b) A final test procedure for the product shall include proof of performance specifications.
c) An on-site test procedure shall include an inspection of controls and indicators after installation of
the equipment.
2.02 Standards
The UPS shall meet the requirements of the following standards:
a) UL-1778, Standards for Uninterruptible Power Supply Equipment, April 1992 revision. The UPS
shall be listed per UL-1778 by the UL agency.
b) IEEE 587-1980/ANSI C62.41 1980 Standards for Surge Withstand ability
c) The UPS shall be designed in accordance with the applicable sections of the documents
published by:
I. National Fire Protection Association (NFPA)/ National Electric Code (NEC)
II. National Electrical Manufacturer's Association (NEMA)
III. Occupational Safety & Health Administration (OSHA)
d) All components shall be listed by Underwriter's Laboratories, Inc. (UL) whenever such listings
have been established.
e) ISO 9001 Quality Standard
Page 1 of 130
2.03 Materials
All materials and parts comprising the UPS shall be new, of current manufacture, and shall not
have been in prior service, except as required during factory testing.
b) System Load: The UPS system shall be able to supply a minimum load of _____kVA /
______ kW consisting of ______ UPS modules rated at________kW.
c) Battery Protection: Each UPS module shall be provided with its individual battery bank.
Each battery bank shall be capable of supporting the rated module power for a minimum
period of ____ minutes at _____ kW load at a temperature of 25°C.
3.02.1 Normal :
The inverters shall continuously supply 100% of the power to the critical load. The
rectifier/battery chargers shall derive power from the utility AC source and supply DC power
to the inverters while simultaneously float charging the batteries.
Each UPS module shall support an equal share of the total load during normal, emergency, or
recharge operation. Each UPS module will automatically disconnect and isolate from the
system load in the event of a module failure, with no interruption to the critical load. For a non-
redundant system, the remaining UPS modules will support the critical load until the defined
overload period has expired, at which point the system will transfer to the bypass source.
3.02.2 Emergency:
Upon failure of the utility AC power source, the inverters, which, without any switching, shall
obtain power from the batteries and continue to supply the critical load. Upon restoration of the
input power from utility or back-up generator power (prior to complete battery discharge) the
rectifiers shall automatically start providing power to the inverters and simultaneously charge
the battery.
Page 2 of 130
3.02.3 Bypass:
The system static switch shall be used to transfer the load to the system bypass without
interruption to the critical power load. This shall be accomplished by turning the inverters off.
Automatic re-transfer or forward transfer of the load shall be accomplished by turning the
inverters on.
3.02.4 Maintenance:
A manual make before break (overlap) system maintenance bypass switch shall be provided
to isolate the UPS system output and system static switch for maintenance. This shall allow
each UPS module to be tested or repaired without affecting load operation.
3.03.1 Normal:
The UPS modules shall continuously supply power to the critical load via the inverter. The
rectifier/battery charger shall derive power from the utility AC source and supply DC power
to the inverter while simultaneously float charging the battery.
3.03.2 Emergency:
Upon failure of the utility AC power source, the critical load shall be supplied by the inverter,
which, without any switching, shall obtain its power from the storage battery. There shall be
no interruption to the critical load upon failure or restoration of the utility AC source.
3.03.3 Recharge:
Upon restoration of the utility AC source (prior to complete battery discharge), the
rectifier/battery charger shall power the inverter and simultaneously recharge the battery.
This shall be an automatic function and shall cause no interruption to the critical load.
3.03.4 Downgrade:
If the battery only is to be taken out of service for maintenance, it shall be disconnected
from the rectifier/battery charger and inverter by means of a battery disconnect. The UPS
shall continue to function as specified herein, except for power outage protection and high
transient response characteristics.
Scalability:
The individual UPS modules must be scalable up to 225 kVA with minimal or no requirements for internal
modification should the power level have to be increased.
In the event that it should be required to add additional modules to the system, it shall be possible to add
modules for either redundancy or capacity by junctioning the outputs of the modules. The system
shall be capable of accommodatingof accommodating up to three modules for capacity plus one
module for redundancy for a total of four modules.
Page 3 of 130
a) Voltage Range: 480 VAC, ± 15%, 3 phase, 3 wires and ground, or 3 phase, 4 wires plus
ground
b) Frequency Range: 60 Hz, ±10%
c) Input Power Factor: up to 0.9 at full load and nominal input voltage.
d) Reactive Current: not to exceed 15% of the UPS nominal input current
e) Input current distortion: < 7.5% @ 255 kVA with full load and nominal input voltage
f) Input Current Walk-in: 0 to 100% over a five second period.
g) Magnetizing Inrush Current: 100% of nominal input current for less than one cycle.
a) Voltage: 480 VAC, 3 phase, 3 or 4 wires plus ground (adjustable +/- 5%)
b) Voltage Regulation: + 0.5% for balanced load; <+ 5% for 100% unbalanced load
The UPS shall be capable of providing the nominal output frequency 60 Hz ± 2.0 Hz
(selectable in 0.25 Hz increments) when the UPS inverter is synchronized to the bypass AC
input line.
Page 4 of 130
j) Frequency Slew Rate:
The slew rate or rate of change of the UPS inverter output frequency when the UPS is
tracking the bypass AC source frequency shall be selectable in 0.5 Hz/second increments up
to 2.0 Hz/second. The UPS will track the bypass when the bypass power is within the
frequency synchronization window as specified in the output frequency regulation, or when
returning to a free-running condition.
k) System Overload:
The UPS module shall be capable of supplying regulated output voltage during overloads of
up to 125% of its ratings for a period of 10 minutes and 150% for one (1) minute. Overloads
in excess of 167% of the UPS rating on an instantaneous basis or in excess of the overload
time periods previously stated shall cause the static bypass transfer switch to reverse
transfer and allow the AC bypass input line to supply the necessary fault clearing current
required. For an instantaneous overload (167% or greater,) after approximately 5 seconds
after the overload has cleared, the static bypass transfer switch shall automatically forward
transfer to the inverter and normal UPS operation shall resume. If the overload still exists
after the five-second period, the static bypass transfer switch shall automatically reverse
transfer the load to the AC bypass input source and the UPS inverter shall turn off. The
system shall require manual restart after this sequence and for timed overload transfers.
l) System Efficiency:
The overall efficiency of the module including input filter and input isolation transformer, input
to output (AC to AC), with nominal input voltage, battery fully charged and the inverter
supplying full rated load, shall be 93.5% at 100% load and 93 % at 50% load.
