STAATSOLIE MAATSCHAPPIJ SURINAME N.V.

TECHNICAL SERVICES - INSPECTION DEPARTMENT


INSPECTION RECOMMENDATIONS
Equipment Tag: 4"-FW-804-1A2D Unit / AREA: 800 (FW Pumps Area)

Reco No.: 006 WO No:

Equipment Name: FW Jockey Pump P-8023 DISCHARGE LINE Project:

Inspection Start Date: 1/5/2014 Report Date: 13-05-2014

Last Inspection Date: 9/5/2014 Inspection Type: UT & VT

FINDINGS :
1. the first spool piece of the discharge is corroded from the outside incl. 1 1/4" flange and reducer 1 1/4"*3"
(see pic.1 in the attachment)

2. Maintenance already replaced a part of this spool due to a leakage at the weld on the elbow ( see pic.1 in
the attachment) , repaired one leaking elbow & another still leaking.

3. According to the UT measurement on this line the average min. thickness is 3.35 mm - 3.9 mm. ;
Original wall thickness was 5.49mm

RECOMMENDATIONS :
1. Renew the line , due to low UT thickness and possibility of more leaks from pitting inside.
2. The valves can be re-used , but must be checked and serviced.
3. The PI must be checked/serviced or be renewed.

Attachments :
VT-report with pictures & comments
UT measurements ; thickness written on the iso's.

Remarks:

WRITTEN BY : APPROVED BY: