Spectra Series Switchboards
Quick Reference
imagination at work
Main Lug Main Device Switchboard Frame
Neutral Bus
Switchboard Frame Width (W)
Neutral Bus
Width (W)
10” Cover 3” A
Ref. 20”
3” Ref.
Cover A
Ground
Bar Main
Ground
C
Bar
Circuit
Breakers 90”
and/or C Panel
Circuit Breakers “X”
90” Fusible
and/or Height
Switches Panel
“X” Fusible Switches
See Height
Branch See Branch
Sizing Sizing Tables
Tables
Cover B
Cover B
1.50 25”
Typ. 3”
1.50 25” Front View Side View
Typ. 3”
Front View Side View Cable Fed Main Devices With or Without CT’s
Top Bottom
Standard Main Lug Termination Main Min. Panel
Amp Main Main
Type Device "X" Width "X"
Quantity and Size Minimum Width Range
Ampere Rating Height (W) Height A B C A B C
per Ø and N (W)
400 & 600 (2) 1/0-600MCM 30 SGDA,
800 & 1000 (3) 1/0-600MCM 30 SGHA, 400-
4 35 38X 14 21 49 14 21 49
1200 (4) 1/0-600MCM 30 SGLA, 600
Circuit SGPA
1600 (5) 1/0-600MCM 30 Breakers
2000 (6) 1/0-600MCM 30 SKHA,
800- 40③
2500 (8) 1/0-600MCM 30 SKLA 6 38X② 14 14 56 23 21 56
1200
3000 (9) 1/0-600MCM 30 SKPA 45
4000 (12) 1/0-600MCM 40 4/600-
10 45 38X 14 7 63 0① 21 63
5000 (15) 1/0-600MCM 45 H,K,R
Fusible 4/600-
ADS 10 40 38X 14 7 63 0① 21 63
Switch J,T
800-
Panel Rating Panel X Height (X=1.375") A B C 19 45 43X 14 7 63 0① 21 63
1200
23X 21 28 35
① Rear access required.
28X 21 21 42 ② SKHA and SKLA available in 48X.
400-2000A 33X 21 14 49 ③ Minimum width may vary due to breaker cable size and quantity.
38X 21 7 56
43X 21 0 63
5 2.5 (Typ.) 3.12 (Typ.)
Note: For bottom feed, reverse A & B dimensions.
Conduit Space
(Typical all
.625 Dia. (Typ.) Selections)
Mounting Holes
Section Layout Notes
Distribution Section • These switchboard arrangements assume line cables enter top.
When line cables enter from below, neutral and ground bus are
Panel "X" Height A B C mounted at bottom, and A and B cover dimensions are reversed.
23X 21 28 35 • All dimensions are in inches and X values (1X = 1 3/8 inches).
28X 21 21 42 • Front access to load cables requires a 7" high cover minimum.
33X 14 21 49 • Front access to neutral and/or ground bus requires a 14" high
38X 14 14 56 cover minimum.
43X 7 14 63 • Any circuit breakers with externally wired accessories (such as
53X 7 0① 77 shunt trip, undervoltage release, auxiliary switches) will require a
① Rear access required.
1X filler between adjacent devices.
• For double branch units, only same circuit breaker type devices
can be mounted across from each other.
Distribution section front view same as main lug section.
• All single branch circuit breakers, in service entrance equipment,
Distribution section side view same as main lug section side are mounted with load lugs staggered to allow for equal cabling in
view except omit lugs. both wire gutters. Main device line lugs are located on the left side.
• After determining all applicable conditions, lay out switchboard
and calculate branch circuit "x" heights, including future space.
Add spaces sufficient to fill panel to standard X increment.