Page 5 of 130
3.06 System Components
3.06.1 Rectifier/Battery Charger
General:
Incoming AC power shall be converted to a regulated DC output voltage by the
rectifier/battery charger. A solid-state SCR phase-controlled bridge rectifier shall provide
regulated DC voltage, which shall be subsequently filtered to provide power for the
inverter and battery charging functions. The rectifier/battery charger shall employ input
AC current limiting as well as battery charge current limiting for battery protection. The
battery charging circuitry shall be capable of being set for automatic battery recharge
operation, float service, manual battery charge service and equalizing or commissioning
operation.
a) AC Input Protection:
The rectifier/battery charger shall be designed to limit the input harmonic current
distortion fed back into the input source to less than ____% with nominal input voltage
and rated load on the UPS inverter output.
The rectifier/battery charger shall contain a walk in circuit that causes the unit to assume
the load gradually after the input voltage is applied. Currents shall increase from 20% to
100% over a 5 second period after the battery open circuit voltage has been reached.
The initial magnetization inrush current shall be limited to 100% of the rectifier/battery
charger full load current.
The rectifier/battery charger shall limit the reactive current to less than 15% of the
nominal input current at no load preventing excessive reactive current from interfering
with generation operation. Reactive current shall be inhibited with a 100% solid state
system.
g) Capacity:
Page 6 of 130
The rectifier/battery charger shall have sufficient capacity to support a fully loaded
inverter and recharge the battery to 95% of its full capacity within 10 times the discharge
period when input current limit is set at 125% of the normal full load rating.
h) Current Limiting:
Two separate and distinct current limiting schemes shall be employed in the
rectifier/battery charger.
The AC input current limit shall operate such that the total DC output current of the
rectifier/battery charger is sufficient to operate the inverter at rated load and recharge a
discharged battery to 95% of its original capacity in 10 times the discharge period.
Current demands in excess of this setting shall cause a corresponding decrease in the
rectifier/battery charger output DC voltage. Input current limit shall be set at 150% of
nominal input current. A programmable second step input current limit, allowing a further
limit of the input current, shall be activated by a dry contact input.
The battery charge current limit shall limit the DC recharge current by reducing the
rectifier/battery charger DC output voltage when a set current limit set in the UPS
personalization is reached. The charger may apply up to 10% of the nominal DC current
to the battery, ensuring a recharge time equal to 10 times the discharge time at full load.
A second, lower charge current limit shall be provided and activated by a customer
provided dry contact input.
The battery charger logic circuitry shall be set up to manually accommodate four modes of
operation by an internal selector switch.
a) Automatic:
In this mode of operation, the battery charge output voltage shall be set at a charge voltage
which shall be slightly higher than the normal float voltage after the UPS experiences input
AC power outages of a set (selectable between 0 - 255 seconds) duration. After (0 - 255
hours) of operation at the charge voltage, the battery charger output voltage shall
automatically revert to the normal float voltage condition. For input AC power outages of less
than the selected duration, the normal float voltage level shall be maintained.
b) Float Service:
In this mode of operation, the battery charger output voltage shall be capable of providing a
float voltage that can be adjusted to the desired value depending on the number and type of
cells used in the external battery.
In this mode of operation, the battery charger output voltage shall be capable of being set to a
voltage slightly higher than the normal float voltage setting. Normally, the charge voltage
setting shall be set at the maximum float voltage setting specified by the battery
manufacturer.
Page 7 of 130
d) Equalize/Commissioning Service:
This operation shall be performed with the UPS inverter turned off. The equalize or
commissioning voltage shall be capable of being set at 2.4 to 2.6 Volts per cell for a lead acid
battery. The equalize or commissioning operation shall only be performed:
1. on new batteries that are supplied dry charged with separate electrolyte
2. an installed battery that has significant voltage differential from cell to cell
3. if specified by the battery manufacturer as part of the normal start-up sequence for
commissioning the use of this battery
The battery charger shall be equipped with a manual and selectable timer that can be used
periodically to maintain the battery in optimum condition. At the conclusion of the selected
charge period, the battery charger output voltage shall revert to the normal float voltage
setting.
a) DC Ripple Voltage:
The DC ripple voltage shall be limited to a value less than 1% of DC voltage at nominal UPS
load.
When operating on battery, a low battery voltage protection circuit shall be used to monitor
the DC bus voltage. The UPS inverter shall be automatically turned off when the battery
voltage reaches the cut off voltage. At a pre-set battery voltage value or two (2) hours after
the UPS has shutdown on a DC under voltage condition (battery cut off voltage), the battery
circuit breaker shall open in order to prevent excessive battery discharge.
The battery charger shall be equipped with a temperature probe to enable temperature
compensated charging. Installation of the probe shall be optional. The temperature
compensated charging process shall adjust the battery float voltage to compensate for the
ambient temperature using a negative temperature coefficient of 3 mV per cell per degree
Celsius at nominal temperature of 25 degrees Celsius.
An input circuit breaker shall be provided at the input of the rectifier. The breaker shall be
sized for the maximum load current of the UPS and recharging of the battery simultaneously.
In the event that UPS logic control power is lost the breaker shall open via a shunt voltage
trip.
e) Rectifier Fusing:
The inputs of the rectifier shall be protected with fuses to prevent failures of the rectifier
SCRs from affecting any other UPS components. The fusing shall only operate to prevent
catastrophic failure of the SCRs and shall not be used for thermal overload protection of the
current path.
3.07 Inverter
Page 8 of 130
General:
The UPS output shall be derived from a Pulse Width Modulated (PWM) output signal with active
error gain correction, and shall utilize IGBT (insulated gate bipolar transistors) on the inverter
design. The inverter shall be capable of providing the specified precise output power
characteristics while operating over the battery voltage range with no deterioration of
performance specifications.
The inverter assembly shall be constructed of modular rack mounted assemblies to facilitate
rapid maintenance and inspection.
