FIRE FIGHTING NON-COMPLIANCE LIST

Project : NSK Micro Precision Sdn Bhd


Location : No.43, Jalan Taming Dua, Taman Taming Jaya, 43300 Balakong, Selangor Darul Ehsan.

Passive Fire Requirement

Non-Compliance Comments By-Laws/Standards/Guide


Protected Escape - Provide additional door leading - UBBL 2012
Staircase to outside at NSK 1 and 2.

Active Fire Requirement

Non-Compliance Comments By-Laws/Standards/Guide


Sprinkler System - Provide additional sprinkler - MS1910: 2017
point where it is not
available.
Hose Reel System - Add additional hose reel to - Ketetapan Teknikal
comply with 30m point to Bomba 2012
point at NSK 1, 2 and 3.
- To be located outside of
protected staircase.
Smoke Spill System - To install smoke spill system - UBBL 2012
at clean room 1st Floor NSK 2 - MS1780: 2015
- To re-design and install
smoke spill system at NSK 1
and 2.