Air System Sizing Summary for CHILLED WATER AHU

Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018


Prepared by: Siddique Ice and cold storage 12:34PM

Air System Information


Air System Name CHILLED WATER AHU Number of zones 1
Equipment Class CW AHU Floor Area 2920.0 ft²
Air System Type SZCAV Location ISLAMABAD, Pakistan

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 299.2 Tons Load occurs at Jun 1000
Total coil load 3589.9 MBH OA DB / WB 111.2 / 88.5 °F
Sensible coil load 2978.9 MBH Entering DB / WB 74.9 / 57.0 °F
Coil CFM at Jun 1000 71348 CFM Leaving DB / WB 36.2 / 35.0 °F
Max block CFM 71348 CFM Coil ADP 31.9 °F
Sum of peak zone CFM 71348 CFM Bypass Factor 0.100
Sensible heat ratio 0.830 Resulting RH 30 %
ft²/Ton 9.8 Design supply temp. 68.0 °F
BTU/(hr-ft²) 1229.4 Zone T-stat Check 1 of 1 OK
Water flow @ 5.0 °F rise 1436.74 gpm Max zone temperature deviation 0.0 °F

Central Heating Coil Sizing Data


Max coil load 2326.4 MBH Load occurs at Jun 0500
Coil CFM at Jun 0500 71348 CFM BTU/(hr-ft²) 796.7
Max coil CFM 71348 CFM Ent. DB / Lvg DB 35.7 / 65.9 °F
Water flow @ 20.0 °F drop 232.76 gpm

Supply Fan Sizing Data


Actual max CFM 71348 CFM Fan motor BHP n/a
Standard CFM 71314 CFM Fan motor kW 61.22 kW
Actual max CFM/ft² 24.43 CFM/ft²

Outdoor Ventilation Air Data


Design airflow CFM 1651 CFM CFM/person 7.34 CFM/person
CFM/ft² 0.57 CFM/ft²

Hourly Analysis Program v4.90 Page 1 of 46


Zone Sizing Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

Air System Information


Air System Name CHILLED WATER AHU Number of zones 1
Equipment Class CW AHU Floor Area 2920.0 ft²
Air System Type SZCAV Location ISLAMABAD, Pakistan

Sizing Calculation Information


Calculation Months Jan to Dec Zone CFM Sizing Sum of space airflow rates
Sizing Data Calculated Space CFM Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (MBH) (CFM) (CFM) Peak Load (MBH) (ft²) CFM/ft²
Zone 1 539.1 71348 71348 Jul 1600 75.0 2920.0 24.43

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
Zone 1
BUFFER 1 9.0 Jul 1600 1194 1.2 40.0 29.85
BUFFER 10 1 13.2 Jul 1600 1746 1.3 79.8 21.88
BUFFER 11 1 7.4 Jul 1600 976 1.3 20.0 48.80
BUFFER 12 1 7.3 Jul 1600 967 1.1 25.0 38.66
BUFFER 13 1 8.5 Jul 1600 1131 1.2 36.0 31.40
BUFFER 14 1 7.4 Jul 1600 976 1.3 20.0 48.80
BUFFER 15 1 6.9 Jul 1600 911 1.3 16.0 56.93
BUFFER 16 1 11.5 Jul 1600 1524 1.7 54.0 28.22
BUFFER 2 1 10.2 Jul 1600 1354 1.6 40.0 33.85
BUFFER 3 1 7.4 Jul 1600 973 1.3 20.0 48.67
BUFFER 4 1 7.9 Jul 1600 1050 1.5 20.0 52.49
BUFFER 5 1 9.6 Jul 1600 1267 1.4 40.0 31.66
BUFFER 6 1 9.0 Jul 1600 1191 1.2 40.0 29.77
BUFFER 7 1 9.9 Jul 1600 1312 1.2 48.4 27.10
BUFFER 8 1 13.6 Jul 1600 1794 1.7 72.0 24.91
BUFFER 9 1 13.8 Jul 1600 1830 1.5 79.8 22.94
CH1 1 7.9 Jul 1600 1046 1.3 25.0 41.83
CH2 1 7.9 Jul 1600 1046 1.3 25.0 41.83
CH3 1 7.3 Jul 1600 971 1.3 20.0 48.56
CH4 1 7.3 Jul 1600 971 1.3 20.0 48.56
D 1 9.1 Jul 1600 1201 1.2 40.5 29.64
DECARTIONING 1 20.2 Jul 1600 2676 2.4 86.0 31.12
ENTRANCE 1 27.1 Jul 1500 3591 1.8 208.0 17.26
Liquid filling space 1 37.2 Jul 1600 4920 13.3 218.8 22.49
MAIN ENTRANCE 1 16.0 Jul 1600 2117 2.0 90.0 23.52
OFF LOADING AREA 1 14.5 Jul 1600 1924 1.7 83.5 23.04
OFF LOADING AREA 2 1 13.2 Jul 1600 1743 1.5 72.9 23.91
OFF LOADING AREA B 1 14.6 Jul 1600 1928 1.7 83.5 23.09
PRODUCT OUT 1 36.0 Jul 1600 4766 3.6 216.0 22.06
PRODUCT OUT 2 1 17.9 Jul 1600 2365 2.3 54.0 43.80
SIDE ROOM 1 11.1 Jul 1600 1467 1.5 52.8 27.78
STERILE AMOULE FILLING 1 29.8 Jul 1600 3940 3.1 221.4 17.79
STERILE powder ville 1 26.7 Jul 1600 3530 2.8 171.2 20.62
STERILLIZATION 1 30.9 Jul 1600 4089 3.2 240.0 17.04

