Page 1 of 16
—
Dielectric Frequency Response and
Temperature Dependence of
Dissipation Factor
By
Peter Werelius and Matz Ohlen
Megger, Sweden
Hob 20 TechCon®
O9 AsiA- PACIFICPage 2 of 16
Hob 20 TechCon®
proc Se yl O9 Asia- PACIFICPage 3 of 16
Dielectric Frequency Response and Temperature Dependence of
Dissipation Factor
Peter Werelius and Matz Ohlen
Megger Sweden
Abstract
Modern technology and developments in signal acquisition and analysis techniques have
provided new tools for transformer diagnostics. Of particular interest are dielectric response
measurements where insulation properties of oil-paper systems can be investigated.
Dielectric Frequency Response, DFR (also known as Frequency Domain Spectroscopy, FDS),
was introduced more than a decade ago and has been thoroughly evaluated in a number of
research projects and field tests with good results. Moisture assessment and bushing
diagnostics in transformers as well as cable testing and insulation testing in rotating
machinery are important applications where DFR provides accurate information for decisions
on maintenance and/or replacement.
Measuring 50/60 Hz tan delta at various temperatures is an established technique for
identifying aged/high moisture content in e.g. bushings. The testing takes substantial time
since you have to wait for the bushing to cool down, make a measurement, wait, take a new
measurement etc. This paper presents a new method (patent pending) where a DFR
measurement is used to determine the temperature dependence of the insulation and the result
is presented as 50/60 Hz tan delta/power factor as a function of temperature. The technique
saves a lot of time since the test is only one measurement sequence at the actual ambient
temperature.
Another well known issue is how to do correct temperature compensation of tan delta
measurements taken at high or low temperature. Traditionally, correction tables for “average”
components are used giving poor accuracy, especially when measuring old/aged components.
The new technique calculates the correct temperature correction for the actual unit based on
the condition of the insulation. This means that tan delta/power factor measurements on new
or old/aged components can be performed at high or low temperatures and indivi
converted to the reference temperature.
Introduction
With an aging power component population, today's electrical utility industry faces a tough
challenge as failures and consequent repair and revenue loss may inflict major costs.
Transformers have become one of the most mission critical components in the electrical grid.
The need for reliable diagnostic methods drives the world’s leading experts to evaluate new
technologies that improve reliability and optimize the use of the power network.
The condition of the insulation is an essential aspect for the operational reliability of electrical
power transformers, generators, cables and other high voltage equipment. Transformers with
Hob 20 TechCon®
proc Ses yl O9 Asia- PACIFIC