T/shooting Guide
Trouble Shooting Guide
n Error Indicator
• The function is to self-diagnosis airconditioner and express the troubles identically if there is any trouble.
• If more than two troubles occur simultaneously, primarily the highest trouble of error code is expressed.
• After error occurrence, if error is released, error LED is also released simultaneously.
• To operate again on the occurrence of error code, be sure to turn off the power and then turn on.
• Having or not of error code is different from Model.
LED1
LED1
(1 Digit)
(1 Digit)
LED2 LED1 LED2
(10 Digit) LED2 (1 Digit) (10 Digit)
(10 Digit)
3) SH Chassis
1 Digit LED1
(1 Digit)
10 Digit
LED2
(10 Digit)
LED3
(100 Digit)
2. SE Mirror, S8, SD, SM, SN, SJ, SK, S2 Chassis
(Number Display Model)
-1-
Trouble Shooting Guide
3. SF Chassis (1 LED Model)
LED1
Left Right
(100 Digit) (1 Digit)
Down
(10 Digit)
-2-
Trouble Shooting Guide
Error indication
Error
Description Indoor unit
code
Down Right
01 Indoor unit air sensor error - 1 Time
02 Inlet pipe sensor error - 2 Times
04 Float switch error - 4 Times
05 Communication error (IN-OUT) - 5 Times
06 Outlet pipe sensor error - 6 Times
09 EEPROM check sum error - 9 Times
10 BLDC motor fan lock 1 Time -
12 Mid pipe sensor error 1 Time 2 Times
2sec
-3-
Trouble Shooting Guide
n Outdoor Unit Error
1) 2 LED Type
LED1
(Green, 1 Digit)
LED2
(Red, 10 Digit)
2) 1 LED Type
Red LED
Error Indication
Error
Description Indoor Unit Outdoor Unit
Code
LED2 LED1 Red Green
21 DC Peak (IPM Fault) 2 Times 1 Time 2 Times 1 Time
22 CT2 (Max. Current) 2 Times 2 Times 2 Times 2 Times
23 DC Link Low/High Volt. 2 Times 3 Times 2 Times 3 Times
25 AC Low/High Volt. 2 Times 5 Times 2 Times 5 Times
26 DC Comp Position Error, LOCKING 2 Times 6 Times 2 Times 6 Times
27 PSC Fault 2 Times 7 Times 2 Times 7 Times
29 Comp Phase Over-Current 2 Times 9 Times 2 Times 9 Times
32 Inverter Compressor D-Pipe Overheat 3 Times 2 Times 3 Times 2 Times
37 Exceed the Compression Ratio Limit 3 Times 7 Times 3 Times 7 Times
40 CT Sensor Error 4 Times - 4 Times -
41 D-Pipe Sensor Error 4 Times 1 Time 4 Times 1 Time
44 Outdoor Air Sensor Error 4 Times 4 Times 4 Times 4 Times
45 Cond. Middle Pipe Sensor Error 4 Times 5 Times 4 Times 5 Times
48 Cond. Out Pipe Sensor Error 4 Times 8 Tiems 4 Times 8 Tiems
53 Communication Error (IN-OUT) 5 Times 3 Times 5 Times 3 Times
60 EEPROM Check Sum Error 6 Times - 6 Times -
61 Cond. Pipe High 6 Times 1 Time 6 Times 1 Time
62 Heat Sink Sensor Temp. High 6 Times 2 Times 6 Times 2 Times
63 Cond. Pipe Low 6 Times 3 Times 6 Times 3 Times
65 Heat Sink Sensor Error 6 Times 5 Times 6 Times 5 Times
67 BLDC Motor Fan Lock 6 Times 7 Times 6 Times 7 Times
72 Detect 4 Way Valve Transfer Failure 7 Times 2 Times 7 Times 2 Times
73 PFC SW Fault 7 Times 3 Times 7 Times 3 Times
-4-
Trouble Shooting Guide
n Old Model Error
Error Error Indication Indoor
Description
Code Indoor Outdoor Operation
Indoor Temperature Sensor Error
1 - Suction Sensor open/short ● - Operation
- Indoor Pipe Sensor open/short
Outdoor Temperature Sensor Error
2 - Suction Sensor open/short ● ● Operation
- Outdoor Pipe Sensor open/short
DC Peak Error
6 ● ● Shutdown
- DC Peak occurred
CT Error
7 ● ● Shutdown
- CT detected
EEPROM Error
12 - ● Operation
- EEPROM Check sum Error
PSC Error
13 - ● Operation
- PSC Fault Error
Ex) Error Code 6 : DC Peak Error Ex) Error Code 13 : PSC Error
6times 6times 1time 3times 1time 3times
3sec 3sec
-5-
Trouble Shooting Guide
n DRED Indicator
• The function is DRED connect signal from outdoor unit.
• [Number Display Model] : It displays “d1, d2, d3” for mode value if the DRED Mode set is received from the out-
door unit.