Hourly Analysis Program v4.90 Page 2 of 46


Zone Sizing Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (MBH) Load (CFM) (MBH) (ft²) CFM/ft²
VIAL WASHING 1 27.8 Jul 1600 3683 3.1 202.7 18.17
WFI FILTRATION 1 24.0 Jul 1600 3180 2.5 137.7 23.09

Hourly Analysis Program v4.90 Page 3 of 46


Ventilation Sizing Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
Design Ventilation Airflow Rate 1651 CFM

2. Space Ventilation Analysis Table


Floor Maximum Required Required Required Required Uncorrected
Area Maximum Supply Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air Outdoor Air
Zone Name / Space Name Mult. (ft²) Occupants (CFM) (CFM/person) (CFM/ft²) (CFM) (% of supply) (CFM)
Zone 1
BUFFER 1 40.0 5.0 1194.0 5.00 0.18 0.0 0.0 32.2
BUFFER 10 1 79.8 5.0 1746.4 5.00 0.18 0.0 0.0 39.4
BUFFER 11 1 20.0 5.0 976.0 5.00 0.18 0.0 0.0 28.6
BUFFER 12 1 25.0 5.0 966.6 5.00 0.18 0.0 0.0 29.5
BUFFER 13 1 36.0 5.0 1130.6 5.00 0.18 0.0 0.0 31.5
BUFFER 14 1 20.0 5.0 976.0 5.00 0.18 0.0 0.0 28.6
BUFFER 15 1 16.0 5.0 910.9 5.00 0.18 0.0 0.0 27.9
BUFFER 16 1 54.0 5.0 1523.9 5.00 0.18 0.0 0.0 34.7
BUFFER 2 1 40.0 5.0 1353.9 5.00 0.18 0.0 0.0 32.2
BUFFER 3 1 20.0 5.0 973.5 5.00 0.18 0.0 0.0 28.6
BUFFER 4 1 20.0 5.0 1049.7 5.00 0.18 0.0 0.0 28.6
BUFFER 5 1 40.0 5.0 1266.6 5.00 0.18 0.0 0.0 32.2
BUFFER 6 1 40.0 5.0 1191.0 5.00 0.18 0.0 0.0 32.2
BUFFER 7 1 48.4 5.0 1311.8 5.00 0.18 0.0 0.0 33.7
BUFFER 8 1 72.0 5.0 1793.6 5.00 0.18 0.0 0.0 38.0
BUFFER 9 1 79.8 5.0 1830.3 5.00 0.18 0.0 0.0 39.4
CH1 1 25.0 5.0 1045.8 5.00 0.18 0.0 0.0 29.5
CH2 1 25.0 5.0 1045.8 5.00 0.18 0.0 0.0 29.5
CH3 1 20.0 5.0 971.1 5.00 0.18 0.0 0.0 28.6
CH4 1 20.0 5.0 971.1 5.00 0.18 0.0 0.0 28.6
D 1 40.5 5.0 1200.5 5.00 0.18 0.0 0.0 32.3
DECARTIONING 1 86.0 10.0 2676.4 5.00 0.18 0.0 0.0 65.5
ENTRANCE 1 208.0 5.0 3591.0 5.00 0.18 0.0 0.0 62.4
Liquid filling space 1 218.8 10.0 4919.9 5.00 0.18 0.0 0.0 89.4
MAIN ENTRANCE 1 90.0 5.0 2117.2 5.00 0.18 0.0 0.0 41.2
OFF LOADING AREA 1 83.5 5.0 1923.9 5.00 0.18 0.0 0.0 40.0
OFF LOADING AREA 2 1 72.9 5.0 1743.0 5.00 0.18 0.0 0.0 38.1
OFF LOADING AREA B 1 83.5 5.0 1928.0 5.00 0.18 0.0 0.0 40.0
PRODUCT OUT 1 216.0 10.0 4765.6 5.00 0.18 0.0 0.0 88.9
PRODUCT OUT 2 1 54.0 10.0 2365.2 5.00 0.18 0.0 0.0 59.7
SIDE ROOM 1 52.8 5.0 1466.8 5.00 0.18 0.0 0.0 34.5
STERILE AMOULE FILLING 1 221.4 10.0 3939.5 5.00 0.18 0.0 0.0 89.9
STERILE powder ville 1 171.2 10.0 3530.1 5.00 0.18 0.0 0.0 80.8
STERILLIZATION 1 240.0 10.0 4089.4 5.00 0.18 0.0 0.0 93.2
VIAL WASHING 1 202.7 10.0 3683.1 5.00 0.18 0.0 0.0 86.5
WFI FILTRATION 1 137.7 10.0 3179.7 5.00 0.18 0.0 0.0 74.8

