Professional Documents
Culture Documents
Generación Distribuida
Generación Distribuida
Reduction
KHDang Jiqing Yu Tong Dang Bo Han
1. Northeast Dianli University 2.Chengdu Waste-To-Energy Co. Ltd 3. Anyang Rural Electric Power Service Center
Jilin China Chengdu China Anyang China
dkxy4886@hotmail.com yu19860227111@163.com dangtong-sh@hotmail.com yxypop@163.com
the current absorbed by load is: I L = L (1) the previous case with no DG. Thus, the line loss in
3VP this section can be expressed as:
IV. LINE LOSS REDUCTION ANALYSIS
r ( L − G )( PL2 + QL2 )
Loss B = ˄5˅
Electrical line loss occurs when current flows through 3VP2
transmission and distribution systems. The magnitude of
the loss depends on amount current flow and the line
resistance. Therefore, line loss can be decreased by reducing B.3) Total Line Loss
either line current or resistance or both. If DG is used to By combining line loss from source to the location of DG
provide energy locally to the load, line loss can be reduced and from DG location to the location of load, the total line
because of the decrease in current flow in some part of the loss can be expressed as:
network.
A. Line Loss Analysis for System without DG rL ( PL2 + Q L2 + PG2 + QG2 − 2 PL PG − 2Q L QG ) G
Loss ASG =
3V P2 L
Schematic of the system for this analysis is shown in ˄6˅
Figure 1. Line loss on a distribution feeder is equal to the
C. Line Loss Reduction
product of line current squared times the line resistance.
Therefore, line loss equation for a three phase system is
Loss reduction (LR) is given by the difference in the line loss
defined as:
with and without DG. Hence,
2043
LR = Loss − Loss B AT ˄7˅ location, resulting in lower electrical line loss. However,
higher DG ratings cannot always guarantee lower line loss.
rG (2 P P + 2Q Q − P − Q ) 2 2
The figure shows that as DG rating increases higher than 2.0
= L G L G G G
P
indicates that DG
The positive sign of LR indicates that the system loss may cause a higher line loss in the distribution system if
reduces with the integration of DG. In contrast, the the rating and location of DG are not well justified. Hence,
negative sign of LR implies that DG causes the higher this fact should be taken into account before determining the
system loss. rating and location of DG. The suitable rating of DG mainly
D. Per-unit Loss Reduction depends on the amount and location of load in the feeder.
Per-unit loss reduction (PULR) is defined as the ratio Generally, the higher amount of load, the penetration of DG
of loss reduction to the line loss without DG. PULR can be higher without causing higher electrical line loss in
presents the benefit of DG in normalized form. the system.
The location of DG also plays a vital role for electrical
LR
PULR = line loss. To study this affect, the locations of DG are varied
Loss B along the feeder: 20 (location 1), 40(location 2), 60 (location
˄8˅ 3), 80(location 4), and 100% (location 5) from the source
G while load and DG power factors are kept at 0.85 lagging.
= 2 (2PL PG + 2QL QG − PG2 − QG2 )
( PL + QL2 ) L PULR are calculated once again by (13) and the results are
shown in Figure 4.
Consequently, the percentage of line loss reduction is
simply defined as:
2044
VI. CONCLUSIONS [13] Xue Ying-chengˈTai Neng-lingˊIntroduction to the Existing DG
Interconnection Standards Worldwide ˊ Southern Power System
Use of distributed generation is one of the many Technologyˈ2008ˈ2(6)˖13-17.
strategies electric utilities are considering to operate their
systems in the deregulated environment. Several DG
technologies are showing promise for this application.
Inclusion of DG at the distribution level results in several
benefits, among which are congestion relief, loss reduction,
voltage support, peak shaving, and an overall improvement
of energy efficiency, reliability, and power quality.
This paper has considered the benefit of DG on loss
reduction for a simple case of a radial distribution line with
one concentrated load at the end and one DG. The results
clearly indicate that DG can reduce the electrical line loss.
However, the inclusion of DG does not always guarantee the
line loss. The DG rating, location, and operating power
factor are important factors for line loss reduction. Therefore,
those factors have to consider very carefully in order to
determine the best location and rating of DG.
The benefits obtained by the introduction of DG should be
weighed against the costs involved before deciding on the
use of DG. As DG technologies improve and cost decrease,
their use is expected to rise.
VII. ACKNOWLEDGEMENT
Preparation of this paper was supported by the Electrical
Engineering College of Northeast Dianli University. The
sponsorship and encouragement provided by the Electrical
Engineering College are acknowledged with thanks.
REFERENCES
[1] IEEE 929-2000 IEEE Recommended Practice for Utility Interface of
distributed generation Systems.
[2] Martin, G., “Renewable Energy Gets the Green Light in Chicago,”
IEEE Power&Energy Magazine, pp. 34-39, November/December
2003
[3] UL 1741-2001 Inverters, Convertersˈand Controllers for Use in
Independent Power Systems.
[4]GB/T 19939-2005 Technical requirements for grid connection of
distributed generation systemˊ
[5] Compiled by Solar Energy Association of Japan. Translated by LIU
Shu-min, HONG Wei. Solar photovoltaic system design and
construction.Beijing: Publisher of Science, 2006.
[6]State Grid Corp-2009, Technical rule for connection power station to
gird (Trial)ˊ
[7]GB/Z 19964-2005 Technical rule for connection power station to
electric power systemˊ
[8] ANSI C84.1 American National Standard for Electric Power Systems
and Equipment Voltage Ratings (60 Hz).
[9] IEEE Std 519-1992 IEEE Recommended Practices and Requirements
for Harmonic Control in Electrical Power System.
[10] IEC 61727-2004 distributed generation systems—Characteristics of
the utility interface.
[11] GB/T 12326-2008 Power quality-Voltage fluctuation and flickerˊ
[12] Andrews, C. J. and Weiner S. A., “Visions of a Hydrogen Future,”
IEEE Power&Energy Magazine, pp. 26-34, March/April 2004.
2045