3.07.1 Output
The inverter output voltage and capacity shall be as specified and shall operate in
accordance with the following regulation requirements:
1. 0% to 100% load
2. Ambient temperature variations
3. Minimum to maximum DC bus voltage
4. Balanced load conditions
5. Loss or return of main AC input power
For balanced load conditions, the inverter phase displacement shall be 120° ±1°
maximum. For 100% unbalanced loads, phase displacement shall be 120° ±3° degrees
maximum.
b) Voltage Adjustments:
The inverter shall have a control to manually adjust the output voltage ± 5% from the
nominal value.
c) Frequency Control:
The output frequency of the inverter shall be controlled by an oscillator, which shall be
operated as a free-running unit when not synchronized to the bypass AC input source.
The inverter shall track the synchronizing source within ± 2 degrees. If the external
synchronizing source deviates from the preset frequency by ±0.5 Hz, the oscillator shall
automatically revert to a free-running mode of operation.
A customer provided contact closure shall be provided to (1) allow the unit to be
operated continually on its internal oscillator with the static bypass transfer switch
disabled or (2) for normal operation whereby the UPS inverter synchronizes to the
bypass AC input source and the static bypass transfer switch is enabled.
d) Frequency Regulation:
The inverter free-running (non-synchronized mode of operation) steady state output
frequency shall not deviate by more than ± 0.1% from the nominal frequency due to the
following conditions nor should the inverter output have any frequency transients for the
system disturbances:
1. 0% to 100% load
2. Ambient temperature variation.
3. Minimum to maximum DC bus voltage
e) Harmonic Distortion:
The inverter shall provide active output filtering necessary to limit the output voltage
waveform distortion (THD) to:
Page 9 of 130
1. Total Harmonic Distortion (THD) maximum of 3%, and single harmonics of 1%
maximum over the entire linear load
2. Non-Linear Load Capability. Output voltage total harmonic distortion (THD) shall be
less than 4% when connected to a 100% non-linear load with a crest factor not to
exceed 3.5.
f) Dynamic Regulation:
The inverter dynamic voltage regulation shall not exceed ± 5% due when a 100% load
step is applied or removed with 0% or 100% initial load.
g) Transient Recovery:
The output voltage shall return to within ± 0.5% of the steady state value within 16.67
milliseconds (1 cycle).
h) Overload:
The inverter shall be capable of supplying currents and regulated voltage for overloads
up to 125% of full load current for a period of 10 minutes and 150% current for one
minute. The static bypass transfer switch shall transfer the load to bypass if the overload
exceeds the inverter's instantaneous rating of approximately 167% or the time periods
previously stated.
i) Fault Clearing:
The inverter shall electronically current limit to protect against excessive overload
conditions. Simultaneous to turning the inverter off, the static bypass transfer switch shall
be used to transfer the load to the bypass AC input source, which shall be used to
provide the necessary fault clearing current required.
If the bypass is not available, the inverter shall current limit at 212% of rated output
current for 200 milliseconds. If the fault is not cleared, the inverter shall shut down if
bypass is still not available.
j) Inverter DC Protection:
The inverter shall be protected by the following features that shall be independently
adjustable for maximum system flexibility.
1. Output Protection:
The inverter shall immediately current limit to protect against overloads and abnormal
load conditions, which exceed the unit's rating without sustaining any damage to any
part of the UPS.
2. Over-current Protection:
The inverter shall be protected from excessive overloads, including faults and
reverse currents, by fast-acting fuses to prevent damage to power semiconductors.
The purpose of theof the inverter output fusing shall be only to clear inverter failure
faults. These fuses shall not clear in the event of a load short on the inverter output.
3. Surge Protection:
The inverter shall have built-in protection against under voltage, over current, and
over-voltage surges on the output caused by load transfer between the UPS and the
bypass AC input source.
Page 10 of 130
5. Thermal Overload Protection:
The inverter shall be provided with thermal overload protection to alarm and then
protect against fan failures and high internal ambient temperature conditions.
3.08 Display and Controls
The control panel on Galaxy PW™ UPSs shall comprise the controls and indications required to check the general
status of the system. The control panel shall be designed to provide an easy and rapid overview of
system status and shall not require particular training. The UPS information shall concern only the UPS on
which the panel is located. System level information for multi-module systems shall be displayed of the System
Bypass Cabinet.
a) The UPS shall be provided with a status/control panel for each of the UPS modules. The
System Bypass Cabinet used on multi-module systems shall also include an LCD display to
and control panel for system level monitoring. The UPS control panel shall include a day light
visbile high contrast display for status/alarm, metering and display of operating instructions
(in five languages). Approximately fifty (50) conditions are monitored and displayed on a
combination of LED's and the LCD on the status panel.
b) The control panel shall include an LED mimic diagram to indicate the power flow of the UPS
module.
c) UPS operation shall be controlled via a microprocessor controlled logic system. All
operations and parameters are firmware controlled and shall not require any manual
adjustments or potentiometers.
Page 11 of 130
LED Indicator Panel: The control panel shall have an LED indicator array showing with the following
LED indicators:
"Rectifier/charger" LED
■ light off: rectifier/charger OFF
■ light shines green: rectifier/charger ON
■ light shines red: rectifier/charger fault
In the event of a rectifier charger fault the associated alarms shall be displayed on the alphanumeric display panel:
❏ input circuit breaker Q1 open
❏ protection fuse at the rectifier/charger input (FUE) blown
❏ abnormally high internal rectifier/charger temperature
❏ abnormally high battery charge current
❏ abnormally high battery voltage
❏ fault, non-calibration or non-personalization of the electronic control board for the rectifier/charger
❏ fault on the electronic power-supply board
❏ abnormally high temperature in the harmonic filter inductor
"Battery" LED
■ light off: battery float charging
■ light flashing green: battery recharging
■ light shines green: load on battery power
■ light flashing red: low-battery shutdown warning
■ light shines red: battery at end of back-up time and circuit breaker QF1 open, or battery fault
"Static-bypass" LED
■ light off: bypass AC source within specified tolerances and static bypass open
■ light shines green: static bypass closed
■ light shines red: the stored alarm indicates one or several of the following faults:
❏ bypass AC source voltage or frequency outside specified tolerances
❏ static-bypass fault
❏ abnormally high internal static-bypass temperature
❏ static-bypass ventilation fault
❏ power-supply fault for the static-bypass control function
❏ fault on the electronic board controlling the transfer function
❏ non-calibration or non-personalization of the electronic control board for the inverter
❏ fault on the electronic power-supply board
❏ fault on monitoring the "inverter ready" response channels (parallel UPS system)
"Inverter" LED
■ light off: inverter OFF
■ light flashing green: inverter starting, inverter ON but not connected to the load
■ light shines green: normal inverter operation
■ light shines red: inverter fault, the stored alarm indicates one or several of the following faults:
❏ inverter shutdown due to inverter output voltage outside specified tolerances
❏ protection fuse at the inverter output (FUS) blown
❏ abnormally high inverter-output transformer temperature
❏ abnormally high inverter temperature
❏ output-voltage fault (amplitude or phase) (parallel UPSs)
❏ fault, non-calibration or non-personalization of the electronic control board for the inverter
❏ fault on the electronic power-supply board
"Load" LED
■ light off: load not supplied
■ light shines green: load supplied via the inverter or the bypass AC source (via the static bypass)
Page 12 of 130
"Anomaly" indicator LED: This indicator light indicates the presence of anomalies
Audible Alarm:
The UPS shall be be equipped with an audible alarm will sound under the following situations:
The alarm shall sound slowly and discontinuously for a minor problem or when the inverter is on battery power. When
the alarm "LOW BATTERY SHUT-DOWN" is activated, the buzzer shall sound more rapidly. Finally, if the inverter
shuts down, the sound shall be loud and continuous. The buzzer may be reset by pressing the alarm acknowledge
button. If the buzzer is reset, a higher level alarm shall set it off again.