Hourly Analysis Program v4.90 Page 4 of 46


Ventilation Sizing Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

Totals (incl. Space Multipliers) 71347.8 1650.6

Hourly Analysis Program v4.90 Page 5 of 46


Air System Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jun 1000 HEATING DATA AT DES HTG
COOLING OA DB / WB 111.2 °F / 88.5 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 125 ft² 2603 - 125 ft² - -
Wall Transmission 9358 ft² 23361 - 9358 ft² 13289 -
Roof Transmission 4245 ft² 64849 - 4245 ft² 32768 -
Window Transmission 125 ft² 1700 - 125 ft² 1194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 1680 ft² 37065 - 1680 ft² 17500 -
Floor Transmission 2397 ft² 10786 - 2397 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 3533 W 12055 - 0 0 -
Task Lighting 3504 W 11955 - 0 0 -
Electric Equipment 6496 W 22166 - 0 0 -
People 225 55124 46125 0 0 0
Infiltration - 183565 418141 - 10235 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 425228 464266 - 74986 1
Zone Conditioning - 432045 464266 - 67975 1
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 71348 CFM 0 - 71348 CFM 0 -
Ventilation Load 1651 CFM 66099 146765 1651 CFM 42973 2
Supply Fan Load 71348 CFM 208900 - 71348 CFM -208900 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 707044 611031 - -97953 3
Central Cooling Coil - 2978910 611031 - -97953 0
Central Heating Coil - -2271866 - - 0 -
>> Total Conditioning - 707044 611031 - -97953 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 6 of 46


Zone Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

Zone 1 DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 125 ft² 2846 - 125 ft² - -
Wall Transmission 9358 ft² 23953 - 9358 ft² 13289 -
Roof Transmission 4245 ft² 126683 - 4245 ft² 32768 -
Window Transmission 125 ft² 2023 - 125 ft² 1194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 1680 ft² 45165 - 1680 ft² 17500 -
Floor Transmission 2397 ft² 10786 - 2397 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 3533 W 12055 - 0 0 -
Task Lighting 3504 W 11955 - 0 0 -
Electric Equipment 6496 W 22166 - 0 0 -
People 225 55124 46125 0 0 0
Infiltration - 226309 409339 - 10235 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 539065 455464 - 74986 1

Hourly Analysis Program v4.90 Page 7 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' BUFFER '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 210 ft² 545 - 210 ft² 298 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 642 - 24 ft² 250 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 48 W 165 - 0 0 -
Task Lighting 48 W 164 - 0 0 -
Electric Equipment 80 W 273 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3337 6035 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9022 7060 - 1193 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' BUFFER '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 45 0.057 - 110 - 64
S EXPOSURE
WALL 45 0.057 - 105 - 64
E EXPOSURE
WALL 48 0.057 - 137 - 68
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 72 0.057 - 193 - 102
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 8 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' BUFFER 10 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 307 ft² 800 - 307 ft² 436 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 642 - 24 ft² 250 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 97 W 329 - 0 0 -
Task Lighting 96 W 327 - 0 0 -
Electric Equipment 160 W 545 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6656 12040 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13196 13065 - 1331 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' BUFFER 10 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 63 0.057 - 153 - 89
S EXPOSURE
WALL 63 0.057 - 147 - 89
E EXPOSURE
WALL 79 0.057 - 224 - 112
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 103 0.057 - 275 - 146
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 9 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' BUFFER 11 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 114 ft² 288 - 114 ft² 162 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1310 - 48 ft² 500 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7375 4043 - 1307 0

TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' BUFFER 11 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 36 0.057 - 88 - 51
S EXPOSURE
WALL 36 0.057 - 84 - 51
E EXPOSURE
WALL 21 0.057 - 60 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 21 0.057 - 56 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 10 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' BUFFER 12 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 156 ft² 408 - 156 ft² 222 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 627 - 24 ft² 250 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 30 W 103 - 0 0 -
Task Lighting 30 W 102 - 0 0 -
Electric Equipment 50 W 171 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 2085 3772 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7304 4797 - 1116 0

TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' BUFFER 12 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 45 0.057 - 110 - 64
S EXPOSURE
WALL 21 0.057 - 49 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 45 0.057 - 128 - 64
W EXPOSURE
WALL 45 0.057 - 121 - 64
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 11 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' BUFFER 13 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 210 ft² 564 - 210 ft² 298 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 627 - 24 ft² 250 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 44 W 149 - 0 0 -
Task Lighting 43 W 147 - 0 0 -
Electric Equipment 72 W 246 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3003 5432 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 8543 6457 - 1193 0

TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' BUFFER 13 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 36 0.057 - 88 - 51
S EXPOSURE
WALL 12 0.057 - 28 - 17
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 81 0.057 - 231 - 115
W EXPOSURE
WALL 81 0.057 - 217 - 115
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 12 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' BUFFER 14 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 114 ft² 288 - 114 ft² 162 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1310 - 48 ft² 500 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7375 4043 - 1307 0

TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' BUFFER 14 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 36 0.057 - 88 - 51
S EXPOSURE
WALL 36 0.057 - 84 - 51
E EXPOSURE
WALL 21 0.057 - 60 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 21 0.057 - 56 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 13 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' BUFFER 15 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 96 ft² 256 - 96 ft² 136 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1262 - 48 ft² 500 -
Floor Transmission 16 ft² 72 - 16 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 19 W 66 - 0 0 -
Task Lighting 19 W 66 - 0 0 -
Electric Equipment 32 W 109 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1335 2414 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 6883 3439 - 1281 0

TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' BUFFER 15 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 12 0.057 - 29 - 17
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 12 0.057 - 28 - 17
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 36 0.057 - 102 - 51
W EXPOSURE
WALL 36 0.057 - 97 - 51
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 14 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' BUFFER 16 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 198 ft² 512 - 198 ft² 281 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1897 - 72 ft² 750 -
Floor Transmission 16 ft² 72 - 16 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 65 W 223 - 0 0 -
Task Lighting 65 W 221 - 0 0 -
Electric Equipment 108 W 368 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 4504 8147 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 11515 9172 - 1676 0

TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' BUFFER 16 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 33 0.057 - 80 - 47
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 422 290
S EXPOSURE
WALL 57 0.057 - 133 - 81
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 54 0.057 - 154 - 77
W EXPOSURE
WALL 54 0.057 - 145 - 77
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 15 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' BUFFER 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 162 ft² 416 - 162 ft² 230 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1979 - 72 ft² 750 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 48 W 165 - 0 0 -
Task Lighting 48 W 164 - 0 0 -
Electric Equipment 80 W 273 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3337 6035 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 10231 7060 - 1625 0

TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' BUFFER 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 45 0.057 - 110 - 64
S EXPOSURE
WALL 45 0.057 - 105 - 64
E EXPOSURE
WALL 48 0.057 - 137 - 68
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 24 0.057 - 64 - 34
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 490 290
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 16 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' BUFFER 3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 106 ft² 269 - 106 ft² 151 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1310 - 48 ft² 500 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7356 4043 - 1295 0

TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' BUFFER 3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 32 0.057 - 78 - 45
S EXPOSURE
WALL 32 0.057 - 75 - 45
E EXPOSURE
WALL 21 0.057 - 60 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 21 0.057 - 56 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 17 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' BUFFER 4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 82 ft² 210 - 82 ft² 116 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1945 - 72 ft² 750 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7932 4043 - 1511 0

TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' BUFFER 4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 8 0.057 - 19 - 11
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 32 0.057 - 75 - 45
E EXPOSURE
WALL 21 0.057 - 60 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 21 0.057 - 56 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 18 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' BUFFER 5 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 186 ft² 480 - 186 ft² 264 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1255 - 48 ft² 500 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 48 W 165 - 0 0 -
Task Lighting 48 W 164 - 0 0 -
Electric Equipment 80 W 273 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3337 6035 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9571 7060 - 1409 0

TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' BUFFER 5 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 72 0.057 - 175 - 102
S EXPOSURE
WALL 24 0.057 - 56 - 34
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 408 290
E EXPOSURE
WALL 45 0.057 - 128 - 64
W EXPOSURE
WALL 45 0.057 - 121 - 64
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 19 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' BUFFER 6 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 210 ft² 536 - 210 ft² 298 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 627 - 24 ft² 250 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 48 W 165 - 0 0 -
Task Lighting 48 W 164 - 0 0 -
Electric Equipment 80 W 273 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3337 6035 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9000 7060 - 1193 0

TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' BUFFER 6 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 72 0.057 - 175 - 102
S EXPOSURE
WALL 48 0.057 - 112 - 68
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 45 0.057 - 128 - 64
W EXPOSURE
WALL 45 0.057 - 121 - 64
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 20 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' BUFFER 7 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 246 ft² 608 - 246 ft² 349 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 642 - 24 ft² 250 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 59 W 200 - 0 0 -
Task Lighting 58 W 198 - 0 0 -
Electric Equipment 97 W 330 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 4037 7302 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9913 8327 - 1244 0

TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' BUFFER 7 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 93 0.057 - 226 - 132
S EXPOSURE
WALL 93 0.057 - 217 - 132
E EXPOSURE
WALL 18 0.057 - 52 - 26
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 42 0.057 - 114 - 60
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 21 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.15.A. COMPONENT LOADS FOR SPACE '' BUFFER 8 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 234 ft² 588 - 234 ft² 332 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1979 - 72 ft² 750 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 87 W 297 - 0 0 -
Task Lighting 86 W 295 - 0 0 -
Electric Equipment 144 W 491 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6006 10863 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13553 11888 - 1727 0

TABLE 1.15.B. ENVELOPE LOADS FOR SPACE '' BUFFER 8 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 81 0.057 - 197 - 115
S EXPOSURE
WALL 81 0.057 - 189 - 115
E EXPOSURE
WALL 48 0.057 - 137 - 68
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 24 0.057 - 64 - 34
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 490 290
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 22 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.16.A. COMPONENT LOADS FOR SPACE '' BUFFER 9 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 283 ft² 739 - 283 ft² 402 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1337 - 48 ft² 500 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 97 W 329 - 0 0 -
Task Lighting 96 W 327 - 0 0 -
Electric Equipment 160 W 545 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6656 12040 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13831 13065 - 1547 0