• However, it displays the DRED Mode after displaying the information of the set temperature and AI for 5 seconds
once the signal is input by wireless remote controller.
• [3 LED Model] : Once the DRED Mode set is received from the outdoor unit whenever the mode value is
changed, the 3rd LED flashes for 5 times and returns normally.
• Once the DRED Mode set is received from the outdoor unit, the DRED display is disappeared.
• However, if the DRED Mode is set, the 3rd LED flashes for 5 times and returns normally in the next cases.
- When the wireless remote control signal is input,
- When the operation is “on” from the operation “off” state,
DRED indication
Demand response mode
Description Indoor unit
(DRM)
LED3 LED2 LED1 Number Display
DRM1 or DRM2 or DRM3 DRED access signal 5 Time - - -
DRM1 DRED access signal - - - d1
DRM2 DRED access signal - - - d2
DRM3 DRED access signal - - - d3
1) SB, SC, SM, SV Chassis (3 LED Model) 2) SM, S2 Chassis (Number Display Model)
-6-
Trouble Shooting Guide
n Troubleshooting Guide (Indoor Unit)
-7-
Trouble Shooting Guide
Check Method
Measure resistance
Check Point
Refer to Check Point
Resistance is adequate? 1. 10k Ω / at 25℃(77℉)±10%
2. 5k Ω / at 25℃(77℉)±10%
Yes
Sensor OK
Replace Sensor No
Resistance (Black)
5~4kΩ@25~30°C
Resistance (Black)
10~8kΩ@25~30°C
Resistance (Blue)
5~4kΩ@25~30°C
Resistance (Black)
5~4kΩ@25~30°C
-8-
Trouble Shooting Guide
Resistance - Temp. Sensor Table
Resistance(KΩ)
Temp (℃/℉)
Air Sensor s-Pipe Sensor D-Pipe Sensor
-30/-22 204.35 102.17 -
-25/-13 146.97 73.49 -
-20/-4 107.09 53.55 -
-15/5 79 3950 -
-10/14 58.95 29.48 -
-5/23 44.47 22.24 -
0/32 33.9 16.95 585.66
5/41 26.09 13.05 465.17
10/50 20.27 10.14 372.49
15/59 15.89 7.94 300.58
20/68 12.55 6.28 244.33
25/77 10 5 200
30/86 8.03 4.01 164.79
35/95 6.49 3.24 136.64
40/104 5.28 2.64 113.98
45/113 4.32 2.16 95.62
50/122 3.56 1.78 80.65
55/131 2.95 1.48 68.38
60/140 2.46 1.23 58.27
65/149 2.06 1.03 49.88
70/158 1.74 0.87 42.9
75/167 1.47 0.74 37.05
80/176 1.25 0.63 32.14
90/194 0.92 0.46 24.46
100/212 0.68 0.34 18.89
-9-
Trouble Shooting Guide
Inspection Description of
Cause of Error Check Point
Number Inspection
Is it normal ? No
Check float switch
Yes
Is the float
No
switch clean ?
Clean float switch
Yes
Check the wire
connection (Open,
Soldered poorly)
Is it normal ? No
Correct connection
Yes Or re-soldering PCB
Is the resistance of f
loat switch normal No
(short) ? Change the float switch
Check Point
1. Check the wire connection. (Open, Soldered poorly) ’ Repair the connection or change the PCB.
2. Check the resistance of float switch (Abnormal : Open, Normal : short) ’ Check the float switch.
3. Check the level of water.
- 10 -
Trouble Shooting Guide
1. Check input power AC 208~230V(in case of 115V Model : 115V) (indoor, outdoor unit)
- 11 -
Trouble Shooting Guide
- -
- 12 -
Trouble Shooting Guide
n Trouble Shooting Guide [Outdoor Unit (2 LED Type / 1 LED Type)]
1) CH21: DC Peak Error
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
2 LED Type
1 LED Type
- 13 -
Trouble Shooting Guide
2 LED Type
1 LED Type
17
18
19
20
21
22
23
24
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
- 14 -
Trouble Shooting Guide
2) CH22: CT2 Error (Input Over-current)
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
2 LED Type
1 LED Type
- 15 -
Trouble Shooting Guide
3) CH23: DC Link Low Voltage Error
2 LED Type
1 LED Type
- 16 -
Trouble Shooting Guide
4) CH26: DC Comp Location Sensing Error
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
2 LED Type
1 LED Type
- 17 -
Trouble Shooting Guide
5) CH27: PSC Fault Over-current Error
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
2 LED Type
1 LED Type
- 18 -
Trouble Shooting Guide
6) CH29: Compressor phase Over-current Error (only verifiable at Outdoor unit PCB Assembly)
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
2 LED Type
1 LED Type
- 19 -
Trouble Shooting Guide
7) CH32: Inverter Compressor D-Pipe Overheat Error
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
4 Pin Type
Red 4 Pin
Connector
3 Pin Type
- 20 -
Trouble Shooting Guide
8) CH40: CT Sensor Error (Open/Short)
Fig.1
Fig.2
Tester
Fig.2
Tester
- 21 -
Trouble Shooting Guide
9) CH41/44/45/65: Inv D-Pipe/Outdoor Inlet/Cond. Pipe/Heat sink Sensor Error
- 22 -
Trouble Shooting Guide
10) CH53: Outdoor Unit <-> Indoor Unit Communication Error
- 23 -
Trouble Shooting Guide
11) CH60: Outdoor Unit PCB EEPROM Error
Check Method
ڸ
ڹ ں
- 24 -
Trouble Shooting Guide
12) CH61: Cond. Pipe Overheat Error
(Fan constraint,
caution Check that whether the housings and harness would be separated by pulling those with hands directly.
