Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Benefit of Distributed Generation on Line Loss

Reduction
   
KHDang Jiqing Yu Tong Dang Bo Han
1. Northeast Dianli University 2.Chengdu Waste-To-Energy Co. Ltd 3. Anyang Rural Electric Power Service Center
Jilin China Chengdu China Anyang China
dkxy4886@hotmail.com yu19860227111@163.com dangtong-sh@hotmail.com yxypop@163.com

Abstract—The penetration of distributed generation resources QG Reactive power of DG, Var


in distribution grids increasing worldwide, it is both a
challenge and an opportunity for a variety of technologies and QL Reactive power of Load, Var
operating scenarios. The need to provide acceptable power
quality and reliability will create a very favorable climate for r Line resistance per phase per unit length, Ω / km
the entry of distributed resources and innovative operating R Total resistance per phase, Ω / km
practices. Distributed resources is a term that encompasses
both distributed generation and distributed energy storage. Y Fraction of real load power supplied by DG
Integration of DG into an existing utility can result in several
benefits. Customers could benefit from DG in term of better II. OVERVIEW
quality of supply at lower cost. Among the many benefits of Recently distributed generation has achieved prodigious
distributed generation is a reduced line loss. The purpose of progress, electric utilities are seeking new technologies to
this paper is to quantify this benefit for the simple case of a provide acceptable power quality and reliability to their
radial distribution feeder with concentrated load and customers. Small non-conventional generation option is
distributed generator. With the introduction of DG, line loss
reduction can be expected. The analysis is conducted for
rapidly becoming attractive to many utilities because these
varying locations of the distributed generator along the feeder technologies produce energy with less environmental impact,
and for varying output capacities. The results are presented easy to site, and are highly efficient [1-3].
in graphical form in terms of clearly-defined normalized Distributed generation can be considered as “taking
parameters. power to the load”. DG promises to generate electricity with
Key Words—distributed generation, line loss reduction, high efficiency and low pollution. Unlike large central power
distributed resources plants, DG can be installed at or near the load. DG ratings
range from 5 kW up to 100 MW. Maintenance cost for DG
such as fuel cells and photovoltaics is quite low because of
I. NOMENCLATURE the absence of moving parts [4]. Several DG technologies are
G Distance from source to the DG location, km under various stages of development. They include
microturbines, photovoltaic systems, wind energy conversion
I G DG output current per phase, A / φ systems, gas turbines, diesel engines, and fuel cell systems
I L Load current per phase, A / φ [5-7]. At present, wind energy has become the most
competitive among all renewable energy technologies [8].
I S Source current per phase, A / φ Integration of DG into an existing utility can result in
L Total length of distribution line, km several benefits. These benefits include line loss reduction,
reduced environmental impacts, peak shaving, increaseVd
Loss B Total line loss before the inclusion of DG, W overall energy efficiency, relieved transmission and
Loss AGL Line loss from DG location to the location of distribution congestion, voltage support, and deferred
investments to upgrade existing generation, transmission,
load after the inclusion of DG, W and distribution systems. This paper focuses on line loss
Loss ASG Line loss from source to the DG location reduction analysis. In this study, one-concentrated load is
assumed at the end of the line.
after the inclusion of DG, W With the introduction of DG, line loss reduction can be
Loss AT Total line loss after the inclusion of DG, W expected. This factor is analyzed, quantified and presented
in this paper for different locations of the DG along the
PG Real power of DG, W feeder and for different DG power outputs.
PL Real power of Load, W
PFG Operating power factor of DG III. SYSTEM MODELING
PFL Power factor of Load Schematics of the two cases are shown in Figures 1 and
2. Both systems have a concentrated load at the line end.