TABLE 1.16.B. ENVELOPE LOADS FOR SPACE '' BUFFER 9 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 63 0.057 - 153 - 89
S EXPOSURE
WALL 63 0.057 - 147 - 89
E EXPOSURE
WALL 103 0.057 - 292 - 146
W EXPOSURE
WALL 55 0.057 - 147 - 78
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 490 290
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 23 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.17.A. COMPONENT LOADS FOR SPACE '' CH1 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 132 ft² 349 - 132 ft² 187 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1262 - 48 ft² 500 -
Floor Transmission 25 ft² 112 - 25 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 30 W 103 - 0 0 -
Task Lighting 30 W 102 - 0 0 -
Electric Equipment 50 W 171 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 2085 3772 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7903 4797 - 1332 0

TABLE 1.17.B. ENVELOPE LOADS FOR SPACE '' CH1 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 21 0.057 - 51 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 21 0.057 - 49 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 45 0.057 - 128 - 64
W EXPOSURE
WALL 45 0.057 - 121 - 64
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 24 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.18.A. COMPONENT LOADS FOR SPACE '' CH2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 132 ft² 349 - 132 ft² 187 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1262 - 48 ft² 500 -
Floor Transmission 25 ft² 112 - 25 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 30 W 103 - 0 0 -
Task Lighting 30 W 102 - 0 0 -
Electric Equipment 50 W 171 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 2085 3772 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7903 4797 - 1332 0

TABLE 1.18.B. ENVELOPE LOADS FOR SPACE '' CH2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 21 0.057 - 51 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 21 0.057 - 49 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 45 0.057 - 128 - 64
W EXPOSURE
WALL 45 0.057 - 121 - 64
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 25 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.19.A. COMPONENT LOADS FOR SPACE '' CH3 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 114 ft² 299 - 114 ft² 162 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1262 - 48 ft² 500 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7338 4043 - 1307 0

TABLE 1.19.B. ENVELOPE LOADS FOR SPACE '' CH3 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 21 0.057 - 51 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 21 0.057 - 49 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 36 0.057 - 102 - 51
W EXPOSURE
WALL 36 0.057 - 97 - 51
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 26 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.20.A. COMPONENT LOADS FOR SPACE '' CH4 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 114 ft² 299 - 114 ft² 162 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1262 - 48 ft² 500 -
Floor Transmission 20 ft² 90 - 20 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 24 W 83 - 0 0 -
Task Lighting 24 W 82 - 0 0 -
Electric Equipment 40 W 136 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 1668 3018 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7338 4043 - 1307 0

TABLE 1.20.B. ENVELOPE LOADS FOR SPACE '' CH4 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 21 0.057 - 51 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 21 0.057 - 49 - 30
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 36 0.057 - 102 - 51
W EXPOSURE
WALL 36 0.057 - 97 - 51
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 27 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.21.A. COMPONENT LOADS FOR SPACE '' D '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 210 ft² 545 - 210 ft² 298 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 642 - 24 ft² 250 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 49 W 167 - 0 0 -
Task Lighting 49 W 166 - 0 0 -
Electric Equipment 81 W 276 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 3378 6111 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 9072 7136 - 1193 0

TABLE 1.21.B. ENVELOPE LOADS FOR SPACE '' D '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 45 0.057 - 110 - 64
S EXPOSURE
WALL 45 0.057 - 105 - 64
E EXPOSURE
WALL 48 0.057 - 137 - 68
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 72 0.057 - 193 - 102
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 28 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.22.A. COMPONENT LOADS FOR SPACE '' DECARTIONING '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 311 ft² 801 - 311 ft² 441 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 627 - 24 ft² 250 -
Floor Transmission 86 ft² 387 - 86 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 104 W 355 - 0 0 -
Task Lighting 103 W 352 - 0 0 -
Electric Equipment 172 W 587 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 8056 14571 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 20224 16621 - 2401 0

TABLE 1.22.B. ENVELOPE LOADS FOR SPACE '' DECARTIONING '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 90 0.057 - 219 - 128
S EXPOSURE
WALL 66 0.057 - 154 - 94
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 77 0.057 - 220 - 110
W EXPOSURE
WALL 77 0.057 - 208 - 110
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 29 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.23.A. COMPONENT LOADS FOR SPACE '' ENTRANCE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 120.0 °F / 90.0 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 270 ft² 703 - 270 ft² 383 -
Roof Transmission 84 ft² 2406 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1978 - 72 ft² 750 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 252 W 859 - 0 0 -
Task Lighting 250 W 852 - 0 0 -
Electric Equipment 416 W 1419 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 17514 31367 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 27135 32392 - 1778 0

TABLE 1.23.B. ENVELOPE LOADS FOR SPACE '' ENTRANCE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 54 0.057 - 131 - 77
S EXPOSURE
WALL 54 0.057 - 126 - 77
E EXPOSURE
WALL 93 0.057 - 262 - 132
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 225 145
W EXPOSURE
WALL 69 0.057 - 185 - 98
DOOR 28 0.300 - 357 - 210
DOOR GLASS 20 0.580 0.880 493 478 290
H EXPOSURE
ROOF 84 0.309 - 2406 - 645

