communication equipment has to operate. vironment. and represent acceptable operating with
Reference should be made to level 4 (30 V conti stand levels for equipment design.
nuous and 300 V for 1 s) of
IEC 61000-4-16 Electromagnetic compatibility The equipment should be tested using an injection
(EMC)- Part 4-16: Testing and measurement tech network to combine the required communications
niques - Test for immunity to conducted, common signals with a povvgrJsequency interference signal.
mode disturbances in the frequency range 0 Hz With the interference suitably injected, the magnitude
to 750kHz of the communications signal levels should be reduc
ed to the receive level claimed by the manufacturer
For magnetic fields also to the following two stand and correct operation of the communications equip
ards are applicable. ment should be maintained.
'.
Unbalanced Balanced Balanced 12.7
Length of
Class communications communications communications communications
circuit [m] (V] (1% unbalance) [V] {0.1 % unbalance) (V]
1 1 to 10 0,5 0,005 0,0005
2 10 to 100 5 0,05 0,005
3 100 to 1000 50* 0,5 0,05
4 Greater than 1000 500* 5 0,5
*) The unbalanced class of communications circuit covers such cases as RS232. For practical reasons, such communica
tions systems are considered to be run over very short distances within the substation or to link equipment to intelligent
test equipment such as portable computers. It is not proposed that they be practical for substation applications
covering distances above 20 m. Standard balanced circuits are of the class associated with PTO circuits where up to
500 V of common mode voltage is balanced to within 1%. In addition, techniques such as transformer coupling can
achieve impedance balancing to within 0,1%.
12.6.5.3.2 Electrostatic discharges than 1000 km without the need of any repeater, and
electronic PLC systems have increased the band width
Handling with sensitive electronics implies always the up to 64 kBit/s.
risk of electrostatic discharges, which may result in
mal-functions of the lED of in destruction of electro The relevant standards are
nic components. The risk is increasing with decreas-
IEC 60353 Line traps for a.c. power systems
ing air moisture level. The related standard is ·
IEC 60481 Coupling devices for power
IEC 61000-4-2 Electromagnetic compatibility line carrier systems
(EMC)- Part 4-2: Testing and measurement
IEC 60495 Single sideband power line carrier
techniques - Electrostatic discharge immunity test
terminals
IEC 60663 Planning of (single-sideband) power
line carrier systems
12.7 Dedicated communication
beyond substation boundaries 1 2.7.2 Tele-protection
12.7.1 Power line carrier Tele-protection allows to block or activate remote
Apart from modern wide-band communication net protection actions, e.g. on the other side of a long
works, the narrow-band Qower jine 93rrier (PLC) line. Therefore, it applies also for modern micro
systems must not be neglected yet since PLC systems processor based distance relays.
provide economical communication links over long IEC 60834 Tete-protection equipment of power
distances, e.g. for very long HV overhead lines of systems - performance and testing (series). 295
more
12.8 Power quality lity but there is not a general
agreement what total power quality
really means. Therefore, the mentioned
standards (mainly about harmonics) are
only the first steps toward a general
power quality standard.
12.10 At least in deregulated markets, power quality is a
IEEE 519:19921EEE Recommended
negotiable issue between power suppliers and con
Practices and Requirements for
sumers. Power quality may be based on a lot of fac
Harmonic Control in Electrical
tors, where frequency deviations, harmonics and
Power Systems
reactive power content belong to the well-known
and accepted ones. New measurement technologies
IEEE 1459:2000 IEEE Trial Use
offer a lot of additional figures about the power qua
Standard Definitions for the
Measurement of Electric Power Quantities Under IEC 60255-24 Electric relays- Part 24: Common
Sinusoidal, Nonsinusoidal, Balanced or Un balanced format for transient data exchange (COMTRADE)
Conditions for power systems
IEC 61000-4-7 Electromagnetic compatibility IEEE Std C37.111-19991EEE Standard common
(EMC) - Part 4: Testing and measurement techni format for transient data exchange
ques - Section 7: General guide on harmonics and
interharmonics measurements and instrumen- ·
tation for power supply systems and equipment 12.9.2 Function block programming
connected thereto.
Basically, functions in substation automation may be
programmed nearly in any programming language. It
is very convenient for the user to program not by
coding lines but to use high-level functions blocks
("function block language") as used by program
mable controllers. The related standard series is
IEC 61131 Programmable controllers
12.9.1 Disturbance recorder data Symbols for electrical diagrams, also especially for
protection devices/functions are defined in
A standard storage format of disturbance recorder
IEC 60617 Graphical symbols for diagrams
data (COMTRADE format) is defined in the following
two related (i.e. identical) standards: Parts 2 to 11 are available by IEC in database form.
296
12.10.3 Classifications and designations
IEC 60750 Item designation in Electro-Technology
The German version now replacing DIN 40719 is 12.10.5 Relationship between standards
DIN EN 61346-1 lndustrielle Systeme, Anlagen
-Plant objects (e.g.bay)
und Ausrustungen und lndustrieprodukte - -Designation of object
e.g. Drawings
Strukturierungsprinzipien und Referenzkenn
zeichnung - Teil 7: Allgemeine Regeln
Symbols
DIN EN 61346-2 lndustrielle Systeme, Anlagen For diagrams
und Ausrustungen und lndustrieprodukte - Struk
turierungsprinzipien und Referenzkennzeichnung -
Teil2: Klassifizierung von Objekten und Kodierung
von Klassen
Set of
documents
The standard Data exchange 'II\
designation
1
!
1 2.14 References
12.14 [1) Switchgear Manual,@ ABB Calor Emag Schaltanlagen Mannheim, 10th revised edition,
Cornelsen Verlag, Berlin, 2001
[2)1nternational Electricity Cornrnission (IEC): wv\lw.iecch
[3) Institute of Electrical and Electronic Engineers (IEEE): wvwv.ieee.org
[4) Deutsches lnstitut fUr Normung (DIN): wvwv.din.de
[5) International Standard Organization (ISO): wvwv.iso.org
300
-
13 The System Standard IEC 61850 for Substation Automation
301
... ...
...
.,
I
I
.
13 The System Standard IEC 61850 for Substation Automation I •
-·1I I
302
Figure 73-1 The different kinds of
openness
ones more centralized solutions, some prefer to technology of the application domain preferred system
have a high level of integration of functions in one structures may change. For example, some sensor technologies
box. other ones prefer dedicated devices for any func prefer passive fibers, other ones full serial communications resultiY"Jg
tion. Therefore, the communication standard has to in different places for process interfaces, New functions may
support the free allocation of functions. emerge over the time. Therefore, the communication stand
ard has to support not only the free allocation of func
Open to support state-of-the-art system tech
tions but also to provide extension rules.
nology;Depending on the state-of-the-art in system
Open to easy communication engineering and
maintenance: A device is defined by its allocated
functions. A system is defined by its devices and the
connections in between. Therefore, a communication
standard has to have some means to describe these
properties. If such a description is part of the standard the
system may be extended and modified civer the 13.4 Structure 13.4
... ...
.... ...
'(
'?
3.4 IEC 61850-5 Communication networks and For interoperability, not only data have to be standar
systems in substations - Part 5: dized but also the access to these data called servi
Communication requirements for functions ces. In part 7-2, all general and domain specific servi
and devices models ces are defined.
Communication in substation follows the state-of
the-art in communication technology, but its only pur IEC 61850-7-3 Communication networks and
pose is t:::> support all functions to be performed in systems in substations - Part 7-3: Basic communi
substations. Therefore, a lot of requirements arise cation structure for substation and feeder equip
from these functions, i.e. from the domain ment - Common data classes
substation automation. All these requirements are
collected and defined in part 5. Part 7-3 combines all common data attributes to
common data classes to be used in part 7-4. This
IEC 61850-6 Communication networks and combination facilitates both the overview for the
systems in substations - Part 6: rea der and the implementation for the software
Configuration description language for en gineer.
communication in electrical Substations
related to lEOs IEC 61850-7-4 Communication networks and
. systems in substations - Part 7-4: Basic communi
The impact of interoperability is that devices from dif
ferent suppliers have to be combined to one cation structure for substation and feeder equip
ment - Compatible logical node classes and data
system by the system integrator with his dedicated
engineer ing tool. Therefore, the complete system classes
with its en tire devices and communication links has Part 7-4 shows the content of standardized data to
to be de scribed in a formal way in the be exchanged in the substation. It uses terms well
engineering process. The XML-based ubstation known to any user of switchgear: The user can check
onfiguration descripton if he finds in the standard all data items he needs.
.Language (SCL) for IEC 61850 compliant systems is Extension rules show how to overcome application
standardized in part 6. limits.
IEC 61850-7-2 Communication networks and The abstract data model and services have to be rea
systems in substations - Part 7-2: Basic communi lized by the application layer of the communication
cation structure for substation and feeder equip stack. The standardized procedure how to do this is
ment - Abstract communication service interface called "mapping" and given in part 8 and 9. Part 8-1
(ACSO specifies the mapping of common services between
client (mostly an HMI) and server (lED) and of the
communication of eneric Qbject Qriented ubsta
304 tion Events (GOOSE) between devices (IEDs).
1 3.5 Approach
IEC 61850-9-1 Communication networks and 13.5.1 The communication approach 13.5
systems in substations - Part 9-1: SpeCific commu
nication service mapping (SCSM) - Sampled values The communication technology is changing very
over serial unidirectional multidrop point-to-point rapidly while substations have lifetimes of 30 years
link and longer. The functionality of substation automa
Part 9-1 specifies the mapping of analog samples tion is, therefore, changing very rarely. Normally, addi
over serial unidirectional multidrop point-to-point link, tional functionality is added over the years. Therefore,
e.g. the serial communication between an electronic the standardization has to be focused not so much
voltage or current transformer/transducer and bay on the fast changing communication technology but
units e.g. for protection. more on the domain specific object data model. Such
a domain specific object model consists of objects, i.e.
IEC 61850-9-2 Communication networks and part of functions, which are very common in sub
systems in substations- Part 9-2: Specific commu stations like breakers, controllers, and protection,
nication service mapping (SCSM) - Sampled values which exchange data with each other. All these data
over !SO/IEC 8802-3 have attributes like time stamps or the validity of data,
which have to be known or set for a proper
Part 9-2 specifies the mapping of analog samples over opera tion of the substation automation system. The
bi-directional, bus type serial link As an add-on to access and exchange of data is defined by
part 8-1 it allows e.g. the multi-use of data, changing standardized ser vices.
parameters of the electronic transformers/trans
ducers and the transmission of supervision data, The 7-layer ISO/OSI model describes state-of-the-art
commands and trips. communication. The layers in decreasing order
are (Figure 13-2):
IEC 61850-10 Communication networks and
systems in substations - Part 10: (7) Application Layer (Words of the communication
Conformance testing with semantic meaning like voltage, position,
indication, time)
To guarantee interoperability according to the global (6) Presentation Layer (Language or coding like
standard IEC 61850 between all suppliers and to ASCII, double bit indication 16 bit analog)
minimize the risks for system integration, the compli (5) Session Layer (Start/stop talking, who of the
ance with the standard has to be tested in the same partners is allowed to talk)
way all over the world. Therefore, the conformance
testing is standardized in part 10. (4) Transport Layer (Connection exists, sequence
numbers/order, completeness)
(3) Network Layer (Address like phone
number)
(2) Data Link Layer (Length of telegram, error ..
