Page 1 of 16 — Dielectric Frequency Response and Temperature Dependence of Dissipation Factor By Peter Werelius and Matz Ohlen Megger, Sweden Hob 20 TechCon® O9 AsiA- PACIFIC Page 2 of 16 Hob 20 TechCon® proc Se yl O9 Asia- PACIFIC Page 3 of 16 Dielectric Frequency Response and Temperature Dependence of Dissipation Factor Peter Werelius and Matz Ohlen Megger Sweden Abstract Modern technology and developments in signal acquisition and analysis techniques have provided new tools for transformer diagnostics. Of particular interest are dielectric response measurements where insulation properties of oil-paper systems can be investigated. Dielectric Frequency Response, DFR (also known as Frequency Domain Spectroscopy, FDS), was introduced more than a decade ago and has been thoroughly evaluated in a number of research projects and field tests with good results. Moisture assessment and bushing diagnostics in transformers as well as cable testing and insulation testing in rotating machinery are important applications where DFR provides accurate information for decisions on maintenance and/or replacement. Measuring 50/60 Hz tan delta at various temperatures is an established technique for identifying aged/high moisture content in e.g. bushings. The testing takes substantial time since you have to wait for the bushing to cool down, make a measurement, wait, take a new measurement etc. This paper presents a new method (patent pending) where a DFR measurement is used to determine the temperature dependence of the insulation and the result is presented as 50/60 Hz tan delta/power factor as a function of temperature. The technique saves a lot of time since the test is only one measurement sequence at the actual ambient temperature. Another well known issue is how to do correct temperature compensation of tan delta measurements taken at high or low temperature. Traditionally, correction tables for “average” components are used giving poor accuracy, especially when measuring old/aged components. The new technique calculates the correct temperature correction for the actual unit based on the condition of the insulation. This means that tan delta/power factor measurements on new or old/aged components can be performed at high or low temperatures and indivi converted to the reference temperature. Introduction With an aging power component population, today's electrical utility industry faces a tough challenge as failures and consequent repair and revenue loss may inflict major costs. Transformers have become one of the most mission critical components in the electrical grid. The need for reliable diagnostic methods drives the world’s leading experts to evaluate new technologies that improve reliability and optimize the use of the power network. The condition of the insulation is an essential aspect for the operational reliability of electrical power transformers, generators, cables and other high voltage equipment. Transformers with Hob 20 TechCon® proc Ses yl O9 Asia- PACIFIC

You might also like