Hourly Analysis Program v4.90 Page 30 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.24.A. COMPONENT LOADS FOR SPACE '' Liquid filling space '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 25 ft² 562 - 25 ft² - -
Wall Transmission 465 ft² 1204 - 465 ft² 661 -
Roof Transmission 219 ft² 6523 - 219 ft² 1689 -
Window Transmission 25 ft² 404 - 25 ft² 239 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1267 - 48 ft² 500 -
Floor Transmission 219 ft² 985 - 219 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 265 W 903 - 0 0 -
Task Lighting 263 W 896 - 0 0 -
Electric Equipment 1094 W 3733 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 18251 33012 - 10235 1
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 37177 35062 - 13324 1

TABLE 1.24.B. ENVELOPE LOADS FOR SPACE '' Liquid filling space '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 103 0.057 - 251 - 146
WINDOW 1 25 0.382 0.805 404 562 239
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 207 145
E EXPOSURE
WALL 128 0.057 - 365 - 182
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 214 145
W EXPOSURE
WALL 117 0.057 - 314 - 166
S EXPOSURE
WALL 117 0.057 - 274 - 166
H EXPOSURE
ROOF 219 0.309 - 6523 - 1689

Hourly Analysis Program v4.90 Page 31 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.25.A. COMPONENT LOADS FOR SPACE '' MAIN ENTRANCE '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 246 ft² 619 - 246 ft² 349 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 96 ft² 2621 - 96 ft² 1000 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 109 W 372 - 0 0 -
Task Lighting 108 W 368 - 0 0 -
Electric Equipment 180 W 614 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 7507 13579 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 15999 14604 - 1994 0

TABLE 1.25.B. ENVELOPE LOADS FOR SPACE '' MAIN ENTRANCE '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 81 0.057 - 197 - 115
S EXPOSURE
WALL 81 0.057 - 189 - 115
E EXPOSURE
WALL 42 0.057 - 120 - 60
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 436 290
W EXPOSURE
WALL 42 0.057 - 113 - 60
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 490 290
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 32 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.26.A. COMPONENT LOADS FOR SPACE '' OFF LOADING AREA '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 386 ft² 947 - 386 ft² 548 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1277 - 48 ft² 500 -
Floor Transmission 84 ft² 376 - 84 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 101 W 345 - 0 0 -
Task Lighting 100 W 342 - 0 0 -
Electric Equipment 167 W 570 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6965 12598 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14538 13623 - 1693 0

TABLE 1.26.B. ENVELOPE LOADS FOR SPACE '' OFF LOADING AREA '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 143 0.057 - 348 - 203
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 167 0.057 - 391 - 237
E EXPOSURE
WALL 26 0.057 - 74 - 37
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 50 0.057 - 134 - 71
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 33 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.27.A. COMPONENT LOADS FOR SPACE '' OFF LOADING AREA 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 281 ft² 701 - 281 ft² 398 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1303 - 48 ft² 500 -
Floor Transmission 60 ft² 272 - 60 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 88 W 301 - 0 0 -
Task Lighting 87 W 298 - 0 0 -
Electric Equipment 146 W 497 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6081 10999 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 13171 12024 - 1543 0

TABLE 1.27.B. ENVELOPE LOADS FOR SPACE '' OFF LOADING AREA 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 65 0.057 - 158 - 92
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 130 0.057 - 303 - 184
E EXPOSURE
WALL 55 0.057 - 156 - 78
W EXPOSURE
WALL 31 0.057 - 83 - 44
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 34 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.28.A. COMPONENT LOADS FOR SPACE '' OFF LOADING AREA B '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 386 ft² 951 - 386 ft² 548 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1303 - 48 ft² 500 -
Floor Transmission 84 ft² 376 - 84 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 101 W 345 - 0 0 -
Task Lighting 100 W 342 - 0 0 -
Electric Equipment 167 W 570 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 6965 12598 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 14569 13623 - 1693 0

TABLE 1.28.B. ENVELOPE LOADS FOR SPACE '' OFF LOADING AREA B '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 143 0.057 - 348 - 203
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 167 0.057 - 391 - 237
E EXPOSURE
WALL 50 0.057 - 142 - 71
W EXPOSURE
WALL 26 0.057 - 70 - 37
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 35 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.29.A. COMPONENT LOADS FOR SPACE '' PRODUCT OUT '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 25 ft² 571 - 25 ft² - -
Wall Transmission 659 ft² 1599 - 659 ft² 936 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 25 ft² 405 - 25 ft² 239 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1965 - 72 ft² 750 -
Floor Transmission 216 ft² 972 - 216 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 261 W 892 - 0 0 -
Task Lighting 259 W 884 - 0 0 -
Electric Equipment 432 W 1474 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 18191 32903 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 36011 34953 - 3634 0