1
Interrupting Rating, RMS symmetrical (kA)
Record Plus
Frame 100A 250A 600A
Size FBV/FCV FBN/FCN FBH/FCH FBL/FCL FCS FEN FEH FGN FGH FGL FGP
240Vac 65 150 200 200 42 150 200 150 200 200 200
480Vac 35 65 100 150 25 65 100 65 100 150 200
600Vac 22 25 35 42 18 — — 25 35 42 65
Insulated Case Circuit Breakers – Main Devices GE HPC Switch Interrupting Ratings
Power Break II Available Ratings Contact
Frame Size 800A 1600A 2000A 2500A 3000A 4000A Interrupting Switch-fuse
Standard Rating Based on Combination
240Vac 65 85 85 100 100 100
Type Continuous Maximum Ability to Operate at Switch-rated
Amperes ac Volts on Overload ac Volts with
480Vac 65 65 65 100 100 100
Unassisted by Class L Fuse
600Vac 50 50 50 85 85 85 the Fuse
High-Break
800, 1200, "Open" -
240Vac 100 125 125 200 200 200
1600, 2000, 12X amp rating;
480Vac 100 100 100 150 150 150 HPC/R 600 200,000
2500, 3000, "Close-Open" -
600Vac 65 65 65 100 100 100 4000 12X amp rating
Short-time
(0.5 sec) 25 30 30 42 42 42
2
Molded Case Circuit Breaker Branch Device Sizing – Molded Case Circuit Breaker Branch Device Sizing –
Plug-In Bolt-On
3-Pole 2-Pole 3-Pole 2-Pole
Max. Min. Min. Max. Min. Min.
Breaker Module② Module② Breaker Module② Module②
Mounting Breaker Width Depth Mounting Breaker Width Depth
Frames X X Frames X X
Amps (in.) (in.) Amps (in.) (in.)
Height Height Height Height
THQB, THHQB, TED, FB 3 2 35 25
3 — 35 25
TEY, TEYF TEY, TEYF 3 — 35 25
100 SE, SF 3 3 35 25 100
SE, SF, THED 3 3 35 25
SG 4 4 40 25
SG 4 4 40 25
FB 3 2 35 25
TEB, TED, TED 3 2 35 25
3 2 35 25
TQD, THQD 150 SE, SF 3 3 35 25
150 THED, SF 3 3 35 25
SG 4 4 40 25
SG 4 4 40 25
SF 3 3 35 25
TQD, THQD 3 2 35 25 Double 225
225 SF, FE④ 3 3 35 25 SG 4 4 40 25
Double
SG 4 4 40 25 SF, FE④ 3 3 35 25
250
TJD 6 6 45 25 SG 4 4 40 25
250 SF 3 3 35 25 400 SG 4 4 40 25
SG 4 4 40 25
SG, FG 4 4 40 25
TJD 6 6 45 25
400 micro-
SG 4 4 40 25 600① EntelliGuard
4 — 40 25
SG, FG 4 4 40 25 trip unit SGHC,
micro- SGLC, SGPC
600① EntelliGuard SF 3 3 35 25
4 — 40 25 250
trip unit SGHC,
SG 4 4 35 25
SGLC, SGPC
Double 150 SEDA, SEHA, SG 4 4 35 25
4 4 40 25 400
Adjacent SELA, SEPA SK 6 6 40 25
to Fusible SFHA, SFLA,
Switch 250 SFPA
4 4 40 25 SG, FG 4 4 35 25
SF 3 3 35 25 micro-
250 Single 600 EntelliGuard
SG 4 4 35 25 4 — 35 25
trip unit SGHC,
TJD 6 6 35 25 SGLC, SGPC
400
SG 4 4 35 25 SKH, SKL 6 6 45⑤ 25
SG, FG 4 4 35 25
micro-
micro- 1200 EntelliGuard
Single 600 EntelliGuard 6 — 45⑤ 25
4 — 35 25 trip unit SKHC,
trip unit SGHC, SKLC, SKP③
SGLC, SGPC
① Double branch mounting available through 3000A.
SK 6 6 45⑤ 25
② Add 2x to height for accessories on breakers.
micro- ③ SKP requires 45" minimum width if used as a main breaker with cables.
1200 EntelliGuard ④ FE shown at 100kAIC at 3X. If 150 kAIC, then X height is 5X.
6 — 45⑤ 25
trip unit SKHC, ⑤ Minimum width may vary due to breaker cable size and quantity.