Keypad:
The Galaxy PW shall be equipped with a mechanical keypad to allow the navigation of the display and
operation of the UPS. The keypad shall consist of the following keys:
"Inverter ON" button: This button is used to start the inverter locally.
"Inverter OFF" button: This button turns the inverter off locally. The key shall be depressed for over three
seconds to turn inverter off to avoid accidental transfer to bypass.
Menu Select Keys: These keys are used to select commands in the main menu and access the secondary
messages.
Validation Key: This key is used to validate the user’s choice once a menu item is selected.
Menu Settings Key: This key is used to access the main menu: display language, display-contrast setting, sound
level of the buzzer, lamp test, date and time settings, inverse-video and event log.
"W.Hz" Power / Frequency key: This key is used to access other measurements:
■ normal AC source, bypass AC source and inverter frequencies
■ level of active and apparent power drawn by the load
■ load power factor
■ inverter load level (percent)
"Primary Message" key: This key is used to access the primary messages.
Page 13 of 130
■ battery temperature
■ available battery backup time
■ inverter load level (percent)
"Forced-transfer" key: This key is used to voluntarily transfer the load to the inverter or from the inverter to the
static bypass (return transfer). Transfer and return transfer are carried out only following confirmation requested by
the system display and a warning as to the risk of an interruption in the supply of power to the load.
"Alarm reset" key: This key is used to reset stored alarms. The system accepts resetting only when alarms have
been cleared.
"Buzzer reset" key: This key is used to stop the buzzer. However, new alarms set the buzzer off again.
LCD Display:
The LCD display continuously indicates the system operating status as well as list primary and secondary messages
relating to UPS status and operation:
Primary Messages
LOAD PROTECTED / ON-LINE MODE: This is the normal display when there are no alarms or problems and the
load is correctly supplied by the inverter, in on-line mode.
LOAD PROTECTED / PARALLEL ON-LINE MODE: This is the normal display when there are no alarms or problems
and the load is correctly supplied by the inverter in a parallel UPS system, in on-line mode.
LOAD NOT PROTECTED / ON-LINE MODE: This display indicates that the load is not supplied by the inverter, or
that there is no battery backup. The buzzer sounds continuously.
LOAD NOT PROTECTED / PARALLEL ON-LINE MODE: Situation identical to that in the previous screen, but for
parallel UPS systems.
LOAD PROTECTED / BATTERY DISCHARGING: Remaining battery time (min) = XX % kW used = XXX
The load is supplied by the inverter, but the normal AC source is down or outside tolerances and power is supplied by
the battery. This message indicates the remaining battery time in minutes prior to inverter shut-down
and the percent load. The battery time calculation takes into account:
LOAD PROTECTED / LOW-BATTERY SHUTDOWN WARNING: Remaining battery time (min) = XX % kW used =
XXX. This message replaces the preceding if the power outage persists and the warning level has been reached.
The user is warned that the battery is about to shut down. The buzzer sounds rapidly and discontinuously.
LOAD PROTECTED / ECO MODE: This is the normal display when there are no problems: the load is supplied by
the inverter or the bypass AC source, and battery backup is available.
LOAD NOT PROTECTED / ECO MODE: This display indicates that the load is supplied but has no battery backup.
The arrow indicates the presence of one or more problems specified in secondary messages. The buzzer sounds
continuously.
LOAD FORCED TO INVERTER ECO MODE: The load has been transferred to the inverter following a specific
request by the user.
Secondary Messages:
Page 14 of 130
LOAD ON MAINS 2: The load has been transferred to the bypass AC source (M2) and is no longer
protected (only in on-line mode). The buzzer sounds continuously.
MAINS 2 OUTSIDE TOLERANCES / TRANSFER DISABLED / CHECK MAINS 2: The bypass AC source (M2)
frequency or voltage is outside tolerances and the inverter is unable to synchronize. Transfer of the load from the
inverter to the bypass AC source (M2) or vice-versa will result in an interruption of the supply of power to the load.
The buzzer sounds slowly and discontinuously.
BATTERY ROOM VENTILATION / FAULT / CHECK VENTILATION: A fault requiring servicing has occurred in
the battery room ventilation system. The rectifier/charger shuts down after a 30-second time delay. The user must
take steps to re-establish correct operation of the ventilation system. This message also signals an abnormally
high temperature in the filter inductor. The buzzer sounds slowly and discontinuously.
MAINS 1 OUTSIDE TOLERANCES / CHECK MAINS 1: The normal AC source (M1) frequency or voltage is outside
specified tolerances and the rectifier/charger has shut down. The inverter is on battery power.
MAINS 1 INPUT SWITCH Q1 IS OPEN: The normal AC input (M1) switch Q1 is open. It must be closed for
rectifier/charger start-up. The buzzer sounds slowly and discontinuously.
