Mitigeur Watt PDF

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

ES-N170-M2

For Commercial and Industrial Applications


Job Name Contractor
Job Location Approval
Engineer Contractor’s P.O. No.
Approval Representative

Series N170-M2
Hot Water Extender
Tempering Valves
Sizes: 3⁄4" through 2" (20 - 50mm)
Watts Series N170-M2 hot water extender tempering valves
are especially designed for use on larger hot water supply
systems for mixing hot and cold water for a variety of applica-
tions to extend the hot water supply. This series features a Dual-Action
unique "double thermostat design" which combines two ther- Thermostat
mostats in one to provide response to changes in water tem- Design
perature passing through the mixing chamber. In addition, the
operating life of the element is vastly improved over contem- Minimum Flow Requirements
porary designs because the travel load is divided evenly be- to Maintain Set Temperature for Series N170-M2
tween the two sensing elements. Valve Size gpm lpm
This new concept of thermostat design in series N170-M2 34
⁄ " - 2" (20-50mm) 8 to 9 30-34
also provides a powerful force on opening and closing. Thus,
the combination of a sensitive, powerful thermostatic force
Series N170-M2 are provided in sizes 3⁄ 4" through 2" (20-50mm)
combined with a free-moving, high-temperature-resisting
with threaded connections (size 2"-50mm has 11⁄ 2"-40mm cold
rubber disc assures longer valve life and more satisfactory
connection). Temperature range from 130°F to 180°F (55°-82°C).*
system performance.
For proper operation, do not exceed 210°F (99°C).
An additional feature of the series N170-M2 is that the dual-
Max. pressure 150 psi (10.55 bars).
action thermostat is interchangeable in all sizes from 3⁄4"
through 2" (20-50mm) for both old and new designs. Series N170L-M2 are identical to the above except they are furnished
with a special low temperature range thermostat for car wash and
other such applications. Temperature range 100°F to 130°F (38°-55°C).
WARNING
Watts Hot Water Temperature Control Valves cannot be Features
used for tempering water temperature at fixtures. Severe • All bronze body construction with stainless steel disc
bodily injury (i.e., scalding or chilling) and/or death may
result depending upon system water pressure changes. • Solid wall hydraulic principle thermostat assures dependable
ASSE standard 1016 listed devices such as Watts Model mixing of hot and cold water
L111 or MMV should be used at fixtures to prevent • Thermostat controls both hot and cold water
possible injury.
The Watts Hot Water Temperature Control Valves are • New static adjustment screw seal
designed to be installed at or near the boiler or hot water
heater. They are not designed to compensate for system Specifications
pressure fluctuations and should not be used where ASSE
1016 devices are required. These WATTS valves should never A Watts No. N170-M2 shall be installed on heating equipment to
be used to provide "anti-scald" or "anti-chill" service. provide tempered water. Valve shall have bronze body and operate
When installing the Series 1170 valves in a radiant heat appli- so that the thermostat controls the cold water port. Watts Regula-
cation, the components of the radiant heat system must be of
materials with a construction capable of withstanding the high tor Company Series N170-M2.
limit output temperatures of the heating boiler. If you are
uncertain as to the product's adaptability for your application,
please consult an authorized representative before installing
or using the product.

Watts product specifications in U.S. customary units and metric are


approximate and are provided for reference only. For precise measurements,
please contact Watts Technical Service. Watts reserves the right to change or
modify product design, construction, specifications, or materials without prior
notice and without incurring any obligation to make such changes and
modifications on Watts products previously or subsequently sold.
MATERIALS CAPACITY
Body - Bronze
(19mm)(25mm) (32mm) (38mm) (50mm)
Disc - Stainless Steel bars psi 3⁄ 4 "
1" 11⁄4" 1 1⁄ 2 " 2"
Thermostat Assembly - Copper 3.4 50

3.1 45
PRESSURE - TEMPERATURE
2.8 40
Suitable for supply pressure up to 150 psi (10.55 bars).
N170-M2 adjustable temperature range 130-180°F (55°-82°C). 2.4 35

Pressure Drop
N170L-M2 adjustable temperature range 100-130°F (38°-55°C).
2.1 30
Maximum temperature 210°F (99°C).
1.7 25

RECOMMENDED INSTALLATION 1.4 20


To Fixtures
1.0 15
From Cold 0.7 10
Supply
To Model
L111 or MMV 0.3 5

0 0
Thermometer 10 20 30 40 50 60 70 80 90 100 110 120 gpm
P∆
Tempered 140°F * 38 76 114 152 190 228 266 304 342 380 418 456 lpm
Flow
Cold
BASIC CONSTRUCTION
No. N170-M2 180° AGA/ASME Adjusting Screw
Cold

Tempering * T&P Valve Lock Nut


Valve 8"
to ASME Pressure
12" Relief Valve

INTERCHANGEABLE
THERMOSTAT
Shutoff Valves standard in all 5
(on both hot and Storage valves sizes.
cold inlets) Tank
No. 600
Water Heater
Check Valves Drain or
(on both hot and Hot Water Exclusive
cold inlets) Boiler Dual-Action
Thermostat
not vulnerable High temperature
*IMPORTANT: Valve must be to corrosion - resisting rubber
installed trapped as shown powerful, disc provides
hydraulic action positive shut off.
control
DIMENSIONS - WEIGHT

COLD HOT

Bronze Body

C
Temperature Range
130° - 180°F 100° - 130°F Dimensions
MIXED (55° - 82°C) (38° - 55°C) Size (DN) A C D E Weight
E Valve No. Valve No. In. mm in. mm in. mm in. mm in. mm lbs. kgs.
N170-M2 N170L-M2 3 ⁄4 20 4 1⁄ 8 105 5 5⁄ 8 143 2 50 3 1⁄ 2 90 4.13 1.9


COLD HOT
N170-M2 N170L-M2 1 25 4 1⁄ 2 114 5 5⁄ 8 143 2 50 3 1⁄ 2 90 4.38 2.0
D N170-M2 N170L-M2 11 ⁄ 4 32 6 152 6 152 2 50 37⁄16 88 8 3.6

N170-M2 N170L-M2 11 ⁄ 2 40 6 152 6 152 2 1⁄ 8 54 37⁄16 88 8 3.6
N170-M2 N170L-M2 2 X 11⁄2 50 X 40 6 3⁄ 8 162 6 152 2 1⁄ 8 54 37⁄16 88 8.75 4.0

A
CAUTION: NEED FOR PERIODIC INSPECTION
Periodic inspection by a licensed contractor is recommended. Corrosive water conditions, temperatures over 210°F (99°C), un-
authorized adjustments or repair could render the valve ineffective for service intended. Regular checking and cleaning of ther-
mostat assembly helps to assure maximum life and proper product function. Frequency of cleaning depends upon local water
conditions. *See Warning on reverse side.
ES-N170-M2 0115 © Watts Regulator Co., 1996 Printed in U.S.A.