TABLE 1.29.B. ENVELOPE LOADS FOR SPACE '' PRODUCT OUT '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 299 0.057 - 728 - 425
WINDOW 1 25 0.382 0.805 405 571 239
S EXPOSURE
WALL 300 0.057 - 702 - 426
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 54 0.057 - 154 - 77
W EXPOSURE
WALL 6 0.057 - 16 - 9
DOOR 28 0.300 - 356 - 210
DOOR GLASS 20 0.580 0.880 491 490 290
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 36 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.30.A. COMPONENT LOADS FOR SPACE '' PRODUCT OUT 2 '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 246 ft² 627 - 246 ft² 349 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 635 - 24 ft² 250 -
Floor Transmission 54 ft² 243 - 54 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 65 W 223 - 0 0 -
Task Lighting 65 W 221 - 0 0 -
Electric Equipment 108 W 368 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 6497 11751 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 17872 13801 - 2309 0

TABLE 1.30.B. ENVELOPE LOADS FOR SPACE '' PRODUCT OUT 2 '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 57 0.057 - 139 - 81
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 81 0.057 - 189 - 115
E EXPOSURE
WALL 54 0.057 - 154 - 77
W EXPOSURE
WALL 54 0.057 - 145 - 77
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 37 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.31.A. COMPONENT LOADS FOR SPACE '' SIDE ROOM '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 254 ft² 677 - 254 ft² 360 -
Roof Transmission 84 ft² 2492 - 84 ft² 645 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1310 - 48 ft² 500 -
Floor Transmission 40 ft² 180 - 40 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 64 W 218 - 0 0 -
Task Lighting 63 W 216 - 0 0 -
Electric Equipment 106 W 360 - 0 0 -
People 5 1225 1025 0 0 0
Infiltration - 4404 7966 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 11084 8991 - 1505 0

TABLE 1.31.B. ENVELOPE LOADS FOR SPACE '' SIDE ROOM '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 32 0.057 - 78 - 45
S EXPOSURE
WALL 32 0.057 - 75 - 45
E EXPOSURE
WALL 95 0.057 - 270 - 135
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 95 0.057 - 255 - 135
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 84 0.309 - 2492 - 645

Hourly Analysis Program v4.90 Page 38 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.32.A. COMPONENT LOADS FOR SPACE '' STERILE AMOULE FILLING '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 25 ft² 571 - 25 ft² - -
Wall Transmission 465 ft² 1188 - 465 ft² 661 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 25 ft² 405 - 25 ft² 239 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1269 - 48 ft² 500 -
Floor Transmission 221 ft² 996 - 221 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 268 W 914 - 0 0 -
Task Lighting 266 W 906 - 0 0 -
Electric Equipment 443 W 1511 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 12950 23424 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 29769 25474 - 3109 0

TABLE 1.32.B. ENVELOPE LOADS FOR SPACE '' STERILE AMOULE FILLING '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 127 0.057 - 309 - 180
WINDOW 1 25 0.382 0.805 405 571 239
S EXPOSURE
WALL 128 0.057 - 300 - 182
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 93 0.057 - 265 - 132
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 218 145
W EXPOSURE
WALL 117 0.057 - 314 - 166
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 39 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.33.A. COMPONENT LOADS FOR SPACE '' STERILE powder ville '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 25 ft² 571 - 25 ft² - -
Wall Transmission 432 ft² 1103 - 432 ft² 613 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 25 ft² 405 - 25 ft² 239 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 627 - 24 ft² 250 -
Floor Transmission 171 ft² 770 - 171 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 207 W 707 - 0 0 -
Task Lighting 205 W 701 - 0 0 -
Electric Equipment 342 W 1168 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 11564 20917 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 26675 22967 - 2811 0

TABLE 1.33.B. ENVELOPE LOADS FOR SPACE '' STERILE powder ville '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 119 0.057 - 290 - 169
WINDOW 1 25 0.382 0.805 405 571 239
S EXPOSURE
WALL 120 0.057 - 281 - 170
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 96 0.057 - 274 - 137
W EXPOSURE
WALL 96 0.057 - 259 - 137
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 40 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.34.A. COMPONENT LOADS FOR SPACE '' STERILLIZATION '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 25 ft² 571 - 25 ft² - -
Wall Transmission 503 ft² 1330 - 503 ft² 714 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 25 ft² 405 - 25 ft² 239 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 48 ft² 1296 - 48 ft² 500 -
Floor Transmission 171 ft² 770 - 171 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 290 W 991 - 0 0 -
Task Lighting 288 W 983 - 0 0 -
Electric Equipment 480 W 1638 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 13860 25069 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 30901 27119 - 3162 0

TABLE 1.34.B. ENVELOPE LOADS FOR SPACE '' STERILLIZATION '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 83 0.057 - 202 - 118
WINDOW 1 25 0.382 0.805 405 571 239
S EXPOSURE
WALL 84 0.057 - 196 - 119
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 180 0.057 - 512 - 256
W EXPOSURE
WALL 156 0.057 - 419 - 222
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 41 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.35.A. COMPONENT LOADS FOR SPACE '' VIAL WASHING '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 425 ft² 1068 - 425 ft² 603 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 72 ft² 1931 - 72 ft² 750 -
Floor Transmission 171 ft² 770 - 171 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 245 W 837 - 0 0 -
Task Lighting 243 W 830 - 0 0 -
Electric Equipment 405 W 1383 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 11954 21622 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 27831 23672 - 3063 0