INTERNAL UPS FAULT / LOAD TRANSFER FAULT / CALL MAINTENANCE: A fault has occurred in the static
switch that transfers the load between the inverter and the bypass AC source (M2). Servicing by the after-sales
support department is required. The buzzer sounds continuously.
OVERLOAD / RATED CURRENT PER PHASE = XXX A / CHECK LOAD LEVEL: This display informs the user that
load current is greater than rated current, and gives the value. The buzzer sounds continuously.
UPS SHUTDOWN DUE TO AN OVERLOAD / CHECK LOAD LEVEL: This message follows the preceding when
the overload persists. The UPS has shut down and the buzzer sounds continuously.
INVERTER NOT IN PHASE WITH / MAINS 2 / TRANSFER DISABLED /CHECK MAINS 2: The phase difference
between the inverter and the bypass AC source (M2) is outside tolerances. Transfer of the load between
the inverter and the bypass AC source (M2) will result in an interruption in the supply of power to the load.
For parallel UPSs, this message should be interpreted as meaning the phase difference between the inverter for
which the message is displayed and the other inverters is outside tolerances.
UPS SHUTDOWN BY AN EXTERNAL COMMAND: The inverter has received a command to shut down. The
command is in the form of a signal from received the remote indications relay board which has been set for
this function. n the inverter is started again.
MAINS 2 INPUT SWITCH Q4S IS OPEN: The bypass AC source (M2) input switch Q4S is open, i.e. backup power
for the load via the bypass AC source (M2) is not available.
INVERTER OUTPUT SWITCH Q5N IS OPEN: Inverter output switch Q5N is open, i.e. the load cannot be supplied
via the inverter.
BYPASS SWITCH Q3BP IS CLOSED: Maintenance bypass switch Q3BP is closed. The system is in maintenance
configuration and the load is supplied by the bypass AC source.
STATIC SWITCH (M2) OFF DUE TO AN OVERLOAD: The load is no longer supplied by the bypass AC source (M2),
due to an extended overload. The buzzer sounds continuously.
BATTERY AT END OF SERVICE LIFE CALL MAINTENANCE: The battery is nearing the end of its estimated
service life. This information is based on average service-life calculations since its initial installation. The buzzer
sounds slowly and discontinuously.
EMERGENCY OFF: This message is displayed when the external emergency-off pushbutton is pressed. The result
is:
Page 15 of 130
■ shutdown of the rectifier/charger
■ opening of the battery circuit breaker
■ blocking of the static bypass
■ opening of the backfeed protection contactor (M2)
■ opening of the Q1 circuit breaker (M1)
■ activation of a relay contact on the remote-indications relay board
Servicing by the after-sales support department is required. The buzzer sounds discontinuously.
THE BATTERY C.B. QF1 IS OPEN / CHECK THE INSTALLATION: Battery circuit breaker QF1 is open. The
load is no longer protected because battery power is no longer available in the event of a normal AC source outage.
The buzzer sounds continuously.
LOW BATTERY SHUTDOWN: The inverter has shut down at the end of battery power. The buzzer sounds
continuously.
INTERNAL UPS FAULT / INVERTER FAULT / CALL MAINTENANCE: A fault has occurred in the inverter.
Servicing by the after-sales support department is required. The buzzer sounds continuously.
INTERNAL UPS FAULT / CHARGER FAULT / CALL MAINTENANCE: A fault has occurred in the rectifier/charger.
Servicing by the after-sales support department is required. The buzzer sounds slowly and discontinuously.
THE NUMBER OF UPS READY IS INSUFFICIENT, LOAD TRANSFER IN STAND BY: This message may be
displayed in non-redundant, parallel UPS systems, when the number of ready inverters in not sufficient
to supply the load.
INVERTER NOT CONNECTED: This message may be displayed in parallel UPS systems, when the inverter is not
connected to the load.
PARALLEL UPS, FORCED TRANSFER INHIBITED: This message is displayed when forced
connection is requested on a parallel UPS system for a power extension.
INTERNAL UPS FAULT, SELF-TEST FAULT: Communication between the system and the display is faulty. The
buzzer sounds slowly and discontinuously.
UPS SUPPLIED BY A GENERATOR SET: This message informs the user that the UPS has received the order to
limit the current drawn by the rectifier/charger. It is displayed when the corresponding signal is transmitted by the
remote indications board which must be configured for this function.
Page 16 of 130
Power Measurements:
The UPS display shall indicate all of the following power measurements for the specific UPS module.
System power measurements shall be displayed on the System Bypass Cabinet display.
■ Battery
❏ voltage
❏ charge or discharge current
❏ remaining battery time (for the specific UPS module)
❏ battery temperature
■ output load
❏ phase-to-neutral voltage
❏ phase-to-phase voltages
❏ currents of the three phases
❏ frequency
❏ active and apparent power
❏ frequency
■ log all UPS events and alarms with a date and time stamp
■ allow referencing of the last 500 alarm / events that occurred on the UPS module
■ provide general statistical data on UPS operation
■ provide measurement records for a number of physical values concerning system operation.
The time-stamping information shall be accessed via the Galaxy PW™ keypad and display (standard equipment).
This information shall also be accessible via the RS232/485 communications board.
■ total backup time (h): this is the total time of operation on battery power since initial startup of the
UPS. It is expressed in hours
■ total time on static switch (h): this is the total time of operation on the static switch since initial startup of the UPS.
It is expressed in hours
■ total time on UPS (d): this is the total time that the load has been supplied by the UPS since initial startup. It is
expressed in days
■ total time with Tbatt > 25° C (h): this is the total time of operation with the battery temperature greater than 25° C
since initial startup of the UPS. It is expressed in hours
■ last reset: this is the date that the information was last set to zero by the Teleservice function;
■ elapsed backup time (min): this is the total time of operation on battery power since the last reset. It is expressed
in minutes
■ nb of backups: this is the number of times the load was supplied by the UPS from battery power since the last
reset
■ nb of backups < 1 min: this is the number of times the load was supplied by the UPS from battery power for less
than one minute, since the last reset
Page 17 of 130
■1 min < nb of backups < 3 min: this is the number of times the load was supplied by the UPS from battery power
for more than one minute and less than three minutes, since the last reset
■ nb of backups > 3 min: this is the number of times the load was supplied by the UPS from battery power for more
than three minutes, since the last reset
■ nb of overloads < 5 s: this is the number of times the UPS was overloaded (out-put current greater than In) for
less than five seconds, since the last reset
■ nbof overloads > 5 s: this is the number of times the UPS was overloaded (out-put current greater than In) for
more than five seconds, since the last reset
■ nb of times TBatt. > 25° C: this is the number of times the battery temperature was measured at over 25° C, since
the last reset
Operating log: The UPS shall maintain an operating that indicates the last 30 measurements
recorded for the given parameter in chronological order. Measurements shall be taken every 30 days.
