Motor Savings Analysis - Replace Existing Page: 1

INPUTS
Motor Characteristics
Existing Motor Premium-Efficiency Motor
Description: Energy Efficient GE - Energy $aver ODP
- NEMA Design B
Size (HP) / Speed (RPM) (Poles): 100,0 HP 1800 RPM 100,0 HP 1800 RPM
Enclosure / Voltage (Volts): ODP 460 Volts ODP 460 Volts
Load (%): 57,4 57,4
Efficiency (%): 92,3 95,3
Full load RPM: 0 RPM 0 RPM
Centrifugal load: False
Old Motor Efficiency Loss (%): 0

Costs/Use
Existing Motor Premium-Efficiency Utility Data
Motor
Dealer discount (%): N/A 0 Energy price (COP/kWh): 619,890015
Purchase price (COP): N/A 12.634.752 Demand charge (COP/kW/mo.): 8
Installation cost (COP): N/A 1.404.216 Power factor (%): N/A
Motor rebate (COP): N/A 0 Rebate program: <None>
Peak months: 12 12 Simple payback criteria, yrs: 0
Hours use/yr: 5000 5000
RESULTS - SAVINGS
Existing Motor Premium-Efficiency Energy Savings
Motor
Differential cost (COP): 14.038.968 Energy (kWh/yr): 7.319
Energy use (kWh/yr): 231963 224644 Demand (kW): 1,5
Energy cost (COP/yr): 143.791.648 139.254.640 Energy savings (COP/yr): 4.537.006
Demand charge (COP/yr): 4.454 4.313 Demand savings (COP/yr): 141
Greenhouse Gas Emissions Reduction Total savings (COP/yr): 4.537.147
State: tonnes CO2/yr:: 0,00 Simple payback (yrs): 3,1

04/08/2019 copyright 2002 WSU