_
detection/correction)
(1) Physical Layer (Medium/connectors,
frequency/level of electrical/optical pulses)
PH Data unit
I (7) Application
I
.
I (6) Presentation _ --------·-·---·-----·-·1 1 I _ ..,.(..,6..,)_P_re_s_e_n_ta_ti_o_n..... -1
I SH Data unit
(5) Session 1 1 1 (5) Session
I
TH Data unit 1
I
(4) Transport 1 1 (4) Transport 1
(3) Network NH Data unit 1
·- I I I__ ·-I-·-I-. ,......
(3...)..N_e_tw_._o_rk
I
(2) Data link F A c Data unit (1 Field) FCS F (2) Data link 1
I 1111 I II I
I (1) Physical ;·I sme -- (1) Physical
1
L
The function model is always implemented as soft 13.5.3 The engineering approach 13.5.3
ware package in devices. Therefore, the function
model has to be complemented by a device The data model with all its options used, the alloca
model. (Physical Device, PD), which describes all the tion of LNs to devices, all the communication links,
common properties of the device. Logical Nodes are and the allocation of functions to the switchgear as
grouped in Logical Devices (LD). The common per the substation single line diagram are described
device pro perties are described in the Logical by means of a standardized Substation Configuration
Node LPHD (Logical Node of the Physical Device). ·description Language (SCL) that is based on XML.
An example of such a model is shown in Figure 1 3- This language is used to exchange data between
4. the system configuration tools of different
suppliers during the engineering process. It allows
easy exten dibility and maintainability of a substation
automation system over a long time (Figure 13-5).
f +· +
Interface
Adaptation per
Mapping
+ Stack
Interface
FAST
MMS --'-
CHANGES Real-time -
Communication
Technology requirements TCP Stack selection
following
state-of-the-art ·-
r L- IP communication
--·-- -·--
technology
Ethernet Link Layer
Figure 73-3 The approach of IEC 67850: Splitting the Application Model from Communication Stack 307
13.6 Seamless Communication
for Utilities
13.6 All communication capabilities f the involved IEDs 13.6.1 Network Control
are provided to the system configurator as configura
tion files by communication from the IEDs, on dedi ·The basic models and services may be used for utili
cated data media, or from an lED database. The allo ty communication tasks also beyond the substation
cation of the functions to the single line diagram and since communication concepts of network control
all needed communication links are added. Using this and substation automation have been merged with
information, the system configuration file can be industrial communication technologies (MMS,
engineered and loaded (back) into the IEDs. Dedi TCP/IP). Broadband communication systems of utilities
cated device tools may be needed to configure the using TASE.2 and IEC 60870-5-104 are today mostly
functions and marshal the data inside the lED but based on TCP/IP networks as used by IEC 61850
all have to support the import and export of also. Seamless communication requests only a har
configura tion files in the SCL format for system monization of the data models used at network level
engineering. i=
PO "Bay Unit"
·8>· 8> !
e (§) @)
Figure 13-4 Device model according to IEC 67850 with the Logical Nodes LLNO (Common properties),
PD/S (Distance), PTOC (Timed overcurrent), CSWI (Switch controO. C/LO (Interlocking),
308. LPHD (Physical device information)
'? . ? . '?
Engineering environment
lED Capabilities
(LN, DO, etc)
System
Confi
13.7
Engineering Association, relation to
Workplace
& J . i1-- Single line diagram,
preconfigured, reports,
ConlfEigDurator etc
File transfer remote
--------------- File transfers and
File transfer
;_ --
§!' B) ·.;J2J]
. -,-_ - --:;..,.,.-- .---
13.7 Benefits
ommon Information Model (CIM) according to IEC The main benefits of the standard result from the fact
61970) and used at substation level (IEC 61850 data that IEC 61850 is a
model). IEC TC57 already proved the feasibility of this
concept. • global system standard for lnteroperability between
devices from various suppliers that are installed in a
substation. This allows optimizing
1 3.6.2 Teleprotedion the selection of devices for dedicated applications and
will improve competition.
The data model and the services of IEC 61850 pro vide • future proof standard because of the split between
already the functionality for line protection sche mes the application model and the communication stack
(refer to Logical Node PSCH) as releases and blackings This allows modifying and extending the application
for distance protection and other schemes used to (functions, data) without touching the
increase the selectivity of protection. The transmission communication stack. Reverse, any update of the
of samples as needed for line differen tial protection is communication stack according to state-of-the-art
outside the substation basically the same as inside. This in communi cation technology will have no impact
provides seamless communica tion also for protection. both
on functions and databases. 309
. ·
; '
1 3.8 References
13.8.1 Introduction
[1] L_ Andersson, K-P. Brand · The Benefits of the coming Standard !EC16850 for
Communication in Substations
Southern African Power System Protection Conference, Johannesburg, November 8-9, 2000
[2] R. Dinges ·Standardisierung in der Schutz- und Stationsleittechnik (Standardization
in Protection and Substation Automation)
ETG-Fachtagung "Schutz- und Stationsleittechnik'; NOmberg, 23124.10.2001
[3] K-P. Brand, W. Wimmer·Der Standard IEC 61850- Offene Kommunikation in Schaltanlagen
im deregulierten Strommarkt (The Standard /EC 6-1850- Open Communication for Substations
in the deregulated Electric Energy Market) Bulletin SEVNSE 93, 1 (2002) 9-13
310
1 3.8.2 Read more 13.8.2
[4] Ch. Brunner, A. Ostermeier · Serial Communication Between Process and Bay Level- Standards
and Practical Experience
CIGRE 2000, Paper 34-106 (9 pages), Paris, September 2000
[5] J. Haude, A. Janz, Th. Rudolph, Th. Schaffler, H. Schubert · A pilot Project for testing the Standard
Drafts for Open Communication in Substations - First Experiences with the future
Standard IEC 67850
CIGRE 2000, Paper 34-109 (6 pages), Paris, September 2000
[7] L. Andersson, K-P. Brand, W. Wimmer· The Communication Standard IEC67850 supports flexible
and optimised Substation Automation Architectures
2nd International Conference on Integrated Protection, Control and Communication - Experience,
Benefits and Trends, Session IV. Paper 3, New Delhi, India, October 10-12, 2001
[8] L. Andersson, K -P. Brand, W. Wimmer · Some Aspects of Migration from present Solutions
to SA Systems based on the Communication Standard IEC 61850
2nd International Conference on Integrated Protection, Control and Communication - Experience,
Benefits and Trends, Session IV. Paper 4, New Delhi, India, October 10-12, 2001
[9] L. Andersson, K-P. Brand, W. Wimmer · The Impact of the coming Standard IEC 67850 on the
Life-cycle of Open Communication Systems in Substations
Transmission and Distribution 02001, Brisbane, Australia, November 11-14, 2001
[10] Eric Udren, Steven Kunsman, Dave Dolezilek ·Significant substation communication
standardization developments
Paper presented at the Western Protective Area Distribution Automation Conference (WPDAC),
Apri/2002
[11] Ch. Brunner, G. Schimmel, H. Schubert ·Standardisation of serial/inks replacing parallel wiring
to transfer process data - Approach, state and practical experience
CIGRE 2002, Paper 34-209 (6 pages), Paris, September 2002
[12] R. Baumann, K-P. Brand, Ch. Brunner, W. Wimmer · Der Standard IEC 67 850 in Schaltanlagen
als Kern einer durchgangigen Kommunikation!osung fUr den Netzbetre1ber
(The StanEfard IEC 61850 in Substations as nucleus of a transparent Communication Soiution
for Network Operators), Bulletin ElectroSuisse 94, 3 (2003)
311
14 Phase Models of Substation Automation Systems
14.1 The concept and limits of life cycles and phases 315 14
14.1.1 Life cycles 315 Table of
14.1.1.1 Cycles and metacycles 315 content
14.1.1.2 From cycles to phases 315
14.1.2 Two kinds of life cycles for substation automation 315
14.1.2.1 System or manufacturer life cycle 315
14.1.2.2 Project or customer life cycle 316
14.1.2.3 Related standards 316
14.1.3 Responsibilities 316
14.1.4 From device to system 317
14.2 System or manufacturer life cycle 317
14.2.1 Market observation and continuous development 317
14.2.2 Concept and design 317
14.2.3 The impact of platforms and application modules 317
14.2.4 Prototypes and testing 317
14.2.5 First production and conformance certification 317
14.2.6 Production with quality control 317
14.2.7 Change requirements and updates 317
14.2.8 Outphasing and continuation 318
14.3 Project or customer life cycle 318
14.3.1 Acquisition and offer phase 318
14.3.1.1 Sales activities 318
14.3.1.2 Requirement Specification 318
14.3.1.3 Specification Evaluation 319
14.3.1.4 Design Specification and tender 319
14.3.1.5 Offer Evaluation 319
14.3.2 Project Execution 319
14.3.2.1 Project manager 319
14.3.2.2 Organization 320
14.3.2.3 Tools 320
14.3.3 Project Execution Phase I (Factory) 320
14.3.3.1 Set-up of Project Management 320
14.3.3.2 Refinement of System Design 320
14.3.4 System Production 320
14.3.4.1 Prerequisites 320
14.3.4.2 System engineering 320
14.3.4.3 SW Engineering 320
14.3.4.4 HW Engineering 321
14.3.4.5 Production of adaption of software 321
14.3.4.6 Production of hardware 321
14.3.4.7 System integration 321 313
14 14.3.4.7 System in,tegration 321
Table of 14.3.4.8 Factory Acceptance Test (FAD 321
content 14.3.4.8 Factory Acceptance Test (FAD 321
14.3.5 Project Execution Phase II (On-site) 321
14.3.5.1 Shipping of the system 321
14.3.5.2 Commissioning on-site . 322
14.3.5.3 Site Acceptance Test (SAD 322
14.3.6 Maintenance Phase 322
14.3.6.1 Warranty period 322
14.3.6.2 Life cycle maintenance 322
14.3.6.3 Decommissioning 322
14.4 References 323
314
14 Phase Models of Substation Automation Systems
14.1 The concept and limits of life 14.1.1.2 From cycles to. phases 14.1
cycles and phases
If we cut off any cycle we get a linear sequence of
14.1.1 Life cycles phases with start and end. Despite the complexity of
real life cycles, the resulting phase model is a good
14.1.1.1 Cyc!es and metacyc!es guideline in structuring both system development
and project management (see Figure 14-2).