The displayed measurements are instantaneous values The following parameters shall be tracked for the
operating log:
The battery capacity is the value measured by the UPS microprocessor. It is expressed in Ampere-hours. This value
changes over time depending on the parameters of the battery itself and its environment. This measurement is used
to check that the battery is capable of supplying the rated power in the event of a utility outage.
The backup time is the value calculated by the UPS microprocessor on the basis of measurements carried out on
the battery. It is expressed in minutes. The calculation uses the percent load and the battery charge status at the time
of the measurement.
The load level is the ratio between the power supplied by the UPS to the load at the time of the measurement and
the rated output of the UPS. It is expressed as a percentage.
The Galaxy PW shall be equipped with a battery management system that logs battery environmental
parameters, cycling history and monitors general battery health. The system shall also perform battery
performance tests at predetermined intervals to asses battery health.
The battery monitoring system shall be displayed on the LCD screen. When the battery test button is depressed it
shall indicate battery charge status and the estimated remaining service life of the battery. The user shall be able to
select the option of manually or automatically (at user predetermined intervals) initiating a battery test. Following the
completion of a battery test, the system shall indicate a positive or negative test result prompting further analysis of
the battery bank. In the event that the diagnostic system determines that it is dangerous to continue testing the
batteries the test shall be interrupted and the operator notified to check the appropriate alarm.
AUTO DIANOSTICS
The UPS shall be equipped with a continuously operating auto-diagnostic system that evaluates the operating
condition of the UPS and all the sub components. In the event that the diagnostics system detects a problem, the
system shall sound an audible alarm to alert the operator
Page 18 of 130
The Galaxy shall incorporate a dry contact relay array along with three communications card ports for use
with the optional communication card offerings.
Dry Contacts:
Alarm dry contacts shall be available for external connection. Each alarm shall include form C
contacts rated 5 Amp @ 250 Volts.
Inputs:
■ emergency off: A normally closed contact causes shutdown of the inverter and the rectifier/charger, opening
of the battery circuit breaker, blocking of the static bypass and activation of a relay contact on the "Media Contacts
11" board
■ battery room ventilation fault: An normally open contact causes shutdown of the rectifier/charger
■ battery circuit breaker QF1 closed: An NO contact prevents inverter start-up if the circuit breaker is open
■ battery temperature: A PC-board, placed near the battery, supplies information on the battery temperature,
thus enabling the rectifier/charger to regulate the battery voltage
■ "auxiliary" signals: Depending on the selected settings, these signals may be used to provoke:
❏ forced shutdown of the inverter (whatever the status of the bypass AC source)
❏ protected shutdown of the inverter (load transfer to the bypass AC source)
❏ limiting of the current drawn by the rectifier/ charger (programmable value) when supplied by an engine generator
set with an insufficient power rating. The additional power required by the inverter is supplied
by the battery which discharges
❏ limiting of the battery charge current (programmable value) if the normal AC source is replaced by an engine
generator set with an insufficient power rating. time is about to run out. The warning threshold may be personalized
Outputs:
Page 19 of 130
b) RS 232 / RS485 serial communications:
A standard serial communication port shall be provided to remotely monitor the UPS. All
alarms messages and standard measurements shall be available on the local port. The
port shall be configurable for RS-232 or RS-485 communications. The port shall use an
open J-BUS (subset of ModBus) protocol with all UPS status information (86 parameters)
available remotely.
The synchronization control circuitry shall monitor the bypass AC input source and provide a
frequency reference to the UPS modules when the bypass AC input source meets the
following criteria:
When the previous conditions are satisfied, an uninterrupted forward or reverse transfer of
the static bypass transfer switch shall be capable of being made.
If the conditions that noted in paragraph 3.10.1 are not satisfied, the frequency reference
provided to the UPS modules shall be determined by the internal oscillator contained in the
UPS module. The non-synchronized frequency source shall be the nominal frequency
±0.1%. During this mode of operation, an uninterrupted transfer shall not be made. If a
system overload or module fault occurs during this mode of operation, an interrupted
transfer having a minimum interrupt time of 200 milliseconds shall be made when
transferring the load to the bypass AC input source.
a) Bypass voltage greater than ± 10% from the UPS rated output voltage
b) Bypass frequency greater than ± 2 Hz (selectable in 0.25 Hz increments) from the UPS
rated output frequency
3.12 DC BUS
3.12.1 Battery Disconnect Breaker:
Each UPS module shall be furnished with a 2,000 A battery disconnect breaker mounted in a
self standing NEMA-1 rated enclosure. The battery disconnect breaker shall allow complete
interruption of all DC current to the UPS module. The battery breaker shall automatically
open in the event of the battery voltage falling to the maximum allowable discharge voltage,
activating the emergency power off (EPO / REPO) system or when activated to open by
other customer specified controlled systems.
The UPS shall be housed in a freestanding enclosure with a dead front construction. The
back of the UPS shall be capable of being mounted as close to a wall as practical. The UPS
cabinet shall be designed for top cable entry with optional bottom entry cabinets available.
Copper wire or bus shall be exclusively for all internal electrical connections excluding heat
sink subassemblies.
a) Dimensions:
The UPS module enclosure dimensions shall not exceed 82” height by 122” width by 39”
depth.
b) Access:
Front access only shall be required for installation and maintenance. All power connections
and component removal shall be possible from the front only.
4.01.2 Ventilation:
Forced air-cooling shall be provided to ensure that all components are operated within their
specified temperature ratings. Power component modules shall be cooled by redundant fans
located directly above critical power components ensuring that the cooling air path is not
obstructed. Internal air baffles shall carry heated air from large magnetic components directly
outside of the UPS to minimize the interior cabinet temperature. Redundant fans shall also be
located above the air baffles. Fan failures or a thermal overload shall be annunciated by a
contact closure. Air inlets shall be provided from the front of the UPS enclosure. Air exhaust
shall be from the top portion of the unit. Air filters on the inlets shall be provided as standard
and shall be readily replaceable from the front of the unit with out the requirement of opening
the UPS module doors.
a) Heat Rejection: Maximum heat rejection per UPS module at 800 kVA/720 kW load shall
be 190,000 BTUs per hour.