978-1-4244-8165-1/11/$26.00 ©2011 IEEE


2042
rL( PL2 + QL2 )
Loss B = (2)
3VP2
B. Line Loss Analysis for System with DG

Assuming that the line is short, voltage drop along the


line is neglected. Schematic of this system is shown in
Figure 2. The complex power supplied by the DG
equals to S L = PL + jQ L Thus, DG output current is given
as:
FIGURE 1. A SIMPLE RADIAL DISTRIBUTION SYSTEM WITHOUT DG.
( PG − jQG )
IG = (3)
Load 3VP
AC Is IL The line loss with the integration of DG is a combination of
two parts:
(I) Line loss from source to the location of DG
IG (II) Line loss from DG location to the location of load
B.1) Line Loss from Source to DG Location
From Figure 2, it can be seen that
DG I S = I L − IG
G km Therefore, the expression for Loss ASG can be given as:

L km rG ( PL2 + QL2 + PG2 + QG2 − 2 PL PG − 2QL QG )


Loss ASG =
3VP2

FIGURE 2. A SIMPLE RADIAL DISTRIBUTION SYSTEM WITH THE ˄4˅


INCLUSION OF DG.
B.2) Line Loss from the Location of DG to Load Location
The load complex power is S L = PL + jQ L , therefore,
Line current in this sector is I which is the same as in
( P − jQL ) L

the current absorbed by load is: I L = L (1) the previous case with no DG. Thus, the line loss in
3VP this section can be expressed as:
IV. LINE LOSS REDUCTION ANALYSIS
r ( L − G )( PL2 + QL2 )
Loss B = ˄5˅
Electrical line loss occurs when current flows through 3VP2
transmission and distribution systems. The magnitude of
the loss depends on amount current flow and the line
resistance. Therefore, line loss can be decreased by reducing B.3) Total Line Loss
either line current or resistance or both. If DG is used to By combining line loss from source to the location of DG
provide energy locally to the load, line loss can be reduced and from DG location to the location of load, the total line
because of the decrease in current flow in some part of the loss can be expressed as:
network.
A. Line Loss Analysis for System without DG rL ( PL2 + Q L2 + PG2 + QG2 − 2 PL PG − 2Q L QG ) G
Loss ASG =
3V P2 L
Schematic of the system for this analysis is shown in ˄6˅
Figure 1. Line loss on a distribution feeder is equal to the
C. Line Loss Reduction
product of line current squared times the line resistance.
Therefore, line loss equation for a three phase system is
Loss reduction (LR) is given by the difference in the line loss
defined as:
with and without DG. Hence,

2043
LR = Loss − Loss B AT ˄7˅ location, resulting in lower electrical line loss. However,
higher DG ratings cannot always guarantee lower line loss.
rG (2 P P + 2Q Q − P − Q ) 2 2
The figure shows that as DG rating increases higher than 2.0
= L G L G G G

pu, the rate of line loss reduction actually declines. This


3V 2

P
indicates that DG
The positive sign of LR indicates that the system loss may cause a higher line loss in the distribution system if
reduces with the integration of DG. In contrast, the the rating and location of DG are not well justified. Hence,
negative sign of LR implies that DG causes the higher this fact should be taken into account before determining the
system loss. rating and location of DG. The suitable rating of DG mainly
D. Per-unit Loss Reduction depends on the amount and location of load in the feeder.
Per-unit loss reduction (PULR) is defined as the ratio Generally, the higher amount of load, the penetration of DG
of loss reduction to the line loss without DG. PULR can be higher without causing higher electrical line loss in
presents the benefit of DG in normalized form. the system.
The location of DG also plays a vital role for electrical
LR
PULR = line loss. To study this affect, the locations of DG are varied
Loss B along the feeder: 20 (location 1), 40(location 2), 60 (location
˄8˅ 3), 80(location 4), and 100% (location 5) from the source
G while load and DG power factors are kept at 0.85 lagging.
= 2 (2PL PG + 2QL QG − PG2 − QG2 )
( PL + QL2 ) L PULR are calculated once again by (13) and the results are
shown in Figure 4.
Consequently, the percentage of line loss reduction is
simply defined as:

% LR = PURE * 100 ˄9˅

V. RESULTS OF LINE LOSS REDUCTION


ANALYSIS
The influences of varying DG location and varying DG
power output are considered in this section. In order to
evaluate the effect of DG power outputs to the system loss,
both of load and DG power factors are set at 0.85 lagging
and the DG is assumed to install at the middle of feeder. The
DG power outputs are varied over seven values: 0.2, 0.4, 0.6,
0.8, and 1.0, 1.2, and 1.4 pu while the amount of load is kept
constant at 2.0 pu. PULR values calculated using (13) are
plotted against DG power outputs, as expressed in Figure 3

FIGURE 4. VARIATION OF LINE LOSS REDUCTION WITH DIFFERENT DG


POWER OUTPUT AND LOCATION.