Every individual, organism, organization, product, and
system show an important feature of life, i.e. they Idea for Approval
new solution
appear, exist for some time and disappear. They are
replaced by identical successors, or by ones transfor
med by evolution. Substation automation systems
also show such a life cycle.
Test
Strategic
Product Management Decision for Actions
Marketing
Functional Strategies
Akquisjtion
Promotion
Offers § s L
Market
obser
a ;! OH OMIPL
.E
Project
develop SA
Product
maintenance
Product
develop·
ment
vation
e standard
team
(Missing ment
T
PMIS.Eff issues)
--· I I
Bt:YPMIS SIOMIPM c. F T I T j,
c
I ..,
I §
i
r
0
Market Out.
Solutions
"mc' introduction phasing
.c.
c
Offers
I
OelivP-riP-S Deliveries
I ti5 (j S/PMIBO S/PM.ED
I
I
COncepts Solutions Standard solutions Products
Concepts . on about existence 1 Introduced Streamlined
Documents Informati 1
... Products product pool
r J
Competitive Product Pool
Hardware, Software, Services, Tools, Ucensable Know-how, Documents, Information
316
.;,.
tor are the same. In any case, a clear definition or cycle as shown in Figure 14-3 more complicated.
negotiation of responsibilities is essential for substa The most visible process is the life cycle for
tion automation projects. products but behind we have the life cycles for
platforms, applica tions, and system concepts. All
14.1.4 From device to system these cycles may be completely asynchronous.
Important is the conti nuous compatibility best
Substation automation is a system composed of pro provided by internal and external standards like 14.2
ducts and interconnected by· communication. There IEC 61850 de-coupling the application from the
may be dedicated life cycles for platforms, devices, implementation of the commu- nication stack.
product families, etc At any time, a system has to ·
exist but maybe with changing components. The sys
tem as such will also have a life cycle defined by a
system generation. Without special comments, the 14.2.4 Prototypes and testing
text will refer always to substation automation sys
tems as whole. In this phase, the feasibility is verified and basic fea
tures are tested internally. Also testing against appli
cable standards may be included. If all products are
part of systems, the system behavior has to be includ
ed also. System testing implies testing of functiona
14.2 System or manufacturer lity, behavior and performance over several commu
life cycle nicating devices. Therefore, the guidelines for com
munication testing in the substation domain found in
14.2.1 Market observation and continuous the report of the CIGRE Task Force TF34.01 (2002)
are necessary but not sufficient for a comprehensive
development system testing in any case.
Close contacts with the customers, continuous
obser vation of the market, and fast following the 14.2.5 First production and conformance
needs of the customers is at the beginning of this
cycle (see Figure 14-3). It is the joint task of sales
certification
and product management.
Normally, the first series has to be out for approval
regarding performance testing in independent labs or
To monitor the trends in technoloqy is mainly the task
conformance testing according to important stand
of the development. Its impact to-solutions has to be
ards. Conformance testing according to IEC 61850 is
closely discussed with the product management.
found in part 10 of this standard (IEC 61850-1 0).
' I
\ Fixing
deviations
I
I
/
1 I
I Exten5ion \
\
I \
I \
- .;
Fixing '
\
_
on-site
'...... Sys.lntegr
FAT
problems
14.2.8 Outphasing and continuation beginning of this cycle also (see Figure 14-4). Now
the focus is on the early identification of coming pro
If all updates regarding technology, production cost jects. There are three checkpoints:
(market price!), and functions are exhausted,
devices and systems will be out-phased. • Collect information about utility environment,
Recommendations for out-phasing procedures will needs and coming projects.
also be found in IEC • Propose solutions in the sense of consultative
61850-4. As long as the business is continued, next selling with benefits for the customer.
generations of devices and systems have to be intro
duced continuously. • Respond fast on project specifications issued
by the customer.
HW engineering comprises the cubicle layout inclu- . The factory acceptance test has benefits both for the
ding the allocation of devices to cubicles and its local manufacturer and for the customer.
wiring.
The customer or one of his representatives is witnes sing
A second step takes care of the allocation of the the FAT. Therefore, he may see in time, if all his
cubicles to the substation and its substation-wide requirements are fulfilled not only on paper but also by
wiring or cabling. This includes both cables for data the running substation automation system. He may help
and power supply. Data may be completely transmit ted clarifying last misunderstandings, and request fixing
over serial links, which are implemented as opti cal deviations.
fibers, but it means HW also.
The manufacturer can fix all problems with the back up
14.3.4.5 Production or adaptation of of all his techrical facilities and experts resulting in much
software less problems than at commissioning on-site. By the
acceptance of the customer, he has reached an
The result of SW engineering is implemented similar as important milestone in project execution, which is often
the result of HW engineering in the devices and related with some payment.
system. Action items are
The limit of facr.ory acceptance test is that not all
• buying SW licenses if applicable,
components anc interfaces of the system may be
• writing programs or activate these in SW libraries, available in the factory. Especially, the switchgear is
• production or collection of relevant documen missing and has w be simulated as good as possible.
tation,
• filling up data bases. The key for a successfully performed FAT is the test
plan negotiated between the manufacturer and
customer.
14.3.4.6 Production of hardware
The result of HW engineering has to be produced
including the following steps. 14.3.5 Project Execution Phase II
• Buying devices (On-site)
• Producing of cubicles
7 4.3.5. 7 Shipping of the system
7 4.3.4.7 System integration After the FAT, the material from the factory has to be
shipped to the site of the customer. Then, the recep tion
• Integration of HW and SW as far as not yet
of the material on-site has to be organized and
covered in the previous steps
supervised.
• Preparation of test set-up including data and
power interconnection (cabling) Since this phase is outside the direct control both of the
• Production or collection of relevant documentation manufacturer and of customer, it has the covered
• Pre-Testing of the system (Pre-FAT) by a proper insurance and an appropriate contract. 321
I
7 4.3.5.2 Commissioning on-site
On-site, the system has to be erected according to
the site plan and has to be properly assembled.
Some parts like building of houses and cabling may
be excluded from the project contract and provided Spare parts, diagnosis and replacement procedures
14.3.6 locally. These contracts need to be known to the influence the availability and safety of the system.
system provider in advance since they may refer to
crucial interfaces. After erecting and connecting all The main task during this period is a fast response of
parts, the system has to be set in operation the manufacturer in case of failures. The meaning of
(commis sioning). "fast" has to be defined also in the contract.
All functions have to be tested by the commissioning
team. If the FAT was very comprehensive, nearly no
323
15 Benefits of Substation Automation
325
15 Benefits of Substation Automation
326
0
1.
Decreasin
0.
0.
0.
15.2.1
0.
:Shed load
PIPm
0.
0.0 0.2 0.4
0.6 0. 1.0
Maximum power
Power- voltage characteristic capability
reliable assessment of the actual power system sta which are collected at the protection center. This
bility limits. approach allows to measure by gathering a large
amount of measurands what has to be estimated
A Wide Area Protection System 0/VAP), which com otherwise, and it results in power system state
plements existing protection and control systems, pro meas urement rather than power system state
vides new solutions for power system monitoring estima tion.
and for the detection of incipient abnormal system
conditions early enough that predetermined defen
sive actions can be initiated either manually by the 15.2.1 A new approach to predict
operator or automatically in emergency situations to voltage instabilities
counteract system instabilities and to maintain power
system integrity (Figure 15-1). The power transfer capacity of transmission lines is
defined by its specific PowerNoltage characteristic
Phasor measurement units (PMU) that are installed at WAP allows monitoring the voltage decline depen
critical locations throughout the transmission network ding on theJoad for voltage instability prediction and
sample voltage and currents phasor to deliver accu to asses the safety margin for the power system ope
rate and actual real time data about the power rator as critical operating information. In case of rapid
system stability conditions. They are synchronized via voltage decline, under-voltage initiated load shedding
the global positioning system (GPS) satellites so that is automatically conducted in the substation to main
simultaneous snapshots of phasors can be taken, tain power system integrity (Figure15-2) 327
15.3 15.2.2 Options to counteract power transmission and distribution level substations. Solu
system collapse tions for substation automation reflect the structure
and requirements for reliability and availability of a
As soon as loss of synchronism occurs in the net spedfic substation (Figure 15-4).
work. violent transients are induced on the genera
ting units located inside or at the border of the out At station level, they comprise substation automation
of-step area and consumers have to stand with systems (SA). An ideal system platform offers a set of
large disturbances. The strategy against transient function modules, which can easily be extended by
instabili ties to be chosen is to initiate load shedding the user stepwise by adding further higher-level func
on fre quency criteria and to isolate out-of-step areas tions to the basic power system control and monitor
as fast as possible and thus save the rest of the ing systems.
grid.
With such a strategy WAP is the solution to On the bay level, they include a range of application
specific solutions for control, automation, protection,
• detect transient and monitoring of lines, transformers, cable feeders,
instabilities, bus-couplers, bus section couplers and busbar confi
• provide early indications for slower actions gurations. The Intelligent Electronic Devices (IEDs) for
enabling a possible re-synchronization, protection and control are integral part of these solu
• initiate rapid action in emergency situations tions. The SA system including the capabilities of the
to avoid the spreading of disturbance, specific IEDs lays the foundation for all the higher
• disconnect the out-of-step areas only with level remote functions such as advanced power
high selectivity. system management and the condition monitoring
of the equipment while it is in service.
Examples of predetermined defense options accord
ing to (Figure 15-3) are described with more techni
cal details in Chapter 11. 15.3.1 Integrated protection and control
to accelerate response to problems
MS Voltage
I
frequency .----1----. Safety
Voltage instability
monitoring
Phasor prediction
Evaluation
margin
AS
• • •
A S : Safety
Defence actions against collapse Emergency control schemes
margin as
proximity to
voltage
collapse
Loa Automatic
d
FACTS.
Islanding
Tap
shedding generatio
changer
control
Figure 75-3
control
Wide area protection
!!!
Split of power Load Generation Tap
Changer Power flow system
adaptation adaptation
blocking control
Local
workplace
Maintenance process
-·..d
Server database ---
Gate way
- I :. :I_
)
; ter- GPs
..
ill_ "l:L.. _z::_
_
--1 I :
I
.I,.!"........................................................................-(--- ::::::...; Station Bus Ethernet TCP /IP
m
c- Cabling
Cabling
)· 66kV
329
. !