The audible noise level from the UPS shall be less than 75 dB "A" weighing when measured
five feet in front of the unit.
Page 22 of 130
a) System single line diagram and related submittal drawings
b) Installation Manual and Users Manual describing system installation requirements and
system operation including necessary safety requirements.
b) The UPS manufacturer shall have a minimum of five years of successful operation in on-line
three-phase parallel UPS systems.
c) The topology used shall be a true on-line topology as defined by the IEC 62040-3 standard
for on-line double conversion UPS systems
d) The design configuration in parallel redundant with 2 (N+1) mode of operation shall achieve
an overall system MTBF (Mean Time Between Failure) of not less than 500,000 hours.
b) All labor, materials, appliances, tools and equipment in connection with furnishing and
delivery of the UPS equipment shall be delivered to site loading dock, complete as shown on
the drawing and/or as specified herein.
c) Off loading from the truck and setting in place of all equipment including batteries specified
herein shall be responsibility of the installation contractor, including and all associated labor,
parts, tools and equipment.
d) Installation and wiring of all equipment shall be the responsibility of electrical installation
contractor under a separate contract.
5.04 Shipping
a) The UPS manufacturer shall include in the bid delivery of the equipment to the job site. The
delivery shall be based on dock-to-dock.
5.05 Training
The manufacturer personnel involved in the system start-up and testing shall provide training
concurrent to system start-up.
5.07 Maintenance
No rear access shall be required for any part replacement or maintenance procedure. All
parts of the UPS shall be designed to facilitate rapid maintenance. Thermal scanning of all
current carrying connections shall be accessible from the front of the UPS.
The UPS system shall be inspected and tested in the manufacturer’s plant to demonstrate
performance and full compliance with the requirements and the design. The UPS
performance can be and should be tested and verified in the factory during the in-plant tests.
A written test report that shows the results of the individual test that the equipment has
satisfactory completed the tests, and the UPS has the capability to support the load, as
required by the specifications. During factory testing all system's parameters must be
recorded.
The manufacturer shall provide all necessary testing equipment including load banks rated
for the full system (kW and kVA). All test instruments shall be calibrated and calibration labels
shall be visible on all test equipment.
a) General operation and functional test of each UPS module and system level. Verify
that all operating controls, alarms, meters, circuit breakers and mimic lights are
functioning properly.
b) Voltage regulation: Record each module and system output voltage at no load, half load
and full rated load.
c) Efficiency: Module efficiency shall be measured at the rated kVA and kW. The efficiency
test shall be performed with the battery circuit breaker open. The efficiency shall be
measured at 100% load.
d) Input current distortion: Record the input current distortion of all 3 input phases of each
UPS module.
e) Output voltage distortion: Record the output voltage distortion of all 3-output phases of
each module and system level at no load and full load.
f) Transient tests: Record output voltage, output current, bypass voltage and bypass
current during the transient tests of applying and removing 0% - 100% - 0% load.
Page 24 of 130
g) Transfer load: Record output voltage, output current, bypass voltage and bypass current
during transfer from inverter to bypass and bypass to inverter with no load and 100%
load.
h) Input fail test: With the module operating at full load and the battery connected,
disconnect the input power to the UPS. Record output voltage, output current, input
voltage and input current during on battery operation.
i) Overload test: Operate each module at 125% and 150% overload for the time specified.
j) Record all parameters indicated on the LCD panel under 0%, 50% and 100% load.
5.08.3.1 The UPS shall be tested on site in accordance with the following procedures:
a) A type written test report that shows the results of the individual tests, that the equipment
has satisfactory completed the tests, and the UPS has the capability to support the load,
as required by the specifications. During site test all system's parameters must be
recorded.
b) The UPS manufacturer shall provide all necessary testing equipment including load
banks rated for the full system kW. All test instruments shall be calibrated and calibration
labels shall be visible on all test equipment.
The UPS manufacturer shall guarantee a service response for the useful life of the
equipment, as long as the system is covered by the warranty period or a seven by twenty
four service agreement.
The UPS systems must be manufactured by MGE UPS SYSTEMS or approved equal.
6.0 ACCESORIES
6.01 Remote Alarm Status Panel
Page 25 of 130
A wall mounted panel with eleven (11) indicating LED's shall display UPS status and any active
alarms. The alarms shall be a latching type, such that if an alarm is triggered, the LED will stay
ON (latch) even if the alarm is corrected. This feature will provide the operator the chance to
verify the occurrence of the alarm. The parameters monitored and controls provided on the
RASP panel include:
Solution-PAC software shall facilitate the management of the UPS and servers over any
point in a wide area network (WAN) or local area network (LAN). The software shall use a
distributed, TCP/IP based architecture and must be SNMP manageable. To reduce the
volume of network traffic the software will employ trap reception acknowledgement.
The software must be capable of graceful server shutdown and management of individual or
multiple servers from any point on the network, for an unlimited number of servers.
Customizable shutdown scripts must be able to be implemented.
c) SNMP Interface
The communications port shall accommodate an SNMP converter to allow acquisition of all
UPS status points via SNMP protocol for the purpose of monitoring the UPS via a network or
direct connection to a PC. The SNMP adapter shall also allow for direct interface with a
computer network via standard network connection.
Page 26 of 130
6.03 Critical BUS Synchronization
6.03.1 Critical Bus Synchronization module (CBS) shall be required to keep the outputs of all three
(3) separate and independent UPS systems in sync during all operating conditions including
when:
6.03.2 The CBS shall be a parallel connected circuit that monitors the bypass and system output of
all UPS systems and it shall activate a sync signal under pre-determined and specific
conditions. The CBS shall not effect the standard and specified performance of the UPS
system detailed in the specifications.
