Equipment Base: Soft Solution Machine Foundation Irrigation Pump Shed-Pump Foundation

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 2

Soft Solution

Machine Foundation Equipment Base 1 2

A B C D E F G H I J K L M N O P
1 ISBN 8 Addendum to STQ 1503 NavigationIrrigation Pump Shed- Pump foundation
2 Machine Foundation - Design - Natural frequency of foundation soil system & amplitude check
3 References Barkan's formula to determine value of Az Cycles (f)/m v/s amplitude curves RPM in cycles amplitude in mm
4 Foundation parameters & v n 2.5 mm for 2900 rpm 2900 Az
5 Length Breadth Depth Concrete Foundation weight Machine m' EUCS Natural Frequency Operating Frequency OF/NF Soil density Amplitude
6 L B D Density Concrete Soil weight Mass(Total) cu cu*A v n h m h h Po Az
7 m m m kg/m^3 kg kg kg kg kg/m^2 (cu*A/m)^1/2 Manfacturer's datasheet # kg/cm^3 kgmf mm
8 1.6 1.6 0.35 2500 2240 358.4 990 365.79001 7680 19661 7.3313621385 2.83 0.386 1.6 2611 1.560622
9 m^3 0.896 Pump 395 by equation 1.0855 27788 8.7159723055 2.83 0.3247 1.6 2611 1.050376
10 Pump 395 [cu=1.13-E/(1-h ^2) /a^.5] Reference Cycles(f )/m v/s amplitude curves mm
11 cu' determined by both methods Method Vessel 100 Permissible amplitude 2.5
12 By' Elastic-Area' equation 1 Frame 100 Since' foundation soil system' amplitude is within limits, the foundation is safe in vibration
13 By 'soil bearing' table consideration 2
14 Sand Silt General principle
15 Soil E h h Coefficient A Cu [cu=1.13-E/(1-h ^2) /a^.5] Wherever possible, the operating frequency should be
16 Kg/cm^2 poisson's r poisson's in equation cm^2 Kg/cm^2 lower than the natural frequency of the foundation soil
17 2000 0.35 0.4 1.13 25600 1.0854843 system & preferably within ratio 0.5
18 L Foundation length m otherwise it should be more than 2
19 B Foundation breadth m In this case the ratio is 0.386 0.324691
20 D Foundation depth m
21 cu Soil elastic uniform compression coefficient for 10 m^2 foundation area 3 to 5 Kg/cm^2 Comparison
22 A Foundation area m^2 Frequency ratio Amplitude
23 h n Natural frequency of foundation soil system vibration Permisible Permisible
24 h m Operating frequency of machine vibration 0.5 2.5
25 h Operating frequency of machine vibration/Natural frequency of foundation soil system vibration Provided Provided
26 h Soil density kg/cm^3 0.3860128509 1.5606 1.050376
27 Po Exciting force produced vertically on machine kgmf Resonance shall not occur
28 Az Amplitude mm Design satisfies both conditions `
29 h Poisson's ratio
30 E Young's modulus of elasticity of foundation soil Kg/cm^2
31 m Combined mass of soil, foundation & machine Kg

ApplicationDeveloper
417474641.xls 21:32:1204/21/2019
PEng Suraj
Soft Solution
Machine Foundation Equipment Base 2 2

Q
1
2
3
4
5
6
7 Method
8 1
9 2
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31

ApplicationDeveloper
417474641.xls 21:32:1204/21/2019
PEng Suraj

You might also like