15.3.3 This integration also enables more effective usage of Conventional load shedding with hard-wired relay
lines by allowing switching protection parameter sets logic is static In case of system voltage or frequency
e g. depending on weather conditions. This is one decline, the scheme activates tripping of pre-selected
prerequisite to the effective usage of a line's power circuit breakers regardless of the actual load condi
bearing capacity. tions. Microprocessor based load-shedding schemes,
however, are in the position to take the actual loads
15.3.2 Under-frequency initiated load into account and to dynamically select only those
shedding to avoid blackouts feeders to be opened, which are needed to regain
the frequency stability (Figure 15-5)
When tripping of power generation occurs on a net
work, the variation of frequency depends of several
dynamic factors in interaction such as the quantity of 15.3.3 High speed power transfer for
spinning reserve, the limitations of the prime mover uninterrupted power supply
system and the speed of governors, the inertia of the
power system or the sensitivity of customer load. This This is another typical example enhancing the power
phenomenon is particularly important on isolated availability for an industrial process. In case of a trans
power systems where the largest generating unit former fault the load is transferred to a second trans
represents a high proportion of the total demand. On former fast enough that the industrial process can
these kinds of power systems, many blackouts can continue without interruption (Figure 15-6). For a more
be avoided with the aid of well-tuned load detailed description refer to chapter 6.3.5.8.
shedding plans.
Se!ective tripping
according
132166kV
to actual loads
I
I
II ..1
I 1
u Busbar
J----------- -$--
. .
330
+
I, T.·················r·········
tu. ,I
j
Line F1
Line Protection Line Protection
15.3.5
High-Speed
Busbar Transfer
Transformer
Protection
Figure 75-6 High speed busbar transfer
1 5.3.4 Adaptive line distance protection to 15.3.5 Bay oriented busbar protection to
improve selectivity and flexibility maintain system integrity
The term "adaptive" is related to a protection philo A transmission substation busbar is a very sensitive
sophy, which permits automated adjustments of pro node in the network. Due to the convergence of
tection settings to make them more attuned to the many supply circuits high current values are involved.
prevailing power system conditions. A typical exam ple Busbar failures due to lightning strokes or connect ors
is adaptive distance protection (see Figure 15-7). melting because of overload are relatively rare, but
Transmission corridors often comprise lines that are when a fault occurs the damage can be wide spread
running parallel over long distances. Load shifting by causing disastrous cascade tripping of generators
from one line to another as a preventive or corrective and lines and finally the collapse of the entire power
measure, has to take into account the mutual impe system.
dance between the parallel lines. In addition to this, the
allowed power transmission capacity of one of the lines Busbar protection schemes have to be very reliable to
may have to be increased by corresponding adaptation of prevent unnecessary tripping and selective to trip only
the protection setting. those breakers necessary to clear the ousbar fault. The
clearing time is important to limit the dama ge caused by
It is crucial that the communication links between sta tion the fault current and the power resto ration time is
1 and 2 are of very high quality with regard to reliability crucial to maintain the power system integrity.
and real time behavior. 331
· · · '(
r----------------------------------1
I
& t
15.3.6
.... .r (: --······················ ------1 1--
Station 2
Station 1
........._f-, .,----...................---.,
_{ _{
•• 'P1 t= n} l;l•- --
I
---------------------------------1
Figure 7 5-7 Adaptive distance protection for parallel transmission lines
•
A bay oriented numerical busbar protection with
communication to a central evaluation unit· can be
upgraded to a complete station protection scheme to
contain in addition to the busbar protection function
also line or transformer protection functions and even
station level interlocking. This integration of functions
can further be used for fast auto-reclosure of those
busbar sections and transmission lines that are not
affected by the busbar fault. Thus the same hardware
provides in addition to the busbar protection a back
up protection or main 2 object protection, thus en
hancing the reliability of the station and reducing
costs for spare parts and maintenance (Figure 1 5-8).
GP
Figure 7 5-9 Power generator block control, protection and monitoring system
nerator protection and control together with SA may. 1 5.3.7 Power transformer
be more cost effective than to extend the legacy
protection control and
power plant control system.
monitoring
A solution with numerical control and protection IEDs
Periodic, off-line tests play an important role in eva
for HV bay control (BC), transformer protection (TP),
luating the general condition of transformers. But
generator protection (GP) and combined MV con
more and more utilities wish to have better informa
trol/protection (C/P) also allows monitoring of the
tion and are turning to a sophisticated process to
complete bay which comprises generator, DC exita
tion system, generator circuit breaker, auxiliaries with collect information while the equipment is still in
regulation transformer 6.3/22.0 kV, generator block ser vice. This on-line monitoring of the transformer
transformer 22/400 kV and the 400 kV switchgear aims at improved reliability, at early stage detection
(Figure 15-9). The voltage figures are typical exam of pro blems, and at reduced maintenance cost
ples only. But in the majority of cases, there are neither
com munication links nor suitable sensors
Again, more functionality with less hardware available for transformer monitoring from remote,
enhan ces the system reliability and reduces which is an ob stacle to install remote monitoring.
maintenance costs. 333
The installation of a modern transformer protection
IED together with a load tap changer control lED
in conjunction with
'? '-?
'? '? '?
1 5.4 Power system monitoring
to work systems harder and
to save costs
15.4 a cheep wide-area communication like Internet is a For once neglecting outages as a result of wrong
cost effective package for remote control of the tap human operation, there are basically three reasons
changer, load dependent control of the cooling sys for power interruptions:
tem, and for load adaptive protection as well as for
remote transformer monitoring. • The breakdown of a utility asset through
normal wear and ageing under working
The benefits are optimized transformer load control conditions.
and better exploitation of the transformer capacity • The outage of an asset being effected by an
(Figure 1 5-10). external event or fault.
• A temporary system disturbance where the
external influence disappears.
Maintenance
..
· '-!
15.4.3 Such data can be derived from disturbance record 1 5.4.3 Power system condition assessment
ings, which are either conducted by dedicated devic
for better knowledge
es or by IEDs with integrated disturbance recorders,
which belong to substation monitoring or substation
Centralized retrieval and transmission of data, and
automation systems as described in Chapter 9 (Figure
transforming data and information into knowledge
15-13).
enables the maintenance and protection engineer to
asses the condition of the entire power system.
lntenuplions
IVVVVVV
Sags
A4_/\_hJ
'j ·- ----- tianoi..C!I
>·.
I
-··.:.,·
·. -1\ /\-A f\ I
'E· t;r
If vv.,. v ' ·.· ,.,....... ··
Substation
l I
Figure 7 5-7 4 Central retrieval and evaluation of event and fault records 337
16 Guide to SA System Specification
339
16 Guide to SA System Specification
16.2 16.1 Introduction pen that a solution is selected that does not repre-
sent the state-of-the-art or is not optimised. On the ,I .
One of the prime objectives of this book is to guide other hand, the specification should allow enough
utilities being the users of SA systems to elaborate a flexibility that reputable manufacturers' standard tech-
technical system specification, which reflects their nology can be used that assures comprehensive, safe
specific needs and requirements in terms of and cost-effective substation automation solutions.
• operation philosophy, Any effort spent into the elaboration of this specifica-
• performance, tion is well invested as it results in high quality
tenders
• availability, that are submitted by the vendors and make the
eva-
luation and decision making process for contract
• maintainability, etc award easy.
in the beginning of the eighties, started slowly but A substation automation system shall provide on one
has been more rapid in the last few years. The origi- hand all the functions that are required for the
cor- nal question of whether microprocessor techno- red and safe operation of the primary
equipment logy should be applied in HV substations, has com- that is contained in a specific substation
as well as for pletely given way to the question of how it should the adequate protection and
condition monitoring. be applied, which is crucial for a SA system imple- On the other hand it has to
incorporate compatible mentation to succeed. But the specification should interfaces for the connection
of the substation with not restrict the vendor to a specific solution and be the switchgear (process
interface) and to one or general enough that vendors can design cost effec- more network control
centres (tele-control interface). tive solutions to meet the customer requirements.
The scope of functionality of a substation automation
The descriptions and recommendations contained in system depends on the following aspects:
Chapter 6: The functions of substation automation • Size and significance of the substation as well
Chapter 7: The substation automation structure as the range of voltage levels concerned.
Chapter 8: The substation automation architecture • Operational processes available to the ].Jser for
testing commissioning and operation, as well as
for maintaining bulh the substation and the SA--
provide comprehensive background knowledge and
address the most common users requirements and system. ,I
needs. It is recommended to specify mainly the tunc- • Availability requirements as a criterion related to II
tiona! requirements rather than giving preference to the substation's criticality and significance in the
340 any vendor specific solution. Otherwise, it may hap- grid or for consumers. I
l
• Integration of the substation control functions Self-monitoring of devices and communication by 16.2.1
into the user's network management concept, checking each function constantly whether all of its
with a varying number of network control levels corresponding functional partners are available will
and a different distribution of functions between have an impact on the system availability and safety.
network control centres and substation control.
• Decoupiing of the renewal cycles between The requirement to provide for easy future exten
substation control, power system management sions or upgrade of the system functionality at
and transmission technology. com petitive prices will most probably make the
supplier to use standard modular components.
• In case of retrofit, the integration into the user's
existing substation environment in terms of inter
faces to the existing equipment and coordination
with secondary devices dedicated for protection
and monitoring that are not substituted by 16.2.1 Crucial Questions to be addressed
new IEDs and have to be integrated in the
new substation automation system.
by the Specification
·
What are the utility specific data? • Name, address, type of business
• Responsible person
Where is the location and what are the • Geographical location
environmental conditions? • Environnemental site condition
e Location in the power grid
16.2.1
What is the type and size of substation (SIS) • Transmission or distribution S/S
that has to be covered by the SA system? • Voltage levels
• Single line diagram
• Type of switchgear bays
• Air insulated (AIS) or gas insulated (GIS) S/S
• New or extended S/S
How shall the substation automation system be • Communication to network control centers
integrated in the power system • Communication to engineering and maintenance
management? centers
• Common data model and allocated functions if
applicable
What is the role and importance of the • The impact of loss of power supply
substation in the power system? from specific lines
• Sensitivity of customers supplied
What are the availability requirements for • Indication of specific availability figures, or "low';
the SA system? "medium·;,high"
• Trouble shooting from remote (access,
response time)
• Availability of spares
What are the general requirements for the • New S/S or refurbishment of conventional
SA system, i.e. the boundary conditions? control and protection of an existing substation
• Details about the control building, switchyard
layout, cable trenches, lengths of cables
• Details of the grounding system and EMI condition s
• Outdoor or indoor installation of the kiosks
• Air conditioned relay and control rooms, yes/no
• Auxiliary power supply
What kind of process interfaces are available? • Conventional CT and VT
• Non-conventional sensors and actuator with
sample rates and accuracy classes
• Pre-processing of data in cases of "intelligent"
switchgear
• Integrated lED functionality in cases of "intelligent"
switchgear
342
What is the scope of functionality? • Operative functions for control,
protection, monitoring, and automation
• Functions for parameterization, testing and
diagnostics
• System configuration and maintenance procedures
• Communication including the related standards 16.2.1
• Remote access
..,
16.3 ,16.2.2 Example of a SA System If a Substation Automation system is needed very
Specification soon, the proprietary protocols may still be the right
solution, in particular for extensions of existing SA
The example of a substation automation system systems. Nevertheless, it may be advisable to address
spe cification enclosed in chapter 21 :Annex' is to be IEC 61850 in the specification for migration scena
con sidered a guidance only. For the various rios if applicable.
requirements specified, a comprehensive description
is available in this book. In any case, the following parts of IEC 61850 may be
helpful for writing the specification:
IEC 61850-3 Communication networks
and systems in substations - Part 3: General
requirements
IEC 61850-4 Communication networks and
16.3 Addressing IEC 61850 systems in substations - Part 4: System and
in the specification project management
IEC 61850-5 Communication networks and
The standard IEC 61850 (see chapter 13) will be systems in substations - Part 5: Communication
completely finalized in 2003/2004, and compatible requirements for functions and devices models
products and systems will be available for delivery
by For future projects, IEC 61850 should be a key
2004/2005, but the first readers of this book will requi rement both for retrofit and new substations
find the following references to this standard (see chapter 13).
already in
2003.