- 25 -
Trouble Shooting Guide
13) CH62: Heat Sink Overheat Error
- 26 -
Trouble Shooting Guide
14) CH67: Outdoor BLDC Fan Lock Error
- 27 -
Trouble Shooting Guide
15) CH72: 4 way valve switching failure
- 28 -
App.
Checking Methods
App.Checking Methods
How to Check ODU Installation Condition
Cause Condition Symptom
• Blocking of the front part of outdoor • Frequent turning-off of the compressor : Inflow of high-tem-
unit perature air generated by outdoor fans into the air condi-
Whirlwind
• Installation of outdoor unit in narrow tioner
space → System in over-load state
• Blocking of the lateral suction point
on the wall of the outdoor unit. • Frequent turning-off of the compressor : Elevation of the
Blocked Airflow • Foreign substances in the heat pipe temperature due to reduced wind velocity
exchanger and obstacles in the sur- → System in over-load state
roundings.
• Moisture • Corrosion of heat exchanger
Corrosion
• High humidity area → Reduced operation efficiency
1200(47-1/4)
or more
Unit : mm(inch)
700(27-9/16) or more
300(11-13/16) or more
600(27-5/8)
or more
600(27-5/8)
300(11-13/16) or more or more 300(11-13/16) or more Unit : mm(inch)
300(11-13/16) or more
Unit : mm(inch)
- 30 -
App.Checking Methods
How to Check Refrigerant Flow Disturbance
Cause Condition Symptom
- 31 -
App.Checking Methods
How to Check Compressor Phase Resistance
o Insulation resistance between compressor and piping
Insulation
Terminal
Resistance
U-Piping ≥1MΩ
V-Piping ≥1MΩ
W-Piping ≥1MΩ
- 32 -
App.Checking Methods
How to Check the Compressor Wiring Error
Y B R
Y (Yellow)
B (Blue)
R (Red)
Y B R
BL RD BR
BL (Blue)
RD (Red)
BR (Brown)
BL RD BR
- Check whether the PCB wires and compressor wires are connected in the same colors.
⇨
- Check whether the compressor - The wiring direction may be different depending upon
wires are properly connected with the kinds of comp.
U, V, and W.
- 33 -
App.Checking Methods
How to Check IPM part
Judgment of the IPM part fault of PCB Check 1. Judgment of damage of IGBT
Purpose
assembly. items 2. Checking the soldering state.
2 LED Type
1 LED Type
17
18
19
20
21
22
23
24
- 34 -
App.Checking Methods
How to Check IPM IGBT (Doide Mode)
1. Remove the connector from PCB.
2. Set the Multi-Tester as Diode Voltage Measurement Mode. ( ).
3. Measure the voltages of P~U / P~V / P~W as shown in Fig. 1.
4. Measure the voltages of U~Nu / V~Nu /W~Nu as shown in Fig. 2.
5. If the measurements are significantly different from the levels shown in the figures, the IPM can be considered as
damage.
2 LED Type
1 LED Type
[Fig. 1] [Fig. 2]
17 17
18 18
19 19
20 20
21 21
22 22
23 23
24 24
- 35 -
App.Checking Methods
How to Check Compressor Phase Current Detection
Generation of compressor over-current Check
Purpose 1. Checking for current detection error.
caused by phase current detection error. items
Caution!
When the measurement is made in the state that the electricity is applied, check the
tester for being in the measurement mode and be careful to avoid possible short of the
parts other than the measuring part.
- 36 -
App.Checking Methods
How to Check Input Current Detection Circuit
Generation of compressor over-current Check
Purpose 1. Checking for current detection error.
caused by phase current detection error. items
Caution!
When the measurement is made in the state that the electricity is applied, check the
tester for being in the measurement mode and be careful to avoid possible short of the
parts other than the measuring part.
- 37 -
App.Checking Methods
How to Check 4-Way Valve Condition
1. Check the working voltge of the 4-way
Judge whether the 4-way valve part has Check
Purpose valve.
any fault. items
2. Check the 4-way valve coil resistance.
CN-4 Way
- 38 -
App.Checking Methods
How to Check EEV Condition
Check
Purpose Judging EEV part fault 1. Measure EEV resistance
items
[Table]
h There may be the difference in the resistance depending upon the EEV Specifications.
- 39 -