M/s PAN POWER TRANSFORMER OIL TEST REPORT

P.O. No.: - Dated: - Inspection Date: 28-12-2012

Inspection Call No.: - Dated: - Offered Quantity: 6

WAPDA Specification: DDS-84: 2007 with Amendment No.: 5 Tested Quantity: 06 Nos.

Visual Pour Temperature of Oil Acidity of Dielect Stren


Specific Gravity Viscosity Flash Point ˚C
Inspection Point °C oil (KV)

Transformer Serial Nos. --- --- --- IEC- 60422 IEC- 60296 IEC- 60296 IEC- 60296 IEC- 60422

Should be Free -30° C 0.03 mg


Max 0.895kg/dm3 12 mm²/s at B.D 55 KV at 2
From --- KOH/g of 135 °C (Min.)
at 20˚C 40˚C(Max) gap.
Contamination (Max) oil(Max)

Found free from


1 -30 - - - 8.29 165 60.0
contamination
Found free from
2 -30 - - - 8.53 170 60.0
contamination
Found free from
3 -30 - - - 10.5 170 60.0
contamination
Found free from
4 -30 - - - 11.1 162 60.0
contamination
Found free from
5 -30 - - - 10.5 170 60.0
contamination
Found free from
6 -30 - - - 11.1 162 60.0
contamination

Testing Engineer. Genral Ma


Pan Power International (Pvt) Limited. Pan Power Internatio
2-2012

Nos.

06 Nos.

lect Strength
(KV)

IEC- 60422 Remarks

55 KV at 2.5mm
gap.

Qualified the
60.0
Test
Qualified the
60.0
Test
Qualified the
60.0
Test
Qualified the
60.0
Test
Qualified the
60.0
Test
Qualified the
60.0
Test

Genral Manager
nternational (Pvt) Limited.