344
17 Strategy to Cope with the fast Changing Technology
345
17.4 17.1 Introduction 17.3 Availability of spares on site
Substations are living very long, and although ·their A conventional way to protect investments against a
secondary system might be exchanged two or three fast changing technology is to order a reasonable
times during the substation life time, its life time . stock of spare parts. There is a trade off between the
remains in the order of 10 to 15 years. During this numbers needed, the related cost and the aging of
time, the system has to be maintained. This means in spare parts meaning at least the expiration of the
minimum the replacement of failed parts, and very warranty. If there are too many spare parts any
often also extension of the system either by new improvement of the system over the time might be
bays or new functions. restricted. Also the costs of keeping spares for 10
years or longer are quite high, and there will always
For conventional systems, extensions were not a big remain a risk that there are not enough spares. So
issue as the electromechanical parts lived quite long. normally only an amount of spares to bridge delivery
For the other parts, manufacturers were selected and time span should be kept on site, and a contract with
contracts made that assured delivery of spare parts the manufacturer should assure spares for the remain
for this time, thus shifting the solution of problem to ing lifetime. As the manufacturer can make these
keep spares available to the manufacturers. However, contracts with many customers, his cost in
with the introduction of mainstream digital minimizing the risk to run out of spares is much
technolo gy, where every year a new HW lower. He can further decide himself if it is better
generation or ope rating system version appears to keep original parts, or compatible parts with new
on the market, the solution of the problem technology, even if they require a bit more
becomes more difficult. There are different adaptation effort at their first implementation.
approaches to handle this pro blem. Some are
more organizational, others more technical.
17.4 Use of standardized
communication
17.2 Vendor commitments
The use of international standards like IEC is always
Vendor commitments, as already done now, should recommended for long-term compatibility. As men
be part of the negotiations. For numerical technology tioned above, the key for system maintenance is a
they result normally in steps. For a very short period standardized communication, i.e. for substations IEC
(e.g. 2 years), originally parts will be available. After 61850. The standard IEC 61850 has also the advan
this time, compatible parts may be delivered. tage that it is based on a concept, which separates
Someyears later, devices with compatible functiona the application layers from the basic communication
lity will be produced only. Part of the negotiation will layers, thus allowing to exploit the benefits from the
be the length of these steps and the way of technical advances in communication (especially the
informa tion of the manufacturer about product lower layers of the stack) without loosing compatibi
replacement strategies and backward compatibility lity on the application level. The selection of lower lay
of products respective product versions. er standards like Ethernet and TCP/IP, which have al
Recommendations are found in IEC 61850-4. Do ready proven backward compatibility across a de
not forget that in a system the communication has velopment time of 10 years or more, supports this
to stay compatible if only
346 some parts are exchanged. strategy further.
1 7. 5 Use of a standardized 17.6 Functional specification 17.7
system description language
. To cope with the fast changing technology and not to
specify the past. it is strongly recommended to spe
To avoid starting any re-engineering for updates and
cify functions, quality and interfaces of systems only
extensions from the scratch, a standardized system
but not boxes and softwnre (see Chapter 16 "Guide
description language in form of computer read
to SA System Specification").
able files shall be used. The Substation Configuration
description Language (SCL) language of the standard The system description language mentioned above
IEC 61850 is such a language. As this language is can be part of this functional specification. It describes
manufacturer independent. it would allow with the needed functionality and its connection to the
relati vely low effort to replace devices from one switchyard in a form, which can be relatively easy
manufac turer with functional compatible ones used by a manufacturer to derive his system solution.
from another manufacturer, beneath allowing to
use technically advanced and functionally compatible It can then be complemented by a more detailed
devices of the same manufacturer. description of each function block
17.7 References
. ·
18 Trends and Outlook
349
18 Trends and Outlook
1.
18.3 18.1 Cha,nges in the Power Industry drastically, and, at least in technically developed coun
tries, each home will be accessible by communication
There are a lot of indications that the future_ power with relatively high bandwidth at reasonable costs.
systems will be much more decentralized than today, The new communication technologies via radio and
i.e. moving towards an Energy Web with the power with Web technologies will also push the use and
network as connection of a lot of small, distributed coordination of distributed generation e.g. with micro
energy generation units, comparable with the turbines, by allowing centralized control and mainte
Internet based World Wide Web. Maybe also other nance of these units from several competing compa
energy forms like Hydrogen will compete the electric nies.
power.
Fault evaluation
;,f· f,§tecti a- c· report (manual
·'-Ma1htenanC:"e evaluation)
Fault data
Disturbance Fault location,
recordings Short fault report,
SA/SMS
Systems (automatics)
Network
Control
Systems Maintenance
Asset Management
Systems
350 Figure 78-7 Non time-critical services for power system management
18.3
Utility
(asset owner)
.... --or-de rs
-·
Monitoring data .,J
--------------'flllll# \ Maintenance Service
Company,
Maintenance
management
Assets
system
nologies. As mentioned above, they will support the tion function. The feasibility of Internet technologies
access from and to any private home, to all offices for such applications cannot be claimed today but
and factories at reasonable costs. has to be carefully evaluated in the future. The
access security is also critical but there may be
As impact on industries including power system solutions from the home banking business. The
management, the Internet provides some alternatives studies in WG 15 of IEC TC57 address already the
to the existing information and control channels. In security aspects for all communications in power
chapter 13 was mentioned, that also modern com system applications.
munication standards like IEC 61850 are using TCP/IP,
which is the core element of Internet for information
routing. A mapping of IEC 61850 to Internet will be Non time-critical applications today like status super
possible in the future as well. The Internet client may vision, maintenance services, post-mortem fault ana
replace the HMis from today. lysis, asset management, meter reading and billing
are already in the trend using Internet technologies.
Critical are real-time applications or applications, which Distribution automation or the distributed generation
need a well-defined response time or data through according to the concept of virtual utilities may also
put. This is important especially for communication cause some challenges in Internet technologies.
between devices constituting a distributed automa- Some of those applications are oulined in Fig. 18-1
and Fig. 18-2. 351
18.4 Prospects in the Substation
Automation Business
The topics mentioned above, the distribution of ener • Central gathering of statistical and maintenance
18.5 gy generation and the general availability of low cost information can be taken over by central monitor
communication channels with high bandwidth might ing systems via Internet in combination with asset
influence the substation business as follows: · management.
18.5 References
352
r
· .,
19 References
Chapter 2 19
References
[1] Volker Lohmann (BBC/Switzerland), Andrew C. Bolton. (ESGOM/South Africa)
Gas insulated switchgear developed for 765 kV, Modern Power Systems,
February 1985, published by United Trade Press Ltd. London/UK
[2] Eric Engelbrecht (ESCOM/South/Africa), Bernhard Sander, Hermann Schachermayr (BBC/Switzerland)
Integrated control for ECOM's 800 kV ALPHA Substation, Transmission and Distribution,
Modern Power Systems, October 1987, published by United Trade Press Ltd. London/UK
[3] Klaus-Peter Brand, JUrgen Kopainsky, Wolfgang Wimmer · Topology based interlocking
of electrical substations, IEEE Trans. on Power Delivery PWRD-1, 3, 118-126 (1986)
Chapter 3
[1.1] Olle I. Elgerd · Electric Energy Systems Theory, 2nd ed., Mac Graw Hill, 1982
[1.2] Olle I. Elgerd, Patrick. D. van der Puije ·Electric Power Engineering,
2nd ed., Kluwer Academic Publishers, 1997
[2.1] Walter A. Elmore (Ed.) · Protective Relaying Theory and Applications,
Marcel Dekker, New York (1994)
[2.2] Helmut Ungrad, Wilibald Winkler, Andrej Wiszniewski · Protection Techniques in Electrical
Energy Systems, Marcel Dekker, New York (1995)
[3] Switchgear Manual, © ABB Calor Emag Schaltanlagen Mannheim, 1Oth revised edition,
Cornelsen Verlag, Berlin, 2001
Chapter 4
Ryan Bird ·Justifying Substation Automation, Black & Veatch, http//:tasnet.com/justa.shtml
Chapter 5
Switchgear
[1] Switchgear Manual· ©ABB Calor Emag Schaltanlagen Mannheim, 10th revised edition,
Cornelsen Verlag, Berlin, 2001
[2] KP. Koppel, B. Stepinski, H. Ungrad, K-P. Brand· New Sustation Concepts,
5th Conf. on Electric Power Supply Industry (CEPSI), Manila (1984)
SF6
[3] K-P. Brand, H. Jungblut · The Interaction Potentials of SF 6 /ons in SF 6 parent Gas
Determined from Mobility Data, Journal of Chemical Physics 78, 4, 1999-2007 (1983) 353
I
19 [4] K-P. Brand ·Dielectric Strength, boiling Point and Toxicity of Gases- Different Aspects
References of the same Basic Molecular Properties
IEEE Trans. on Electrical Insulation El-17, 5, 451-456 (1982)
[5] K-P. Brand, W. Egli, L. Niemeyer, K Ragaller, E. Schade · Dielectric Recovery of an Axially blown
SF6 -Arc after current Zero: Pt.!II- Comparison of Experiment and Theory
IEEE Trans. on Plasma Science PS-10, 3, 162-172 (1982)
[6] K Ragaller, W. Egli, K-P. Brand ·Dielectric Recovery of an Axially blown SF 6 -Arc after
current Zero: Pt./1- Theoretical Investigations, IEEE Trans. on Plasma Science PS-10, 3,
154-162 (1982)
[7] E. Schade, K Ragaller · Dielectric Recovery of an Axially blown SF 6 -Arc after current Zero:
Pt./ - Experimental Investigations, IEEE Trans. on Plasma Science PS-10, 3, 141-153 ( 1982)
[8] K-P. Brand ·A Model Description of the /on Mobility in SF6 at elevated Pressures,
Proc 15th lnt.Conf.on Phenomena in Ionized Gases (ICPIG) Minsk (1981), Part I, 301-302
[9] K-P. Brand, J. Kopainsky · Model Description of Breakdown Properties for Unitary
electronegative Gases and Gas mixture, Proc 3rd Int. Symp. on High Voltage Engineering (ISH),
Milan (1979), Paper 31.05 (4 pages)
[10] K-P. Brand, J. Kopainsky ·Breakdown Field strength of Unitary attaching Gases
and Gas mixtures, Applied Physics 18, 321-333 (1979)
[11] K-P. Brand, J. Kopainsky ·Particle Densities in a decaying SF 6 Plasma
Applied Physics 16, 425-432 (1978)
Sensors
[12] F. Engler et al. · Test and Service Experiences on Gas insulated switching Systems
and Substations with intelligent Control, Cigre 2000, Paper 34-101 (7 pages), Paris, September 200
Chapter 6
[1] Walter A. Elmore (Ed.) · Protective Relaying Theory and Applictions,
Marcel Dekker, New York (1994)
[2] Helmut Ungrad, Wilibald Winkler, Andrej Wiszniewski · Protection Techniques in Electrical
Energy Systems, Marcel Dekker, New York (1995)
[3]1EC 61850-5 Communication netvl/orks and systems in substations- Part 5: Communication
requirements for functions and device models ·
354
(4] K-P. Brand, J. Kopainsky, W. Wimmer · Mikroprozessor-gestatzte Verriegelung von Schaltanlagen mit
beliebiger Sammelschienenanordnung (Microprocessor-aided interlocking of substations with arbitrary
busbar arrangement),
Brown Boveri Technik 74, 5, 261-268 (1987)
[3] L. Andersson, K-P. Brand, W. Wimmer· The impact of the coming standard IEC67850 on the life
cycle of Open Communication Systems in Substations.
