The document contains the settings for various protection relays for a generator including under voltage, over voltage, under frequency, over frequency, reverse power, over current, short circuit, overload, loss of excitation, over excitation, negative phase sequence current, negative phase sequence voltage, bus bar over voltage, differential relay, and stator earth fault relay settings. It lists the minimum, maximum, and trip set point values as well as enable status and fail class for each protection function and generator.
The document contains the settings for various protection relays for a generator including under voltage, over voltage, under frequency, over frequency, reverse power, over current, short circuit, overload, loss of excitation, over excitation, negative phase sequence current, negative phase sequence voltage, bus bar over voltage, differential relay, and stator earth fault relay settings. It lists the minimum, maximum, and trip set point values as well as enable status and fail class for each protection function and generator.
The document contains the settings for various protection relays for a generator including under voltage, over voltage, under frequency, over frequency, reverse power, over current, short circuit, overload, loss of excitation, over excitation, negative phase sequence current, negative phase sequence voltage, bus bar over voltage, differential relay, and stator earth fault relay settings. It lists the minimum, maximum, and trip set point values as well as enable status and fail class for each protection function and generator.
Set point 40.0% 100.0% 93.0%(10230 V) Time Delay 0.0 Sec 100 Sec 15 sec Enable Off On On Fail class Alarm Trip Alarm Generator Under Voltage setting (2) values: Minimum value Maximum value Trip Set point Set point 40.0% 100.0% 90.0%(9900 V) Time Delay 0.0 Sec 100 Sec 15 sec Enable Off On On Fail class Alarm Trip Trip
Generator High Voltage setting (1) values:
Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 106.0%(116600 V) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Generator High Voltage setting (2) values: Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 109.0%(11990 V) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip
Generator Under Frequency setting (1) values:
Minimum value Maximum value Trip Set point Set point 100.0% 80.0% 93.0%(46.5Hz) Time Delay 0.0 Sec 100 Sec 10 sec Enable Off On On Fail class Alarm Trip Alarm Generator Under Frequency setting (2) values: Minimum value Maximum value Trip Set point Set point 100.0% 80.0% 90.0%(45.0 Hz) Time Delay 0.0 Sec 100 Sec 10 sec Enable Off On On Fail class Alarm Trip Trip
Generator Over Frequency setting (1) values:
Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 105.0%(52.5Hz) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Generator Over Frequency setting (2) values: Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 107.0%(53.5 Hz) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip
Reverse Power setting (1) values:
Minimum value Maximum value Trip Set point Set point 0.0% 200.0% -3.0 %(780KW) Time Delay 0.0 Sec 100 Sec 10 sec Enable Off On On Fail class Alarm Trip Alarm Reverse Power setting (2) values: Minimum value Maximum value Trip Set point Set point 0.0% 200.0% -5.0 %(1300KW) Time Delay 0.0 Sec 100 Sec 10 sec Enable Off On On Fail class Alarm Trip Trip Generator over current setting (1) values: Minimum value Maximum value Trip Set point Set point 50.0% 200.0% 100.0% Time Delay 0.0 Sec 3200 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Generator over current setting (2) values: Minimum value Maximum value Trip Set point Set point 50.0% 200.0% 110.0% Time Delay 0.0 Sec 3200 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip Generator Short Circuit setting (1) values: Minimum value Maximum value Trip Set point Set point 150.0% 350.0% 200.0% Time Delay 0.0 Sec 3200 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Generator Short Circuit setting (2) values Minimum value Maximum value Trip Set point Set point 150.0% 350.0% 250.0% Time Delay 0.0 Sec 3200 Sec 1 sec Enable Off On On Fail class Alarm Trip Trip Generator Overload setting (1) values: Minimum value Maximum value Trip Set point Set point -200.0% 200.0% 100.0% Time Delay 0.0 Sec 3200 Sec 10 sec Enable Off On On Fail class Alarm Trip Alarm Generator Overload setting (2) values: Minimum value Maximum value Trip Set point Set point -200.0% 200.0% 110.0% Time Delay 0.0 Sec 3200 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip Loss of Excitation setting values: Minimum value Maximum value Trip Set point Set point 0.0% 150.0% 50.0% Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Over Excitation setting values: Minimum value Maximum value Trip Set point Set point 0.0% 100.0% 80.0% Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip Negative Phase Sequence Current setting values: Minimum value Maximum value Trip Set point Set point 0.0% 100.0% 10.0%In (0.28A) I sec Time Delay 0.2 Sec 100 Sec 0.5 sec Enable Off On On Fail class Alarm Trip GB Trip GB Negative Phase Sequence Voltage setting values: Minimum value Maximum value Trip Set point Set point 1.0% 100.0% 5.0%(550V) Time Delay 0.2 Sec 100 Sec 0.5 sec Enable Off On On Fail class Alarm Trip GB Trip GB Bus Bar over Voltage setting (1) values: Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 105.0%(11550 V) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Alarm Bus Bar over Voltage setting (2) values: Minimum value Maximum value Trip Set point Set point 100.0% 120.0% 107.0%(11770 V) Time Delay 0.0 Sec 100 Sec 5 sec Enable Off On On Fail class Alarm Trip Trip
Differential relay setting values:
Differential Current Set point:
Minimum setting Maximum setting Trip Set point 4% 40 % 10.2 %(0.53 A) I sec
Differential Current Time Delay Set point:
Minimum setting Maximum setting Time delay 0 Sec 10 Sec 6.547 Sec
Stator Earth Fault relay setting values:
Stator Earth Fault Set point:
Minimum setting Maximum setting Trip Set point 10 % 110 % 26 %(1.3 A) In
Stator Earth Fault Time Delay Set point:
Minimum setting Maximum setting Time delay 0 Sec 5 Sec 1 Sec