6.03.3 The CBS shall be a wall-mounted enclosure and shall contain the following indications:
a) SYS 1,2 BYPASS AVAIL – Green Light. When lit it, indicates that the bypass power
to UPS system #1 is available and it is within allowed tolerance (nominal voltage +/-
10%).
b) BYPASS 1, 2 IN SYNC – Green Light. When lit, it indicates that the bypass sources of
UPS system #1 and UPS system #2 are in sync and within the selected and programmed
phase angle.
c) SYSTEMS IN SYNC – Green Light. When lit, it indicates that the UPS outputs of both
systems (1 and 2) are in sync and within the allowed limits. This indication is derived from
comparing the output of the second UPS system to the output of the selected MASTER
system.
d) SYNC CKT ACTIVATED – Amber Light. When lit, it indicates that the CBS is activated
and the UPS systems outputs are no longer tracking their respective bypasses but
instead they are synchronized to the selected “MASTER”.
e) SYNC CKT INHIBITED – Red Light. When lit, it indicates that the CBS is not active due
to one or more of the following conditions:
1. SYNC MODE SELECT is in the OFF position
2. One of the UPS systems is on maintenance bypass
3. All systems are on static bypass
h) LAMP TEST – When pressed it will turn ON all lights as a functional test.
a) Normal operation:
Page 27 of 130
Under normal operation, both UPS systems are in full operation feeding their respective
loads. Their bypass power is available and they are in sync. The Outputs of both systems
are in sync and the CBS is in AUTO mode but not active.
This condition shall remain until the bypass power is re-applied. Upon application of
bypass power, the selected master UPS system shall automatically track its bypass
source. The slave UPS system shall continue to track the selected master UPS system.
When the bypass sources are in sync, the CBS shall de-activated after a preset time
delay and the UPS system shall track its respective bypass source. De-activating the
CBS shall also de-activate the transfer to bypass inhibit signal. Normal operation shall
resume.
Should the bypass power fail on one UPS system, the CBS shall automatically activated
(SYNC CKT ACTIVATED light is lit) after a preset time delay and the outputs of the two
UPS systems shall remain in sync. A signal from the CBS shall be sent to the UPS
system with the failed bypass source inhibiting it from manual or automatic transfer to
bypass.
This condition shall remain until the bypass power is re-applied. When the bypass
sources are in sync, the CBS shall de-activate after a preset time delay and each UPS
system will track its respective bypass source. De-activating the CBS shall also de-
activate the transfer to bypass inhibit signal. Normal operation shall resume.
Should the bypass power on UPS systems is available but they are out of sync or outside
the selected and preset phase angle, the CBS shall automatically activated (SYNC CKT
ACTIVATED light is lit) after a preset time delay and the outputs of the two UPS systems
are in sync.
This condition shall remain until the bypass sources are in sync, the CBS shall de-
activated after a preset time delay and each UPS system will track its respective bypass
source. De-activating the CBS shall also de-activate the transfer to bypass inhibit signal.
Normal operation shall resume.
1. Should one UPS system transfer to bypass, this system shall become the master
regardless of the position of the MASTER SELECT switch. The systems shall
synchronize to the MASTER system after the preset time delay should the UPS
outputs go out of sync.
2. Should one UPS system transfer to maintenance bypass, the CBS shall be inhibited
(SYNC CKT INHIBITED light is lit) and each UPS system will synchronize to its own
bypass source.
Page 28 of 130
The System Bypass Cabinet shall provide a manual two breaker operated external
maintenance bypass with keyed interlocks for safe operation. The System Bypass shall be
capable of routing the utility or bypass source completely around the UPS modules, effectively
isolating the UPS modules. The bussing shall accommodate landing space for up to four UPS
modules and input and out sources of up to 1200 A.
The System Bypass Cabinet shall be outfitted with instrumentation to display the combined
system level input power from the utility / bypass source and output power from the UPS
module system. In the event that the power characteristics of either source or load fall out of
tolerance the monitoring system shall provide an audible and visible alarm which should also be
accompanied by the activation of a dry contact relay.
The System Bypass Cabinet will include a standard monitor system for metering and display of
the system level input/ utility and output/PS power. The monitor shall display the voltage,
current, kVA, kW and frequency and other parameters defined below. All measured values will
be displayed on a large format LCD display mounted on the front of cabinet. The meter shall
also be equipped with LED alarm status indication. All metered values will be in "true RMS"
values with 0.35% accuracy. All values and alarms shall be accessible via the monitoring
systems RS232 and RS485 serial ports using a standard ModBus protocol. The monitor shall
include a keypad allowing for the viewing of different selected values. The monitor shall display
the following values and alarm conditions via the LCD display:
Measured Values:
kWh Energy Consumption
kW Real Power
kVAR Reactive Power
kVA Apparent Power
Power Factor Total
Voltage, L-L, ave. of 3 phases
Voltage, L-N, ave. of 3 phases
Current, average of 3 phases
Kw Real Power, phase A, B, C
Power Factor, phase A, B, C
Line to Line Voltage, phase A-B
Line to Line Voltage, phase B-C
Line to Line Voltage, phase A-C
Line to Neutral Voltage, phase A-N
Line to Neutral Voltage, phase B-N
Line to Neutral Voltage, phase C-N
Current, phase A, B, C
kW Average
kW Minimum
Frequency (measured from phase A)
Alarmed Parameters:
Over Voltage
Under Voltage
Over Current
Under Current
Over KVA
Under KVA
Phase Loss A
Phase Loss B
Phase Loss C
Page 29 of 130
7.0 FIELD SERVICE ENGINEER QUALIFICATIONS
The manufacturer must provide rapid access to service requests in all regions of the nation and must
be capable of reaching any metropolitan area in less than four hours in normal conditions. Service
personnel must be accessible on a 7 x 24 basis throughout every day of the year.
The responding service professionals must be factory-trained engineers with a accredited and proven
competence to service three phase UPS systems and must be exclusively dedicated to servicing
critical power systems. Substitution of third party service personnel employed in fields outside of
critical power system service shall be unacceptable. The factory engineers must have immediate
access to any required spare parts on hand or via the nearest depot. Spare parts shall be accessible
on a 7 x 24 basis from the nearest depot and must be expedited on a next available flight basis or via
direct courier (whichever mode is quickest).
The manufacturer must provide continuous access to a manufacturer-operated customer service and
dispatch center. The dispatch center must be able to provide an immediate link to first level technical
support and prompt access to technicians for more advanced technical questions.
Page 30 of 130