Distribution 2001, Brisbane, Australia, November 2001
[4] L. Andersson, K-P. Brand, W. Wimmer· The communication standard /EC67850 supports flexible
and optimised substation automation architectures, Integrated Protection, Control and Communication
Experience, Benefits and Trends, Session IV - Communication for protection and control. (pages IV-17
to IV-23), New Delhi, India, 10-12 October 2001.
(5] T Skeie, S. Johannessen, 0. Holmeide · Highly Accurate Time Synchronization over Switched Ethernet.
In Proceedings of 8th IEEE Conference on Emerging Technologies and Factory Automation (ETFA'01), pages 195-204,
2001.
[6] T Skeie, S. Johannessen, and C. Brunner· Ethernet in Substation Automation, IEEE Control Systems
Magazine, 22(3): 43-51, June 2002
[7] K-P. Brand, K Frei, 0. Preiss, W. Wimmer· A coordinated Control and Protection Concept
Medium Voltage Substations and its Realization, CIRED 1991
[8] 0. Preiss, W. Wimmer· Goals and Realization of an Integrated Substation Control System,
DPSP&C 1994, Peking, 1994 . .
[9] EWICS TC7, Dependability of critical computer systems, Elsevier Applied Science, London, 1988 [10] CIGRE
. ·
Chapter 9
[1] F. Engler, AW Jaussi ·Intelligent substation automation- monitoring and diagnostics in
HV switchgear /nsta!lations, ABB Review 3/1998
[6] V. Lohmann Integrated Substation Automation System Support: New Maintenance Strategies
°
for T&D Equipment Electrical Engineering Technical Exchange Meeting at Saudi Arabian Oil Company,
November 1998
[7] V. Lohmann, I. De Mesmaeker, B. Eschermann ° New Maintenance Strategies for Power Systems
supported by Substation Automation, Cigre Conference June 1999 in London/UK
[8] V. Lohmann, 0. Preiss · Less Impact of Power Failures Due to Substation Automation,
CIRED Conference, 1999 in Nice
Chapter 10
[1] Ryan Bird ·Justifying Substation Automation, Black & Veatch http/ /tasnet.com/justa.shtml
[3] V. Lohmann, J. Bertsch · Information Technology (IT) and the Application of Numerical Protection
and Control Devices to enhance management and Utilization of Power Networks, International
Distribution Utility Conference, Sydney/Australia, November 1997
[4] V. Lohmann ° Integrated Substation Automation enables new Strategies for Power T&D,
Southern Africa Power System Conference in Johannesburg/South Africa, November 2000
[5] V. Lohmann ° Advances in Power System Management Conference on Global Participation in Indian
International Grid, Energy Management and Convergence, Power Grid Corporation of India Ltd.
and Federation of Indian Chamber of Commerce and Industry, in Mumbai/lndia, August 2001 -
[6] RT Earp, MA. Lee, C. Proudfoot 0 Worldng the Protection Engineer Harder,
Cigre Symposium June 1999, in London/UK Paper No. 320-1
356
Chapter 11 ' 19
References
[1] Piere Cholley, Peter Crossley, Vincent Van Acker, Thierry Van Cutsem, Weihu Fu, Jose Soto lndianez,
Franc liar, Daniel Karlsson, Yasuhiro Kojima, James McCalley, Marian Piekutowski, Goran Rundvik,
Roberto Salvati, Olaf Samuelsson, Gilles Trudel, Costas Yournas, Xavier 'vVaymel,
System Protection Schemes in Power Networks, Ogre Study Committee Task Force SQF 38.02.19,
Final draft vS.O Conference lnternationale des Grandes Reseaux Electriques (Cigre), 2000
[2] Christian Rehtanz · Online Stability Assessment and Wide Area Protection based on
Phasor Measurements, Bulk Power System Dynamics and Control V, August 26-31, 2001,
Onoomichi, Japan
[3] Claudio Canizares · Voltage Stability Report, http:/ /www.power.uwaterloo.ca
[4] Defence plans major disturbances, Large Systems and International Connections Study
Committee 40.01 SYSTDEP, UNIPEDE, Paris/France
Chapter 12
[1] Switchgear Manual, @ ABB Calor Emag Schaltanlagen Mannheim, 1Oth revised edition,
Cornelsen Verlag, Berlin, 2001
[2]1nternational Electricity Commission (IEC): www.iecch
[3]1nstitute of Electrical and Electronic Engineers (IEEE): www.ieee.org
[4] Deutsches lnstitut fUr Normung (DIN): www.din.de
[5] International Standard Organization (ISO): www.iso.org
Chapter 13
[1] L. Andersson, K-P. Brand ·The Benefits of the coming Standard IEC16850 for
Communication in Substations
Southern African Power System Protection Conference, Johannesburg, November 8-9, 2000
[2] R. Dinges · Standardisierung in der Schutz- und Stationsleittechnik (Standardization
in Protection and Substation Automation)
ETG-Fachtagung "Schutz- und Stationsleittechnik'; Nurnberg, 23./24.10.2001
[3] K-P. Brand, W. Wimmer · Der Standard IEC 61850 - Offene Kommunikation in Schaltanlagen
im deregulierten Strommarkt (The Standard IEC 61850 - Open Communication for Substations
in the deregulated Electric Energy Market) Bulletin SEVNSE 93, 1 (2002) 9-13
357
., '? · I
19 (4] Ch. Brunner, A. Ostermeier ·Serial Communication Between Process and Bay Level - Standards
References and Practical Experience
CIGRE 2000, Paper 34-106 (9 pages), Paris,"September 2000
(5] J. Haude, A. Janz, Th. Rudolph, Th. Schaffler, H. Schubert · A pilot Project for testing the Standard
Drafts for Open Communication in Substations - First Experiences with the future
Standard /EC 67850
CIGRE 2000, Paper 34-109 (6 pages). Paris, September 2000
(7] L. Andersson, K-P. Brand, W. Wimmer· The Communication Standard IEC61850 supports flexible
and optimised Substation Automation Architectures
2nd International Conference on Integrated Protection, Control and Communication - Experience,
Benefits and Trends, Session IV, Paper 3, New Delhi, India, October 10-12, 2001
[8] L. Andersson, K.-P. Brand, W. Wimmer · Some Aspects of Migration from present Solutions
to SA Systems based on the Communication Standard /EC 67850
2nd International Conference on Integrated Protection, Control and Communication - Experience,
Benefits and Trends, Session IV, Paper 4, New Delhi, India, October 10-12, 2001
(9] L. Andersson, K-P. Brand, W. Wimmer· The Impact of the coming Standard IEC 61850 on the
Life-cycle of Open Communication Systems in Substations
Transmission and Distribution D2001, Brisbane, Australia, November 11-14, 2001
[10] Eric Udren, Steven Kunsman, Dave Dolezilek · Significant substation communication
standardization developments
Paper presented at the Western Protective Area Distribution Automation Conference (WPDAC),
April 2002
[11] Ch. Brunner, G. Schimmel. H. Schubert · Standardisation of serial/inks replacing parallel wiring
to transfer process data - Approach, state and practical experience
CIGRE 2002, Paper 34-209 (6 pages), Paris, September 2002
[12] R. Baumann, K-P. Brand, Ch. Brunner, W. Wimmer · Oer Standard IEC 61850 in Schaltanlagen
a/s Kern einer durchgangigen Kommunikationlosung fOr den Netzbetreiber
(The Standard /EC 61850 in Substations as nucleus of a transparent Communication Solution
for Network Operators), Bulletin ElectroSuisse94, 3 (2003)
358
· · ? '.:
Chapter 14 6.1.1.4.4.8
Chapter 17
[1] Standards see chapters 12 and 13 of this book
[2]1EC 61850-4 Communication Networks and Systems in Substations- Part 4: System
and Project Management
[3]1EC 61850-6 Communication Networks and Systems in Substations- Part 6: Substation
Automation System Configuration Language
[4] L. Andersson, K-P. Brand, W. Wimmer· The Impact of the coming Standard IEC 67 850 on the
Life-cycle of Open Communication Systems in Substations
Transmission and Distribution 02001, Brisbane, Australia, November 11-14, 2001
Chapter 18
[1] Steve Silbermann · The Energy WEB,
Wired Magazine,Issue 9.07. July 2001
359
Abt
A,·
Au
ABE
Ai
A•.
