OSD Underground
OSD Underground
OSD Underground
Select storage type to be used within the site = below ground OSD
1)Determine the area of the site that will be directed to OSD system
The minor drainage system that the OSD storage will discharge
Into has been designed for a 2 year ARI capacity.
For Penang,
App. 13.A ARI Coefficients of the IDF polynomial Equation
Table 13A1 (year) a. b. c. d.
2 4.5140 0.6729 -0.2311 0.0118
Ln 2I 30 = 4.59
2I 30 = 98.84 mm/hr
= 49.42 mm.
Ln2I60 = 4.20
2I60 = 67.01 mm/hr
= 67.01 mm.
Eq. 13.3 The design rainfall depth Pd for a short duration d (minutes):
Ln 2I 30 = 4.92
2I 30 = 136.65 mm/hr
= 68.32 mm.
Ln2I60 = 4.53
2I60 = 92.83 mm/hr
= 92.83 mm.
Eq. 13.3 The design rainfall depth Pd for a short duration d (minutes):
The site discharge for the storage design storm (10 year ARI) & the
corresponding SSR is calculated for a range of duration to determine
the SSR maximum.
eq. 19.3 The required orifice size under free outlet condition
D= [4*Ao/P ]^0.5 = 206 mm.