Transformer / Reactor:: Typical Limiting Values of Sub Station Electrical Equipments
Transformer / Reactor:: Typical Limiting Values of Sub Station Electrical Equipments
Transformer / Reactor:: Typical Limiting Values of Sub Station Electrical Equipments
1. Transformer / Reactor:
Sr.
Equipment / test data
No. Permissible limits Reference
Transformer oil
a) BDV
-At the time of first charging 60 kV (Gap – 2.5 mm) – Minimum IS – 1866
2. Circuit Breakers
Sr.
Equipment / test data
No. Permissible limits Reference
D) PIR time
Manufacturers
NGEF make
8-12 MS Recommendations
Manufacturers
M&G make
8-12 MS Recommendations
Manufacturers
TELK make
8-12 MS Recommendations
Manufacturers
ABB make (HVDC)
8-12 MS Recommendations
H) Capacitance of grading capacitors Within + 10% / -5% of the rated value IEC 359
K) IR value:
3. Current Transformer
Sr.
Equipment / test data
No. Permissible limits Reference
IR value
4. Capacitive Voltage
Sr.
Equipment / test data
No. Permissible limits Reference
IR Value IR Value
5. Isolators
Sr.
Equipment / test data
No. Permissible limits Reference
IR value
6. Surge Arrester
Sr.
Equipment / test data
No. Permissible limits Reference
7. Miscellaneous
Sr.
Equipment / test data
No. Permissible limits Reference
B)
Temp. above 15-50 Deg. C
(above ambient) Alert
IR values
8. Batteries
Sr.
Equipment / test data
No. Permissible limits Reference
Sr.
No. Oil temperature Deg. C Correction factor(K)
1 10 0.8
2 15 0.9
3 20 1.0
4 25 1.12
5 30 1.25
6 35 1.40
7 40 1.55
8 45 1.75
9 50 1.95
10 55 2.18
11 60 2.42
12 65 2.70
13 70 3.00
If Tan Delta of bushing/winding/CVT/CT is measured at oil temperature T Deg. C. Then Tan Delta at 20 Deg. C shall
be as given below:
Tan Delta at 20 Deg. C = Tan Delta at Temp T Deg. C / Factor K.
Dew Point Limits for SF6 Gas in EHV Circuit Breakers