AG
A'
A
Au
AN
A_
AT<
fl..
si
si
I
8
BC
lc
CE
Cl
(I
L:
c
0
r
'
l
[
r.
.
20 Glossary
361
20 ECB Electronic Circuit Board 21.1.12
Glossary EHV Extra High Voltage 3.3.5, 6.3
EN European Norm 12.5.6
EM Energy Management 3.6.1.2
EMC Electromagnetic Compatibility 5.5, 12.5.6
EMI Electromagnetic Interference 3.4.3.2, 6.2
EMS Energy Management System 6.6, 10.2.2
Est. Estimated 10.2.4
G Conductance 3.3.4
GE General Electric 12.6.4.2.1
GIL Gas Isolated Line 3.3.4
GIS Gas Isolated Switchgear 3.5.1' 6.3
GIS Geographical Information System 15.4.3
GOOSE Generic Object Oriented System Event 13.5.1
GPS Global Positioning System; satellite system which beneath
location also broadcasts the exact time 6.3, 15.2.2
I Current 3.3.6
1/0 Input Output - signal or hardware category 6.2
IEC International Electrotechnical Commission 3.3.5
lED Intelligent Electronic Device, microprocessor based
programmable piece of electronics 3.7.2, 6.2
IEEE Institute of Electrical and Electronic Engineers
ISO International Standard Organization 12.1.1
ISQ Independent System Operator 9
IT Information Technology 4.1, 10.2.3
362
L lnductance 3.3.4
LCD Liquid Crystal Display 6.2
LD Logical Device 13.5.1
LED Light Emitting Diode 6.2
LLG Line-Line-Ground 11.6
LN Logical Node 13.5.1
LPC Local Protection Center 11.1 20
LV Low Voltage 3.3.5, 6.3 Glossary
M Motor 3.3.4
MMS Manufacturing Message Specification 13.5.1
MTBF Mean Time Between Failures 12.3.2.2
MTIF Mean Time ·ro Failure 12.3.2.2
MTIR Mean Time To Repair 12.3
MO Metal Oxide 5.5
MV Medium Voltage 3.3.5, 6.3
R Resistance 3.3.4
R Reliability (used for class indications: R1, R2, etc) 12.3.2.1
RCC Regional Control Center 3.6.1
RMS Root Mean Square, average (integrated) values for
AC current or voltage 6.2 363
20 RTNA Real Time Network Analysis 10.1
Glossary RTSC Real Time Sequence Control 11.6
RTU Remote Terminal Unit; data acquisition device of a network
control system within a substation 3.72, 6.6
u Voltage 3.3.6
UHV Uitra High Voltage 3.3.5, 5.2
ULG Under Load Tap Changer Control 11.6
ULF Under-Frequency Load Shedding 11.5
UPS Uninterruptible Power Supply 4.1' 21.1.18
us United States of America 3.3.3
364 UVLS Under-Voltage Load Shedding 11.5
VDU Visual Display Unit 11.1 20
VIP Voltage Instability Predictor 11.1 Glossary
vs Voltage Stability 11.6
VSA Voltage Stability Assessment 11.6
vsc Voltage Source Converter 5.6
VT Voltage transformer 6.2, 16.2.1
z Impedance 3.3.4
ZIP Impedance (Z)-Current (I)-Power (P) 11.6
(J) Circular frequency 3.3.6
365
21 Annex
i.
368
I
21 Annex communication functions. It shall enable local station control
via PC by means of a human machine interface (HMI)
and control software package, which shall contain an
comprehensive range of system con trol and data acquisition
(SCADA) functions. It shall include the communication
gateway, inter-bay-bus, intelligent electronic devices (lED) for
bay control and protection as shown in the general system 21.1
21.1 Example of a system architec ture in Figure 21-1.
specification
21.1.1 Utility data (at least contact address)
21.1.2.2 Design principles
21.1.2.1 Scope of supply The concept of station and bay level as indicated in Figure
21-1 results from the requirement that all pro cess and bay
This specification covers the design, manufacture, ins pection, oriented functions are to be processed on bay level while all
testing at the manufacturer's works and at site, packing for functions, which either concern more than one bay or need
export, shipment, insurance, trans port and delivery to site, information from more than one bay are to be allocated on
installation, commissioning, and maintenance during guaranty station level.
period including replacement of defective material for a period
of 12 months starting from the date on which the system has 21.1.2.2.2 Bay controllED
been taken over or for a period of 18 months after the
last delivery. The bay level intelligent electronic devices (lED) for control
shall provide the direct connection to the switchgear
The substation automation system (SA) shall comprise full station without interposing and perform the fol lowing control and
and bay protection, control, monitoring and monitoring functions:
Station Level
lnterbay bus
Data Exchange
Bay Level Bay Control Bay Protection Bay Protection Bay Protection
lED !ED lED lED . 369
Bay1 Bayn
Data exchange between the bay control level and 21.1.2.3.2 CE-marking
station control level, as well as between the different
IEDs depends on the function assignments. Each lED • EN 50081-2 Emissive (Industry)
370 shall exchange data directly with any other !ED de- • EN 50082-2 lmmun!ty (Industry)
j
21.1.2.3.3 General for Substation Automation
•IEC 61850
21.1.2.3.4 Detailed
• IEC 60255-6: Measuring relays and • IEC TS 61000-6-5 Electromagnetic interference 21.1.3
protection equipment (EMC)- Part 6:- Generic standards- Section 5:
• IEC 60255-7: Test and measurement Immunity of power station and substation envi
procedures for electromechanical ali-or-nothing ronment including all referenced and applicable
relays parts of the standard family IEC 61000.
372
2 7. 7 .4.4 Quality assurance and inspection
2 7. 7 .4.2 Project specific requirements The SA system shall be full-sized pre-assembled and 21.1.5
tested at the vendor's workshop before shipment
Specific functionality and boundary condition of the and subject to inspection by the responsible person
SA shall be adapted to the requirements, which are nel of the buyer.
related to the particular voltage level and the
specific substation layout. The project specific
drawings are attached:
21.1.5 System design
• Overall single line diagram
• General system architecture 2 7. 7 .5. 7
• Location of substation General
buildings
• Control and operation The system shall be designed so that personnel with
principles out any background in microprocessor based tech
• Protection nology is in the position to operate the system easily
schemes after they have been provided with some basic train
Ing.
2 7. 7.43 Vendor's experience and local System control via a Personal Computer (PC) shall be
support mouse operated and the following HMI (Human
Machine Interface) functions shall be provided (Figure
Only experienced and technically capable manufactu 21-2):
rer of control and protection systems for electricity
transmission and distribution applications will be • Acquisition and plausibility check of switchgear
accepted. Preferred manufactures are those who status
have experience in deliveries of the full scope of sta
• Control of switchgear
tion automation systems, and services. This
experien ce has to be substantiated by means of • Remote checking of protection parameters
reference installations being in service under and optional activation of alternative parameter
similar environ mental conditions for at least 2 years. sets
If a new func tionality is requested, this time span • Display of actual measured values (U, :, P, Q,
may be reduced or skipped for this special f)
functionality. • Display of events
In order to assess the vendor's experience with the • Display of
enquiry, the vendor is required to present the follow alarms
ing with his bid: • Display of measurands and
trends
• Technical design specification and description
of SA • Sequenced control functions
• Catalogues and brochures of equipment • Disturbance records and fault location
and devices offered • System self-supervision
• Reference list • Hard copy printing
The vendor shall assure for long-term maintenance The offered SA shall support remote control and
and availability of spares. Moreover, a guarantee monitoring from NCC/SCADA centers via gateways
shall be submitted for the availability of spares that are either integrated into the station PC or inde
during the pendent IEDs depending on the availability require-
lifetime of the SA equipment (not less than10 years). ments. · 373
'( '?
,
21.1.5.3.1 Operator
station
Direct manual control facilities will be Failure of any single component within the equip
incorporated in the switchgear, which ment shall neither cause unwanted operation nor
can be used in case of mainte nance lead to a complete system breakdown. The n-1 crite
or emergency. Direct switchgear control ria must be maintained also in worst case scenarios.
would be conducted without any Further, a single failure must not have any affect on
interlocking. Local bay control via the primary system that is monitored and controlled.
local HMI shall provide the same
user safety measures e.g. bay
interlocking, synchro-check as well as
21.1.5.3.4 Required quantity of inputs
user guidance etc. as the station HMI.
and outputs
Local bay control shall be key-locked
and the control either from station The signal quantity is as listed below for each bay:
HMI or from remote shall be disabled
if the local/remote selector switch is (to be specified in the specific enquiry) 375
in the local posi tion.
engineer for modifications. The system software shall
support the generation of typical control macros and
comprise a process database for user specific data
storage.
The IED system software shall be structured in If the complete system consists of parts from various
various levels. This software shall be placed in a suppliers or some parts are already installed on site,
non volatile memory. It lowest level shall assure the FAT shall be limited to sub-system tests. In such a
system performance and contain basic functions, case, the complete system test shall be performed on
376 which shall not be accessible by the application and site together with the site acceptance test (SAT).
maintenance
21.1.8.1.2 Status SupetVision
The time reference within the SA system shall be set The HMI shall provide the operator with access to
from the station HMI or from an external clock alarm and event lists to be displayed on the screen.
syn chronization unit. The time shall then be Besides of these lists on the screen, there shall be a
distributed to the control/protection devices via the print out of hard copies of alarms or events in an
interbay bus. The time synchronization shall be event log.
performed either via the bus or via a separate
An acoustic alarm shall indicate abnormalities and all
wiring for the minute pulse. The required accuracy
unacknowledged alarms shall be accessible from any
is ± 1 ms within the bay and within the station. For
screen selected by the operator.
sampling, the time accu racy has to be better than
25 f.!S. Following standard pictures shall be available from
the HMI:
21.1.8.1.7 Synchronism and energizing check
• Single line diagram showing the switching
The synchronism and energizing check functions shall status and measured values
be distributed to the control and/or protection devi • Control dialogues
ces and have these features: • Measurement dialogues
• Blocking dialogues
• Adjustable voltage, phase angle, and
frequency difference. • Alarm list, station/bay oriented
• Event list, station/bay oriented including
• Energizing for dead line - live bus, or live
acknowledgement functionality
line - dead bus.
• System status
• Settings for manual close command
and • Checking of parameter setting (optional)
l·
• Operator actions
• Position changes of circuit breakers, isolators
and earthing devices ·
5 Indication of protective relay operations
. '?
. ·.
. ·
21.1.8.3.3 Closed-loop commands to switching devices and
control auxilary equipment.
• Tap changing of transformers,
The following closed-loop control functions
have to be assigned to the various system earth-fault neutralizers: Tap changing
levels according to the Table 21-3. of transformers or earth fault neutralizers
start up and shut down of tap change
control.
