Bra (Halfen Deha)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Project Project numer Page

Pos.
1

HALFEN parapet corbel BRA - DIN 1045-1


HALFEN calculation program BRA, Version 4.25

Comment :

Geometry :

153.0
0.8 / -1.6
208.0

208.0
55.0

28.3

55.0
© HALFEN GmbH, Langenfeld, Germany

14.0
5.0
70.0 210.0 70.0

350.0

Loading :

horizontal and vertical line loads


g [kN/m] p [kN/m] e [cm]

H1 0.00 0.00 153.0

H2 0.00 0.00 0.0


HALFEN GmbH, Liebigstrasse 14, Tel.: 02173 / 970 0, FAX: 02173 / 970 123

V1 0.00 0.00 0.0

V2 0.00 0.00 0.0

wind : area = edge area; height above ground > 8 m up to 20 m


wD = 0.80 kN/m²; wS = -1.60 kN/m²

Data for parapet corbel

chosen parapet corbel : BRA A - 5 - 550 - A4 (0242.110-00031)


type of parapt corbel : roof parapet
distance between calc. supports = 28.3 cm; cantilever length = 16.0 cm; unsupported length = 44.8 cm
adjusting area rear support = ±30 mm
Suggested fixing with HALFEN cast-in channel HTA 54/33 and HALFEN bolt HS 50/30-M20 x 75
On site the following assembly accessories will be needed: BRA - M1 - 5

internal forces

load cases
both supports

Date
10/4/2010
Project Project numer Page
2

Pos.
1

N [kN] Vz [kN] My [kNcm] Mz [kNcm] Mi [kNcm]


LC1: dead load 0.00 12.74 216.58 0.00 12.74

LC2: wind pressure -2.91 0.00 -142.69 0.00 -142.69

LC3: wind suction 5.82 0.00 285.38 0.00 285.38

LC4: temperature 0.00 0.00 0.00 39.20 0.00

LC5: horizontal load H1 0.00 0.00 0.00 0.00 0.00

LC6: horizontal load H2 0.00 0.00 0.00 0.00 0.00

LC7: vertical load V1 0.00 0.00 0.00 0.00 0.00

LC8: vertical load V2 0.00 0.00 0.00 0.00 0.00

decisive load case combination


N d [kN] Vz, d [kN] My, d [kNcm] Mz, d [kNcm] Mi, d [kNcm]
© HALFEN GmbH, Langenfeld, Germany

1.35*L1+1.5*L3 8.74 17.20 720.45 0.00 445.26

1.35*L1+1.5*L4 0.00 17.20 292.38 58.80 17.20

1.35*L1+1.5*0.9*(0) 0.00 17.20 292.38 0.00 17.20

1.0*L1+1.0*L3 5.82 12.74 501.96 0.00 298.12

Verifications

max | M y,d | = 720.45 kNcm < 879.80 kNcm = M pl,y,d


max | V z,d | = 28.48 kN < 39.20 kN = 0.33 V pl,z,d
max | Nd | = 8.74 kN < 374.30 kN = N pl,d
max | M i,d | = 445.26 kNcm < 750.00 kNcm = M i,Rd
max | M z,d | = 58.80 kNcm < 816.40 kNcm = M pl,z,d
HALFEN GmbH, Liebigstrasse 14, Tel.: 02173 / 970 0, FAX: 02173 / 970 123

Verification of the section for biaxial bending: [1] 1.35*L1+1.5*L3

| M y, d | = 720.45 kNcm < = 870.12 kNcm

= 0.63 < 1.0

Verifivation of support loads on the tensile and compressive support

compressive support
= 45.68
Dd kN < 52.84 kN = zul FD, Rd
tensile support Z=d 28.48 kN < 30.80 kN = Fz, Rd
(compressive support D k = 32.58 kN; tensile support Z k = 19.84 kN)

Verification of bending for cantilever considering working loads

Date
10/4/2010
Project Project numer Page
3

Pos.
1

act. fz = 1.22 mm < 1.35 mm = allow. fz


max. horiz. displacement of the parapet due to the bending of the parapet corbel : -9.26 mm
This horizontal displacement occurs in the height of 153.00 cm from the bottom edge of the parapet corbel.
© HALFEN GmbH, Langenfeld, Germany
HALFEN GmbH, Liebigstrasse 14, Tel.: 02173 / 970 0, FAX: 02173 / 970 123

Date
10/4/2010
HALFEN GmbH, Liebigstrasse 14, Tel.: 02173 / 970 0, FAX: 02173 / 970 123 © HALFEN GmbH, Langenfeld, Germany
Project

153.0

208.0
208.0

55.0
0.8 / -1.6

28.3
55.0

14.0
5.0

70.0 210.0 70.0

350.0
1
Pos.
Project numer
4

Date
Page

10/4/2010
Project Project numer Page
5

Pos.
1

398

38 7 70 25 50

Suggested fixing
HALFEN cast-in channel HTA 54/33
HALFEN bolt HS 50/30-M20 x 75

Assembly accessory
BRA - M1 - 5
© HALFEN GmbH, Langenfeld, Germany

BRA A - 5 - 550 - A4

160 283 65
HALFEN GmbH, Liebigstrasse 14, Tel.: 02173 / 970 0, FAX: 02173 / 970 123

102 448

550

Date
10/4/2010