Figure 4 clearly indicate that both of rating and


location of DG are highly sensitive to the line loss in the
system. The results show that the line loss reduces as DG is
installed closer and closer to the load. However, this fact
only applies for the case that DG rating is well matched with
the amount of load. If the ratio of DG power output to the
amount of load increases beyond the suitable point, the DG
that installed near the load will cause more electrical line loss
than the one that installed far away from the load. This is
because load cannot consume all the power supplied by DG.
Thus, the remaining power from DG is fed back to the source
FIGURE 3. VARIATION OF LINE LOSS REDUCTION WITH DG POWER OUTPUT.
via the distribution line, resulting in higher line loss.
From the figure, it is clearly seen that DG can reduce However, it should be noted that the location of load in this
the line loss in the system. This is due to the fact that DG study is placed at the line end.
supplies a portion of real and reactive power to the load.
Thus, the feeder current reduces from the source to DG

2044
VI. CONCLUSIONS [13] Xue Ying-chengˈTai Neng-lingˊIntroduction to the Existing DG
Interconnection Standards Worldwide ˊ Southern Power System
Use of distributed generation is one of the many Technologyˈ2008ˈ2(6)˖13-17.
strategies electric utilities are considering to operate their
systems in the deregulated environment. Several DG
technologies are showing promise for this application.
Inclusion of DG at the distribution level results in several
benefits, among which are congestion relief, loss reduction,
voltage support, peak shaving, and an overall improvement
of energy efficiency, reliability, and power quality.
This paper has considered the benefit of DG on loss
reduction for a simple case of a radial distribution line with
one concentrated load at the end and one DG. The results
clearly indicate that DG can reduce the electrical line loss.
However, the inclusion of DG does not always guarantee the
line loss. The DG rating, location, and operating power
factor are important factors for line loss reduction. Therefore,
those factors have to consider very carefully in order to
determine the best location and rating of DG.
The benefits obtained by the introduction of DG should be
weighed against the costs involved before deciding on the
use of DG. As DG technologies improve and cost decrease,
their use is expected to rise.

VII. ACKNOWLEDGEMENT
Preparation of this paper was supported by the Electrical
Engineering College of Northeast Dianli University. The
sponsorship and encouragement provided by the Electrical
Engineering College are acknowledged with thanks.

REFERENCES
[1] IEEE 929-2000 IEEE Recommended Practice for Utility Interface of
distributed generation Systems.
[2] Martin, G., “Renewable Energy Gets the Green Light in Chicago,”
IEEE Power&Energy Magazine, pp. 34-39, November/December
2003
[3] UL 1741-2001 Inverters, Convertersˈand Controllers for Use in
Independent Power Systems.
[4]GB/T 19939-2005 Technical requirements for grid connection of
distributed generation systemˊ
[5] Compiled by Solar Energy Association of Japan. Translated by LIU
Shu-min, HONG Wei. Solar photovoltaic system design and
construction.Beijing: Publisher of Science, 2006.
[6]State Grid Corp-2009, Technical rule for connection power station to
gird (Trial)ˊ
[7]GB/Z 19964-2005 Technical rule for connection power station to
electric power systemˊ
[8] ANSI C84.1 American National Standard for Electric Power Systems
and Equipment Voltage Ratings (60 Hz).
[9] IEEE Std 519-1992 IEEE Recommended Practices and Requirements
for Harmonic Control in Electrical Power System.
[10] IEC 61727-2004 distributed generation systems—Characteristics of
the utility interface.
[11] GB/T 12326-2008 Power quality-Voltage fluctuation and flickerˊ
[12] Andrews, C. J. and Weiner S. A., “Visions of a Hydrogen Future,”
IEEE Power&Energy Magazine, pp. 26-34, March/April 2004.

2045

You might also like