SKLC, SKP③
Single SF 4 4 40 25
Adjacent
250
to Fusible
Switch SKP 6 6 45 25
① Double mounting not available in 2500A or higher main bus rating.
② Add 1x to height for accessories on breakers.
③ SKP requires 45" minimum width if used as a main breaker with cables.
④ FE shown at 100kAIC at 3X. If 150 kAIC, then X height is 5X.
⑤ Minimum width may vary due to breaker cable size and quantity.
3
Outdoor Enclosures
NEMA 3R outdoor enclosures consist of standard indoor • Front extensions: non-walk in 5" & 10", walk in 35" & 40"
cubicles and components enclosed with a front frame and • 110 mph wind rating
roof assembly to provide a weather resistant structure. Any • Floor sills 1.5"
number of sections may be bolted together. However, all
sections must be of the same depth. Standard outdoor con- Options available are:
struction consists of: • Gasketing
• Flat roof • Fluorescent light, 120-volt, 15-amp and grounded
• Section height 91" convenience outlet
• Front and rear venting • Rodent guards
• Galvanized end caps, front/rear louvered doors and rear covers • Rear doors same as front with wind stops
• Standard screen behind louvers • Lifting brackets
• Single door 15"W – 35"W • Inside, movable, 4-way hoist and trolley (walk-in only)
• Double door 40"W – 60"W • Busway entrance
• Wind stop on each door • 130 mph wind rating
• 3-point catch with provisions for padlock • Filters
91”
91”
15W to 35W
Single Doors
PL
A V 8” 8”
AS VS
PB
4
Main Devices (Inches)
Device Stationary Draw out
Type Ampere Min. Unit Min. Section Min. Section Min. Unit Min. Section Min. Section
Designation
Rating Height Width Depth②⑥ Height Width Depth②⑥
800 28"① 30" 25" -- -- --
1200 32① 30 25 -- -- --
THPR⑦
High Pressure 1600 32 30 25 -- -- --
Contact 2000 40 30 25 -- -- --
Switches 2500 44 35 30 -- -- --
THPC 3000 44 40 35 -- -- --
4000③ 52 40 40 -- -- --
800 28 25 30 -- -- --
1200 32 30 30 -- -- --
1600 32 30 30 -- -- -- ① CT compartment on line
Bolted Pressure side requires 4" filler.
QA or CBC 2000 32 30 30 -- -- --
Switches ② If metering CTs are
2500 36 35 35 -- -- -- required, add 5" to
3000 48 45 35 -- -- -- depth. For devices at
extreme top or bottom,
4000 48 45 35 -- -- -- depth shown may not
25⑤ provide sufficient conduit
MCCB Standard SG 600 20 25 -- -- -- entrance space. See
& Hi-Break SK 1200 24 25⑤ 25 -- -- -- Section 5.10 for conduit
space available.
30 800 -- -- -- 28 30 40④ ③ When integral ground fault
50 1600 -- -- -- 28 30 40④ is present, a 4" filler is
required on the load side.
T50H 2000 -- -- -- 28 30 40④ ④ Additional depth for
WavePro
75 3200 -- -- -- 32 35 50 metering CTs not required
for any stationary units or
100 4000 -- -- -- 32 40 50④ for electrical drawout units.
125 5000 -- -- -- (refer to factory GE-Houston) ⑤ 30" width is recommended
for 1200A devices or
Metering -- -- 25 25 -- -- -- when more than three
Ground Fault- devices are stacked in
-- 8 25 25 -- -- -- one section.
Ground Break ⑥ If vertical neutral bar is
Automatic 800 -- 28H x 35W x 35D -- -- -- required, add 5" to depth.
⑦ Not available in electrical
Throwover 4000 -- 28H x 35W x 35D -- -- -- unit.
GE Energy
41 Woodford Avenue, Plainville, CT 06062
www.geindustrial.com
© 2011 General Electric Company
imagination at work
DE-280C (07/11)