21.1.8.3.3 • Unit/individual control: Output of
single, double and adjusting
• Double command lock-out: Checking if • Monitoring of command delay:
parallel commands are selected with the Command release disconnection after
aim to avoid the output of several execution or after
commands at the same time. a defined time if commands have
not been executed properly.
• Switching sequences: For various
tasks, switching sequences may be
stored as a chain consisting of individual
controls or to simplify operating
processes or to make them safer (e.g.
transformer change, by isolation and
earthing).
• Automatic change over switching:
Switching sequences which are carried
out when certain external events occur,
without interference of an operator.
• Automatic acknowledgement:
Command output for resetting the
transient earth-fault relay after a defined
time.
function
Unit/individual control X
Transformer tap changing, X
earth-fault neutralizers
I
Double command lock out X
I
Monitoring of command delay
X
Switching sequences I
X X
Automatic change-over switchi11g X X
X
Automatic acknowledgement
X
Synchrocheck
X
Bay interlocking
X
Station interlocking X
! •
X Control transformers
. r
Assignment to Bay control Station and network control level
or process
level
System tasks Bay control Local Telecontrol Archiving Central
or process
interface unit
control function
21.1.8.3.4 Time synchronization X X
Information inhibition X
System configuration X X
System information X
Self-monitoring X X X X X
Other functions
Acquisition of metered X
measurands
Archiving X X
Data listing X
Information data base
management X
Protocol conversion X
Fault recording X
Protection device interfacing (X) X
adding up impulses offered via a time frame or • Fau!t recording: There are three possibilities of
by an accepted International Standard for meter fault recording:
readings.
• Via digital protection devices
• Archiving: Information like measured • Via external fault recording devices
values, metered measurands, alarms and
events must be archived in a non-erasable • Via an internal function of the control
way for later evaluation. equipment
• The faults must be archived in
• Event and status listing: If necessary, sponta
neous or requested operational events and status the station control system,
print-outs as defined by certain sorting criteria, including their time tag, and
on a VDU or printer. stored there
for evaluations.
• Protocol conversion: The conversion of the
internal representation of information and • Protection device interfacing: The serial
commands into other formats for network control interfacing of the protection devices shall be
386 centers. possible according to international communication
standard, i.e. IEC 60870-5-103 or IEC 61850.
. · .
. (
mary voltage shall not be used for more than 100
ms.mory voltage shall not be used for more than 100
ms. For the close on a three-phase faults, which
last longer than 100 ms, a seal-in function shall be
ap plied that prevents auto-reclosure.
The protection scheme shall be an integral part of It shall be possible to select between the directional
the SA system. AIIIEDs shall be integrated for data and non-directional alternative, when choosing the
shar ing, and meet the real-time communication earth-fault current protection function. Its operation
require ments for automatic functions. The data shall be based on the measurement of the zero
presentation and the configuration of the various sequence quantities of the protected line. The mini
IEDs shall be compatible with the overall system mum operate current should be < 10 %. The mini
communication and data exchange requirements. mum operate voltage must be < 1 % of the rated
vol tage. The time delay should be selectable
The project specific protection requirements shall be between independent and all standardised
specified accordingly. The following describes the pro dependent time characteristics (IEC curves).
tection functions in general terms.
Separate communication schemes must be available
for the earth fault function.
21.1.9.7 Line protection
As an alternative for high impedance grounded
The numerical line protection devices shall be select
systems, additional sensitive earth-fault protection,
ed for the protection of lines according to specific
operating on a watt-metric or transient (Wischer)
the network configurations and conditions. The
principle, may be required, if it is required to detect
sche me must ensure reliable isolation for all kind of
transient earth faults.
faults, which might occur on the specific line.
Depending on voltage level and complexity, the
following line protection functions may be 21.1.9.1.3 Communication
links
required.
A wide range ·of permissive tripping and blocking
21.1.9.1.1 Distance function scheme communication logics shall be available for
the distance protection as well as for the
The maximum operate time of distance protection
directional earth-fault current protection. Scheme
Zone 1, specified for a SIR 10 and faults within 50%
logics should be independent for both protection
of a set reach, must not exceed 45 ms (MV), 40 ms
schemes with independent communication links.
(HV), 20 ms (EHV). This shall be substantiated by
For EHV. the distance protection scheme shall
isochrone diagrams, which have been measured on
have a logic for phase segregated communication
protection terminals connected to similar capacitive
for current single pole tripping also in case of
voltage transformers and to current transformer as
simultaneous fault on double circuit lines Standard
specified. The guaranteed tripping time shall include
logics such as current reversal, weak end infeed
the output relays. The minimum operate time of a
echo and trip shall be pro vided for both protection
protection shall not exceed 30 ms (MV), 25 ms HV.
functions. Logics operating without separate
13ms (EHV). The earth fault measurement in
reverse directed measuring-- ele ments are not
distance
acceptable.
zone 1 shall be compensated for load currents. The
directional discrimination shall be based on the use of 21.1.9.1.4 Event and disturbance
phase-locked positive sequence voltage, and shall
recording function
provide unlimited directional sensitivity for all unsym
metrical faults. The positive-sequence memory volta A line protection terminal shall provide the user local
ge shall be used at close three-phase fault. The me- ly or remotely with complete information on the last 387
. '(
. '
Continuous self-supervision function with self-diag 2 7. 7. 7 7.2 Access via the control
nostic possibilities must be included in a transformer center
terminal.
Remote access to the substation data shall be enabl 389
ed from the control centers and from Engineering
centers upon request. All information which are relat-
. '.: . ·
21.1.12 System performance
21.1.12 ed to the condition of high voltage apparatus shall be Function Typical values
directly accessible by the respective owners in the uti-
lity organization. Exchange of display (first reaction) <1s
.Presentation of a binary change < 0,5 s
The communication with control centers shall be in the process display
single or redundant (option) and comply with the fol
lowing protocols: Presentation of an analogue change < 1s
in the process display
(to be specified in tender)
21.1.11.4 Terminal parameter setting Each action by the operator must be logged as event
and result in a reaction from the system. The latter
It shall be possible to access all protection and control may be visible or audible, and either confirms the
devices for reading the terminal parameters (settings). operator input or rejects it. Rejections must contain an
_The setting of parameters or activation of parameter explanation with easily understandable error mes
sets shall be restricted by e.g. password to the au sages. The starting and ending of an operator input
thorized protection engineer. must be user friendly at all control levels.
• System configuration
• System testing
• Help functions
• Program documentation
• Down- and up-loading of
programs
& System comm;ss;on1ng
• Data base
management 391
• Changing peripheral
parameters
21.1.18 The engineering system shall be able to monitor data The identification of the inqividual components and
in the running substation control system and to pre the structure shall be in accordance with the relevant
sent changing variables on the display screen in gra IEC standards.
phic representation.
• Electronic
information 21.1.18 General documentation
• Standardized substation configuration
file written in SCL according to 2 7. 7.7 8.7 Standard
IEC 61850-6 documentation
All documentation should be consistent and include Standard documentation is the description of
all information required for operation, maintenance, systems, equipment and functions of a manufacturer,
inspection and repair of the station. which is universally valid and which should not be
adapted to a specific project. It includes:
• Equipment documentation
21.1.16 Hardware documentation • Equipment instruction
manual
The hardware documentation of the control system
• System description
is to be carried out according to the same structure
as the documentation of the other station units and • Description of functions
392 is an integral part of the complete documentation. • Operating instructions
• Fault description
• Service programs
21.2 Assessment of
Wide Area Protection
393
:_-._
394
4 Frequency instability control Yes No 21.2
4.1 The primary spining reserve ...........% of demand maintained all the time
4.2 Network splitting on under-frequency at the boundaries of the utility
4.3 Load shedding from ........... Hz with ........... seconds time delay
4.4 Others
5 Undamped power swing control Yes No
What preventive measures are taken?
5.1 Real transfer power transfer limits must not be exeeded
5.2 Reactive power absorption limits must not be exeeded
5.3 Low voltage limits on generators must not be exeeded
5.4 WAPS implemented on important generators
5.5 Others
What are the curative actions taken?
5.6 Reduction of real power transfer
5.7 Increase of reactive power generation on concerned generators
5.8 Increase of reactive power generation on synchronous compensators
5.9 Actions on DC lines
5.10 Disconnection of radially connected part of the system
5.11 Others
6 Loss of synchronism control Yes No
What preventive measures are taken?
6.1 Security rules in planning and operation stage are to be followed
6.2 Fast valving is conducted on thermal generation units
6.3 Preventive automatic load shedding
6.4 Preventive automatic unit shedding
6.5 Others
What curative actions are taken?
6.6 Generators are disconnected by out-of-step relays
6.7 Generators are disconnected by under-voltage protection relays ·-
6.8 Generators whitout fast valving are tripped rapidly
6.9 Out-of-step relays on some lines
6.10 Blocking of distance protection relays against power swings
6.11 Others
395
. · . '(
21.2 7 Cascade line tripping control Yes No
What preventive measure are taken?
7.1 Security rules are followed in planning and operation stage
7.2 Provision of power swing blocking relays
73 Provision of out-of-step relays
7.4 Early automatic load shedding
75 Early automatic unit shedding
7.6 Others
What curative actions are taken?
7.7 Fast manual load shedding by remote control from control center
7.8 Fast manual action on generators power set-point
79 Starting fast power reserves (gas turbines, hydro units)
7.10 Others
8 Coordination of problems with interconnected utilities Yes No
Exchange of information related to
8.1 Non-availability or loss of important lines
8.2 Temporary weak points in generation
8.3 Major disturbances in power generation
8.4 Deviations os scheduled power exchange
8.5 Changes of reactive power flows and voltage conditions
8.6 Load on tie-lines
8.7 Signals of tie-lines breakers
8.8 Voltage values on busbars
8.9 Real and reactives power values on tie-lines
8.10 Common studies to meet future reqirements
8.11 Others
396
-.
·
Recommended compementary measures or actions for
1 Voltage instability control Required Notrequ.
1 '1 Coordination between neighbouring utilities on reactive margin management
1.2 Coordination between neighbouring utilities on voltage profile control
1.3 Implementation of OLCT blocking at all critical transformers 21.:
1.4 Coordination of OLCT voltage references
1.5 WAPS like load shedding subject to particular network conditions/events
2 Frequency instability control Required Notrequ.
2.1 Automatic load shedding plan for the interconnencted power system
2.2 The load shedding plan should operate in the range of 48 - 49 Hz
2.3 The maximum load shedding shouid be about 40 - 50 % of the demand
2.4 Coordination of the main steps for power restoration
3 Undamped power swings control Required Notrequ.
. ...
397