MAJOR UNDERGROUND FAULT DUTY & PROTECTION DATA FORM


FACILITY CNP WORK CENTER ADDRESS DATE PREPARED

SERMANTECH TECHNICAL PM0504 (UDG-003424) 25 SOUTHBELT INDUSTRIAL DRIVE 3/22/2019


CONTACT NAME CONTACT EMAIL CONTACT PHONE CONTACT FAX

FIGUEROA, NELSON nelson.figueroa@centerpointenergy.com 713-207-6365 ----

SYSTEM FAULT DUTY DATA


Fault Data Reference Point: SERVICE TRANSFORMER PRIMARY

BASE VALUES THEV IMPEDANCE LLL FAULT LG FAULT


Power [MVA] Voltage [kV] R1 [pu] X1 [pu] R0 [pu] X0 [pu] Current [A] X/R Current [A] X/R
100 34.50 0.12550 0.45180 0.32410 1.07450 3,569 3.60 2,437 3.44

SERVICE TRANSFORMER DATA


VOLTAGE WINDING CONFIGURATION
ID kVA %Z
Primary Secondary Primary Secondary
TR-1 1,000 5.60 34,500 480Y/277 DELTA WYE GND'd WYE DELTA WYE GND'd WYE

NEAREST UPSTREAM PROTECTION DATA


RATING MFR CAT# LOCATION VOLTAGE [kV]
FUSE 25K Kearney 31025-53 34.50
OR
MFR CAT# VOLTAGE TAP SETTING [A] TIME DIAL INST [A] CT RATIO
PHASE RELAY (50/51L)
MFR CAT# VOLTAGE TAP SETTING [A] TIME DIAL INST [A] CT RATIO
GROUND RELAY (51G)

NOTES