TABLE 1.35.B. ENVELOPE LOADS FOR SPACE '' VIAL WASHING '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 143 0.057 - 349 - 204
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 211 145
S EXPOSURE
WALL 143 0.057 - 335 - 204
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 204 145
E EXPOSURE
WALL 81 0.057 - 231 - 115
W EXPOSURE
WALL 57 0.057 - 153 - 81
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 42 of 46


Space Design Load Summary for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

TABLE 1.36.A. COMPONENT LOADS FOR SPACE '' WFI FILTRATION '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 119.6 °F / 89.9 °F HEATING OA DB / WB 45.0 °F / 40.0 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 413 ft² 1084 - 413 ft² 587 -
Roof Transmission 221 ft² 6608 - 221 ft² 1709 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 24 ft² 669 - 24 ft² 250 -
Floor Transmission 138 ft² 620 - 138 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 167 W 568 - 0 0 -
Task Lighting 165 W 564 - 0 0 -
Electric Equipment 275 W 940 - 0 0 -
People 10 2450 2050 0 0 0
Infiltration - 10525 19037 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 24027 21087 - 2546 0

TABLE 1.36.B. ENVELOPE LOADS FOR SPACE '' WFI FILTRATION '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 81 0.057 - 197 - 115
S EXPOSURE
WALL 81 0.057 - 189 - 115
E EXPOSURE
WALL 138 0.057 - 392 - 196
W EXPOSURE
WALL 114 0.057 - 305 - 161
DOOR 14 0.300 - 178 - 105
DOOR GLASS 10 0.580 0.880 246 245 145
H EXPOSURE
ROOF 221 0.309 - 6608 - 1709

Hourly Analysis Program v4.90 Page 43 of 46


System Psychrometrics for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

June DESIGN COOLING DAY, 1000

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 111.2 0.02408 1651 400 66099 146765
Vent - Return Mixing Outlet 74.9 0.00577 71348 801 - -
Central Cooling Coil Outlet 36.2 0.00397 71348 801 2978910 611031
Central Heating Coil Outlet 65.7 0.00397 71348 801 2271866 -
Supply Fan Outlet 68.5 0.00397 71348 801 208900 -
Cold Supply Duct Outlet 68.5 0.00397 71348 801 - -
Zone Air - 74.1 0.00534 71348 811 432045 464266
Return Plenum Outlet 74.1 0.00534 71348 811 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4744.4 BTU/(hr-CFM)
Site Altitude = 13.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 425228 Deadband 432045 74.1 71348 811 0 0

Hourly Analysis Program v4.90 Page 44 of 46


System Psychrometrics for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

WINTER DESIGN HEATING

TABLE 1: SYSTEM DATA

Dry-Bulb Specific Sensible Latent


Temp Humidity Airflow CO2 Level Heat Heat
Component Location (°F) (lb/lb) (CFM) (ppm) (BTU/hr) (BTU/hr)
Ventilation Air Inlet 45.0 0.00406 1651 400 -42973 -2
Vent - Return Mixing Outlet 68.6 0.00406 71348 791 - -
Central Cooling Coil Outlet 67.3 0.00406 71348 791 97953 0
Central Heating Coil Outlet 67.3 0.00406 71348 791 0 -
Supply Fan Outlet 70.0 0.00406 71348 791 208900 -
Cold Supply Duct Outlet 70.0 0.00406 71348 791 - -
Zone Air - 69.1 0.00406 71348 800 -67975 -1
Return Plenum Outlet 69.1 0.00406 71348 800 0 -

Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 1.079 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4744.4 BTU/(hr-CFM)
Site Altitude = 13.0 ft

TABLE 2: ZONE DATA

Zone Terminal Zone


Sensible Zone Zone Zone CO2 Heating Heating
Load T-stat Cond Temp Airflow Level Coil Unit
Zone Name (BTU/hr) Mode (BTU/hr) (°F) (CFM) (ppm) (BTU/hr) (BTU/hr)
Zone 1 -74986 Deadband -67975 69.1 71348 800 0 0

Hourly Analysis Program v4.90 Page 45 of 46


Psychrometric Analysis for CHILLED WATER AHU
Project Name: UPGRADATION OF EXISTING INJECTABLE AREA 12/18/2018
Prepared by: Siddique Ice and cold storage 12:34PM

Location: ISLAMABAD, Pakistan


Altitude: 13.0 ft.
Data for: June DESIGN COOLING DAY, 1000

1. Outdoor Air 1
2. Mixed Air
3. Central Cooling Coil Outlet 0.024
4. Central Heating Coil Outlet
5. Supply Fan Outlet
6. Room Air 0.022
0.020

Specific Humidity ( lb/lb )


0.018
0.016
0.014
0.012
0.010
0.008
2
6
0.006
3 4 5
0.004
0.002
0.000
30 40 50 60 70 80 90 100 110
Temperature ( °F )

Hourly Analysis Program v4.90 Page 46 of 46